Voltage Drop Calculator — How Much Voltage Do You Lose on a Long Run?

Every wire is a resistor, and a long run is a long resistor. A 120 V circuit carrying 20 A over 100 ft of 12 AWG copper loses 7.90 V before it reaches the load — 6.58% of the supply — so the outlet at the far end sees 112.10 V, not 120 V. Lights dim, motors run hot, and a 12 V solar run loses the same percentage on a supply twelve times smaller, which is why low-voltage circuits are the ones that fail first. This voltage drop calculator works the drop out three ways at once: the volts lost and the percentage, the voltage that reaches the load and the watts lost as heat in the wire — and then it answers the two questions that follow, which wire is the smallest that holds your target percentage, and how long a run that wire allows. It does it for DC, single-phase and three-phase circuits, copper or aluminium, in AWG, kcmil or mm², from the two methods the field actually uses — NEC Chapter 9 Table 8 resistance and the K method — and it shows both, because the two methods disagree by 0.02 V on the canonical run and the disagreement is worth seeing. It also runs the check most calculators skip: ampacity first, drop second — 12 AWG carries 20 A on ampacity and still fails the drop test at 100 ft — and it grows the equipment grounding conductor with the phase conductors, the way 250.122(B) requires. For the rest of the circuit, price the running cost with the electricity cost calculator, size the load behind the run with the BTU calculator and the generator size calculator, check the heating with the heat pump size calculator and the radiator size calculator, and check the insulation the wire runs through with the insulation calculator.

Quick answer: A 120 V circuit carrying 20 A over 100 ft of 12 AWG copper loses 7.90 V — 6.58% of the supply, so 112.10 V reaches the load. That is more than double the NEC’s 3% branch-circuit recommendation, so the run needs 8 AWG (3.13 V, 2.60%) — even though 12 AWG is fine on ampacity (20 A on the 60 °C column). Enter your circuit below for your exact drop, the smallest wire that holds your target, and the longest run that wire allows.
Key takeaways
  • A 120 V, 20 A, 100 ft run on 12 AWG copper loses 7.90 V (6.58%) by the K method — 7.72 V solid, 7.92 V stranded by Table 8 — more than double the NEC’s 3% branch-circuit recommendation, so the run needs 8 AWG.
  • The K method and the Table 8 resistance method are the same formula: 7.90 V against 7.92 V on the canonical run — the 0.02 V gap is the rounded K constant (12.9), not a disagreement between methods.
  • Ampacity and voltage drop are two different checks: 12 AWG carries 20 A on ampacity (60 °C column) but fails the 3% drop test at 100 ft — and when the wire grows for drop, the equipment grounding conductor grows with it (250.122(B)).
  • 3% on a branch circuit and 5% total are NEC informational notes, not enforceable limits — the only enforceable drop limits are 1.5% / 2.5% on sensitive electronic equipment (647.4(D)) and the fire-pump rule (695.7).
  • One-way length is the trap: the current travels out and back, so a 100 ft run is 200 ft of wire — entering the round-trip length doubles the drop, and it is the most common error in the field’s calculators.
Three solvers in one. “Voltage drop” prices the wire you have. “Smallest wire size” finds the smallest wire that holds your target percentage. “Maximum length” finds the longest run your wire allows at that percentage. The other two answers are shown as extra lines either way.
DC and single-phase AC both use a multiplier of 2 — the current travels out on one conductor and back on the other, so the loop is twice the one-way length. A balanced three-phase circuit uses √3 (1.732) instead, and the drop is line-to-line.
The nominal supply voltage — the percentage drop is the volts lost divided by this number, so the same volts lost are a bigger percentage on 12 V than on 240 V. Pick “Custom” and enter your own voltage below for anything else (230 V, 400 V, 600 V).
Used only when the supply voltage above is “Custom”. Enter the nominal supply voltage in volts — 230 V for most of the world outside North America, 400 V for three-phase in Europe, 600 V for Canadian commercial. Leave it blank unless you picked “Custom”.
The current the load actually draws, in amps — not the breaker size. A 20 A circuit with a 16 A load drops 20% less than the same circuit at a full 20 A. For a continuous load the NEC sizes the conductor at 125% of the load (210.19(A)(1)) — enter the load current here and let the ampacity floor do the rest.
The ONE-WAY distance from the panel to the load — not the round trip. The tool doubles it internally (the current travels out and back), so a 100 ft run is 200 ft of wire. Entering the round-trip length here is the most common voltage-drop error: it doubles the answer.
Copper or aluminium. Aluminium has about 64% more resistance than copper at the same size (K 21.2 against 12.9), so the same run loses about 64% more volts — 13.00 V against 7.92 V on the canonical 12 AWG run — and aluminium needs a larger size to match copper: on the canonical run, 6 AWG aluminium where copper needs 8 AWG.
AWG and kcmil sizes use NEC Chapter 9 Table 8 (resistance at 75 °C, uncoated) and Table 310.16 (ampacity). mm² sizes use the K method only — there is no Table 8 resistance for metric sizes — with the IEC 60364-5-52 ampacity for reference. When you solve for the smallest wire size, the size itself is ignored — but its sizing system (AWG/kcmil or mm²) sets the system the answer comes back in.
Table 8 lists a different resistance for solid and stranded conductors of the same size — stranded is a little higher, because the strands leave air gaps: 12 AWG is 1.93 Ω/1000 ft solid and 1.98 Ω/1000 ft stranded. The K method does not distinguish them (7.90 V either way). kcmil sizes are stranded by construction, and mm² sizes use the K method, so the choice only moves the Table 8 line.
The percentage you want to hold — 3% is the NEC’s branch-circuit recommendation (210.19(A) Informational Note No. 4), 5% is the total for feeder plus branch (215.2(A)(1) Informational Note No. 2). The smallest-wire and maximum-length solvers use this number, and the verdict is judged against it.

Planning this project? Save to Pinterest to find this calculator again later.

How to use the Voltage Drop Calculator — How Much Voltage Do You Lose on a Long Run?

  1. Pick what to solve for. “Voltage drop” prices the wire you have; “smallest wire size” finds the smallest wire that holds your target percentage; “maximum length” finds the longest run your wire allows at that percentage. The other two answers are shown as extra lines either way, so one run gives you all three.
  2. Pick the circuit type. DC (battery, solar, RV), single-phase AC (homes, 120 / 240 V) or three-phase AC (208 / 480 V). DC and single-phase both multiply by 2 — out and back — while three-phase multiplies by √3 (1.732) and the drop is line-to-line.
  3. Pick the supply voltage. 12 V and 24 V for DC, 120 V and 240 V for US homes, 208 V and 480 V for three-phase, 277 V for commercial lighting — or “Custom” and enter your own (230 V for most of the world, 400 V for three-phase in Europe). The percentage is the volts lost divided by this number, so the same volts lost are a bigger percentage on 12 V than on 240 V.
  4. Enter the load current. The amps the load actually draws — not the breaker size. A 20 A circuit carrying 16 A drops 20% less than the same circuit at a full 20 A. For a continuous load the NEC sizes the conductor at 125% of the load; the ampacity floor below does that check for you.
  5. Enter the ONE-WAY length. The distance from the panel to the load, in feet or metres — not the round trip. The tool doubles it internally, because the current travels out on one conductor and back on the other. Entering the round-trip length is the most common voltage-drop error, and it doubles the answer.
  6. Pick the metal and the size. Copper (K = 12.9) or aluminium (K = 21.2) — aluminium loses about 64% more volts at the same size. AWG and kcmil sizes use NEC Table 8; mm² sizes use the K method. Ignored when you solve for the smallest wire size.
  7. Say solid or stranded. Table 8 lists a different resistance for each — 12 AWG is 1.93 Ω/1000 ft solid and 1.98 Ω/1000 ft stranded — so the Table 8 line moves a little. The K method does not distinguish them.
  8. Set the target percentage. 3% is the NEC’s branch-circuit recommendation, 5% is the total for feeder plus branch. The smallest-wire and maximum-length solvers use this number, and the verdict is judged against it.
  9. Read the drop first. The volts lost (K method, headline), the percentage, the voltage that reaches the load and the watts lost as heat in the wire — with the Table 8 resistance figure next to it, solid and stranded, so you can see the 0.02 V spread instead of taking one number on trust.
  10. Read the verdict. Inside 3% is within the branch-circuit recommendation; 3–5% is over the branch recommendation but inside the 5% total — fine for a feeder, not for a branch; over 5% is over both. The verdict is labelled a recommendation, because that is what the NEC’s notes are.
  11. Read the smallest wire and the maximum length. The smallest wire that holds your target percentage at this current and length, and the longest run your wire allows at that percentage (rounded down to the whole foot, because a length of 45.6 ft already exceeds 3%). If the smallest wire is bigger than the wire you entered, the wire has to grow — and the grounding conductor with it.
  12. Read the ampacity floor. The smallest wire that carries the current on Table 310.16’s 60 °C column — the conservative floor for NM cable and circuits of 100 A or less. Ampacity first, drop second: on the canonical run the floor is 12 AWG and the drop needs 8 AWG, so the drop governs. If the floor is bigger than the drop size, the ampacity governs instead.

Voltage Drop Calculator — How Much Voltage Do You Lose on a Long Run? formula

K method (headline result): VD = multiplier × K × I × L ÷ CM — multiplier 2 for DC and single-phase, √3 (1.732) for three-phase; K = 12.9 for copper, 21.2 for aluminium (at 75 °C, from NEC Chapter 9 Table 8); I = current in amps; L = one-way length in feet; CM = conductor area in circular mils. Table 8 method (cross-check): VD = multiplier × I × R × L ÷ 1000 — R = DC resistance in ohms per 1000 ft at 75 °C, uncoated, from the same table; L in feet. The two are the same formula: K ÷ CM is the resistance per foot, rounded.

Percent drop = VD ÷ supply voltage × 100 — voltage at the load = supply voltage − VD — watts lost = VD × I (the heat the wire gives off; also I² × loop resistance).

Smallest wire for a target percentage: the smallest size whose K-method drop is at or below target % × supply voltage — found by walking the size table from 14 AWG up. Maximum length for a target percentage: L = target VD × CM ÷ (multiplier × K × I), rounded DOWN to the whole foot — a length of 45.6 ft already exceeds 3%, so the tool prints 45 ft.

Verdict (labelled a recommendation, not a rule): drop ≤ target % (default 3%) is within the branch-circuit recommendation (210.19(A) Informational Note No. 4) · target % < drop ≤ 5% is over the branch recommendation but within the 5% total for feeder plus branch (215.2(A)(1) Informational Note No. 2) · drop > 5% is over both. The only enforceable drop limits are 647.4(D) (1.5% / 2.5% for sensitive electronic equipment) and 695.7 (fire pumps).

Ampacity floor (Table 310.16, 60 °C column): the smallest size whose 60 °C ampacity is at least the load current — 14 AWG 15 A · 12 AWG 20 A · 10 AWG 30 A · 8 AWG 40 A · 6 AWG 55 A · 4 AWG 70 A · 3 AWG 85 A · 2 AWG 95 A · 1 AWG 110 A · 1/0 125 A · 2/0 145 A · 3/0 165 A · 4/0 195 A · 250 kcmil 215 A · 300 kcmil 240 A · 350 kcmil 260 A · 400 kcmil 280 A · 500 kcmil 320 A (copper; aluminium is lower — see the table below). The 60 °C column is the conservative floor: 110.14(C) limits circuits of 100 A or less to 60 °C unless every termination is listed for 75 °C, and NM cable is a 60 °C wiring method. 240.4(D) caps the breaker at 15 / 20 / 30 A for 14 / 12 / 10 AWG copper — the same numbers as the 60 °C column, so the floor and the cap agree on small conductors.

Equipment grounding conductor (250.122(B)): when the phase conductors are upsized for voltage drop, the grounding conductor must be upsized in the same proportion — EGC circular mils × (new phase CM ÷ old phase CM). On the canonical run the phase grows 12 AWG → 8 AWG (6,530 → 16,510 CM, a 2.53× ratio), so a 12 AWG grounding conductor (6,530 CM) must grow to at least 16,510 CM — 8 AWG.

Metric: 1 mm² = 1,973.5 circular mils; 1 m = 3.28084 ft; 1 ft = 0.3048 m. mm² sizes use the K method only — there is no Table 8 resistance for metric sizes — with the IEC 60364-5-52 ampacity (method C, PVC, two loaded conductors) for reference.

What this does not do: reactance (Table 9 impedance) is ignored — on branch circuits under about 100 ft the difference is under 1%, on a 200 ft feeder at 100 A it can reach 5–10%; derating for more than three current-carrying conductors and ambient-temperature correction are not applied; the supply voltage is the nominal figure, not the measured voltage at the panel.

Worked example

Worked example — 120 V, 20 A, 100 ft one way, 12 AWG copper. This is the tool’s default, worked by hand so you can check it — and it is the field’s canonical example: every ranking calculator prints a version of it.

  1. K method: VD = 2 × 12.9 × 20 × 100 ÷ 6,530 = 7.90 V. Percent: 7.90 ÷ 120 × 100 = 6.58%. Voltage at the load: 120 − 7.90 = 112.10 V. Watts lost: 7.90 × 20 = 158.0 W — the heat the wire gives off along the run.
  2. Table 8, solid: VD = 2 × 20 × 1.93 × 100 ÷ 1000 = 7.72 V (6.43%), 112.28 V at the load. Table 8, stranded: VD = 2 × 20 × 1.98 × 100 ÷ 1000 = 7.92 V (6.60%), 112.08 V at the load. The three figures span 0.20 V — the K constant is rounded, and stranded copper has a little more resistance than solid. The tool prints all three; the headline is the K method, 7.90 V.
  3. Verdict: 6.58% is more than double the 3% branch-circuit recommendation and over the 5% total as well — this run fails both. A motor on the far end starts hard and runs hot; a light dims when the load switches on.
  4. Smallest wire for 3%: the target is 3% of 120 V = 3.6 V. 12 AWG needs 6,530 × 2 × 12.9 × 20 ÷ 3.6 — the size table walks up: 10 AWG (10,380 CM) gives 4.97 V (4.14%), still over; 8 AWG (16,510 CM) gives 3.13 V (2.60%) — the first size that holds. So the run needs 8 AWG, two sizes up.
  5. Maximum length for 3% on 12 AWG: L = 3.6 × 6,530 ÷ (2 × 12.9 × 20) = 45.6 ft, rounded down to 45 ft. At 46 ft the drop is already 3.03%. On 240 V the same wire at the same current allows 91 ft — the voltage doubles, so the length doubles.
  6. Ampacity floor: Table 310.16, 60 °C column — 12 AWG carries 20 A, exactly the load, so the floor is 12 AWG and the breaker cap (240.4(D)) is 20 A. Ampacity says the wire is fine; the drop says it is not. The drop governs.
  7. Grounding conductor: the phase grows 12 AWG → 8 AWG, a 2.53× ratio in circular mils (6,530 → 16,510), so the 12 AWG grounding conductor must grow by the same ratio: 6,530 × 2.53 = 16,510 CM — 8 AWG (250.122(B)).

Same run, 150 ft. 12 AWG at 150 ft: VD = 2 × 12.9 × 20 × 150 ÷ 6,530 = 11.85 V (9.88%) — 108.15 V at the load, and 237 W lost as heat. The smallest wire for 3% is now 6 AWG: 2.95 V (2.46%). Fifty extra feet moves the answer two sizes.

Three-phase — 208 V, 20 A, 100 ft, 12 AWG stranded. The multiplier is √3: VD = 1.732 × 20 × 1.98 × 100 ÷ 1000 = 6.86 V (3.30%), 201.14 V at the load; the K method gives 6.84 V (3.29%). Just over the 3% line — 10 AWG brings it to 4.30 V (2.07%). Three-phase loses about 13% less than single-phase on the same run, because √3 ÷ 2 = 0.866.

DC 12 V — solar / RV, 10 A, 20 ft, 12 AWG stranded. VD = 2 × 10 × 1.98 × 20 ÷ 1000 = 0.79 V (6.60%), 11.21 V at the load, 7.92 W lost. The volts lost are small; the percentage is not — on a 12 V supply the same 0.79 V is 6.60%, and a battery that reads 12.0 V at the panel reads 11.21 V at the load. Low-voltage runs fail on percentage, which is why solar installers upsize early: 10 AWG brings this one to 0.50 V (4.13%), 8 AWG to 0.31 V (2.59%).

Aluminium — 120 V, 20 A, 100 ft, 12 AWG aluminium stranded. VD = 2 × 20 × 3.25 × 100 ÷ 1000 = 13.00 V (10.83%), 107.00 V at the load; the K method gives 12.99 V (10.82%). Aluminium at the same size loses 64% more than copper (13.00 V against 7.92 V). The smallest aluminium wire for 3% is 6 AWG: 3.30 V (2.75%) by Table 8, 3.23 V by the K method. Aluminium needs one size larger than copper on this run (6 AWG against 8 AWG).

A run that passes — 240 V, 30 A, 80 ft, 10 AWG stranded. VD = 2 × 30 × 1.24 × 80 ÷ 1000 = 5.95 V (2.48%), 234.05 V at the load, 178.6 W lost; the K method gives 5.97 V (2.49%). Inside 3% — and the ampacity floor is 10 AWG (30 A), so both checks pass on the same size. Higher voltage is the cheapest fix there is: the same 30 A at 120 V would lose 4.96%.

Metric twin — 230 V, 16 A, 30 m, 2.5 mm² copper. 30 m is 98.43 ft; 2.5 mm² is 4,934 circular mils. VD = 2 × 12.9 × 16 × 98.43 ÷ 4,934 = 8.23 V (3.58%), 221.77 V at the load. Just over 3% — the smallest wire is 4 mm²: 5.15 V (2.24%). A 2.5 mm² ring-final circuit at 30 m is the European version of the canonical run, and it fails the same way.

Voltage drop tables: NEC Table 8 resistance, K constants, the 3% / 5% limits, maximum lengths, and Table 310.16 ampacity

The K method and the Table 8 method are the same formula — and the 0.02 V gap is the point. The K method (VD = 2 × K × I × L ÷ CM, K = 12.9 for copper) and the Table 8 resistance method (VD = 2 × I × R × L ÷ 1000) are the same physics: K ÷ CM is the resistance per foot, rounded to a constant. On the canonical run they give 7.90 V and 7.92 V (stranded) — a 0.02 V gap, 0.25%. The solid-copper Table 8 figure is 7.72 V, 0.18 V below the K figure, because the K constant is rounded up from the solid-copper resistivity and stranded copper has a little more resistance than solid. A calculator that prints only one number hides that spread; this page prints the K figure as the headline and the Table 8 figure next to it, solid and stranded, so the spread is visible. The field’s calculators split on this: calculatorx prints the Table 8 figure (7.72 V solid), voltagedropsolver and voltdropcalc print the K figure (7.90 V), and the difference between them is the rounding, not an error in either.

The 3% rule is a recommendation, and most of the field states it as a law. NEC 210.19(A) Informational Note No. 4 says branch-circuit conductors are “sized to prevent a voltage drop exceeding 3%” at the farthest outlet, and 215.2(A)(1) Informational Note No. 2 says the feeder plus branch total should not exceed 5%. Both are informational notes — 90.5(C) says informational notes are not enforceable as code. The enforceable exceptions are narrow: 647.4(D) limits sensitive electronic equipment to 1.5% on the branch and 2.5% total, and 695.7 limits fire-pump circuits. Most ranking calculators print “3% maximum” as if it were a code limit; it is a design target, and a project specification or a local amendment can set a different one. The tool’s verdict is labelled a recommendation for exactly that reason — and the target percentage is yours to change.

One ranking calculator is wrong on 10 AWG, and the error is checkable. electriciancalc publishes “10 AWG → 3.9 V (3.3%)” for the canonical 20 A, 100 ft, 120 V run. Neither method reproduces it: the K method gives 4.97 V (4.14%) and Table 8 stranded gives 4.96 V (4.13%). 3.9 V is the figure for 9 AWG (3.94 V by the K method) — the page’s 10 AWG row matches a 9 AWG calculation. Do not copy it; the table below is the check.

Ampacity first, drop second — and the order matters. A wire has to pass two checks: carry the current without overheating (Table 310.16 ampacity, with the 240.4(D) breaker caps), and deliver the voltage without losing too much of it (the drop). On the canonical run the ampacity floor is 12 AWG and the drop needs 8 AWG, so the drop governs. On a short run the reverse is true: a 240 V, 50 A, 20 ft run on 8 AWG loses 1.56 V (0.65%) but the ampacity floor is 6 AWG (55 A), so the ampacity governs. Size for ampacity, then check the drop, then take the larger of the two — that is the order in the NEC (310.16 and 240.4(D) before the informational notes) and the order in this tool.

The grounding conductor grows with the phase conductors. NEC 250.122(B) requires the equipment grounding conductor to be upsized in the same proportion when the phase conductors are upsized for voltage drop. On the canonical run the phase grows 12 AWG → 8 AWG — 6,530 to 16,510 circular mils, a 2.53× ratio — so a 12 AWG grounding conductor (6,530 CM) must grow to at least 16,510 CM, which is 8 AWG. The tool computes this whenever the smallest wire is bigger than the wire you entered. It is the line most DIY calculators leave out, and it is the one an inspector checks.

One-way length is the trap. The current travels out on one conductor and back on the other, so the loop is twice the one-way length — that is what the multiplier of 2 means. Enter 200 ft for a 100 ft run and the tool prints 15.81 V instead of 7.90 V; enter the round trip on a three-phase run and the error is the same. Every ranking calculator that prints a worked example uses the one-way length (voltagedropsolver’s 120 V / 20 A / 100 ft → 7.92 V, 6.60%; atlascalcs’ 7.72 V, 6.43%); the ones that get it wrong do not show their work. Measure the run once, from the panel to the load, and enter that number.

Resistance-only: when the AC caveat matters. Table 8 gives DC resistance; alternating current also meets inductive reactance, which Table 9 lists as XL alongside an AC resistance. The full impedance is Z = R·cos θ + XL·sin θ, and the drop is 2 × L × I × Z ÷ 1000. On branch circuits under about 100 ft the reactance adds under 1% to the drop — the tool’s figure is the answer. On a 200 ft feeder at 100 A in steel conduit it can add 5–10%, because the reactance grows with the size and the steel raises it further. If the tool says 4.9% on a long feeder, the real figure may already be over 5% — upsize one more size, or run the Table 9 calculation. DC circuits have no reactance at all: the Table 8 figure is exact.

Why low voltage fails first. The volts lost depend on the current, the length and the wire — not on the supply voltage. The percentage is the volts lost divided by the supply, so the same 0.79 V is 6.60% of 12 V, 0.66% of 120 V and 0.33% of 240 V. A 12 V solar run at 10 A over 20 ft loses the same percentage as a 120 V run at 20 A over 100 ft — and a 12 V run that is 50 ft long needs 4 AWG where the 120 V version is happy on 14 AWG. That is why the DC example above (12 V, 10 A, 20 ft, 12 AWG → 6.60%) is the one that surprises people: the volts are small, the percentage is not.

NEC Chapter 9 Table 8 — DC resistance at 75 °C, ohms per 1000 ft, uncoated. The table the tool uses. Solid and stranded differ because the strands leave air gaps; kcmil sizes are stranded by construction. Aluminium is about 64% higher than copper at the same size.

SizeCircular milsCopper solidCopper strandedAluminium solidAluminium stranded
14 AWG4,1103.073.145.065.17
12 AWG6,5301.931.983.183.25
10 AWG10,3801.211.242.002.04
8 AWG16,5100.7640.7781.261.28
6 AWG26,2400.4910.5100.8080.824
4 AWG41,7400.3080.3210.5080.524
3 AWG52,6200.2450.2540.4030.415
2 AWG66,3600.1940.2010.3190.329
1 AWG83,6900.1540.1600.2530.261
1/0 AWG105,6000.1220.1270.2010.207
2/0 AWG133,1000.09670.1010.1590.164
3/0 AWG167,8000.07660.07970.1260.130
4/0 AWG211,6000.06080.06330.1000.103
250 kcmil250,000—0.0515—0.0847
300 kcmil300,000—0.0429—0.0707
350 kcmil350,000—0.0367—0.0605
400 kcmil400,000—0.0321—0.0529
500 kcmil500,000—0.0258—0.0424

K constants and the multipliers. K = 12.9 Ω·cmil/ft for copper and 21.2 for aluminium at 75 °C (IAEI, from Table 8). The multiplier is 2 for DC and single-phase, √3 (1.732) for balanced three-phase.

MethodFormulaConstants
K method, DC / single-phaseVD = 2 × K × I × L ÷ CMK = 12.9 Cu · 21.2 Al
K method, three-phaseVD = 1.732 × K × I × L ÷ CMLine-to-line drop
Table 8 method, DC / single-phaseVD = 2 × I × R × L ÷ 1000R = Ω per 1000 ft (table above)
Table 8 method, three-phaseVD = 1.732 × I × R × L ÷ 1000Line-to-line drop

The 3% / 5% limits, with the exceptions. Informational notes, not enforceable limits — except the two rows at the bottom.

RuleLimitSourceStatus
Branch circuit3%210.19(A) Informational Note No. 4Recommendation
Feeder2%215.2(A)(1) Informational Note No. 2Recommendation
Feeder + branch, total5%215.2(A)(1) Informational Note No. 2Recommendation
Sensitive electronic equipment1.5% branch · 2.5% total647.4(D)Enforceable
Fire pumps15% at starting, 5% running*695.7Enforceable

*695.7 limits the drop at the fire-pump controller: 15% while the motor is starting and 5% while it is running. The tool’s verdict is judged against the 3% / 5% recommendations; a fire-pump or sensitive-equipment circuit needs its own limit — set the target percentage to 1.5% and size from there.

Maximum one-way length at 3% (K method, copper, at the full 60 °C ampacity of the size). Rounded down to the whole foot — a length of 45.6 ft already exceeds 3%. Doubling the voltage doubles the length; doubling the current halves it.

SizeCurrent120 V240 V
14 AWG15 A38 ft76 ft
12 AWG20 A45 ft91 ft
10 AWG30 A48 ft96 ft
8 AWG40 A57 ft115 ft
6 AWG55 A66 ft133 ft
4 AWG70 A83 ft166 ft

Table 310.16 ampacity — the ampacity floor (60 °C column) and the 75 °C column. Not more than three current-carrying conductors, 30 °C ambient. The 240.4(D) cap is the breaker limit on small conductors.

SizeCopper 60 °CCopper 75 °CAluminium 60 °CAluminium 75 °C240.4(D) breaker cap (Cu)
14 AWG15 A20 A——15 A
12 AWG20 A25 A15 A20 A20 A
10 AWG30 A35 A25 A30 A30 A
8 AWG40 A50 A35 A40 A—
6 AWG55 A65 A40 A50 A—
4 AWG70 A85 A55 A65 A—
3 AWG85 A100 A65 A75 A—
2 AWG95 A115 A75 A90 A—
1 AWG110 A130 A85 A100 A—
1/0 AWG125 A150 A100 A120 A—
2/0 AWG145 A175 A115 A135 A—
3/0 AWG165 A200 A130 A155 A—
4/0 AWG195 A230 A150 A180 A—
250 kcmil215 A255 A170 A205 A—
300 kcmil240 A285 A190 A230 A—
350 kcmil260 A310 A210 A250 A—
400 kcmil280 A335 A225 A270 A—
500 kcmil320 A380 A260 A310 A—

Metric sizes — circular mils and IEC ampacity. 1 mm² = 1,973.5 circular mils. The ampacity is IEC 60364-5-52 Table B.52.3, method C (clipped direct / in conduit on a wall), PVC insulation, two loaded conductors — the reference figure for the drop calculation, not an NEC ampacity.

SizeCircular milsIEC ampacity (method C, PVC)
1.5 mm²2,96017.5 A
2.5 mm²4,93424 A
4 mm²7,89432 A
6 mm²11,84141 A
10 mm²19,73557 A
16 mm²31,57676 A
25 mm²49,338101 A
35 mm²69,073125 A
50 mm²98,677151 A
70 mm²138,147192 A
95 mm²187,485232 A
120 mm²236,824269 A

The field, as it stands. calculatorx holds the exact-phrase top spot with Table 8 values, the K method, metric Ω/km, DC / single-phase / three-phase and an uncertainty engine (IEC 60364-5-52); voltagedropsolver is second with the canonical 120 V / 20 A / 100 ft → 7.92 V / 6.60% example; voltdropcalc is third with the three solvers in one (drop, reverse wire size, maximum length, plus the cost of losses); atlascalcs is fourth with a diagram and a cost plan (7.72 V / 6.43%). The giants are gone from this field — Inch, Omni, CalculatorSoup and Southwire are absent from the current top five — which is why a tool that does all three solvers, shows both methods, and runs the ampacity and grounding checks has room to rank. The question variant (“how to calculate voltage drop”) is held by voltagelab (the K method, with the 647.4(D) / 695.7 exceptions and 250.122(B) named), jcrproductions, fielddojo and electriciancalc — the last of which is wrong on 10 AWG, as shown above.

Measurement tips

  • Size for ampacity first, then check the drop — and take the larger wire. The ampacity floor (Table 310.16, 60 °C column) and the drop size are two different answers, and the circuit needs the bigger of the two. On the canonical run the floor is 12 AWG and the drop needs 8 AWG, so the drop governs; on a short 50 A run the floor is 6 AWG and the drop is happy on 8 AWG, so the ampacity governs. A wire that passes one check and fails the other is the wrong wire.
  • Measure the one-way length, not the round trip. The tool doubles the length internally — the current travels out and back. Walk the route the cable actually takes (up, across, down, around the corners), not the straight line on the plan, and enter that number once. Entering the round trip doubles the answer, and it is the most common voltage-drop error.
  • Use the load current, not the breaker size. A 20 A circuit carrying 16 A drops 20% less than the same circuit at a full 20 A. Size the breaker for the circuit and the wire for the load — and remember a continuous load is sized at 125% of the load current for ampacity (210.19(A)(1)), so a 16 A continuous load needs a 20 A conductor.
  • Upsize the grounding conductor with the phase conductors. When the wire grows for drop — 12 AWG to 8 AWG on the canonical run — the equipment grounding conductor grows by the same ratio (250.122(B)): 6,530 to 16,510 circular mils, so the 12 AWG ground becomes 8 AWG. It is the line an inspector checks, and the one most DIY calculators leave out.
  • On a long run, raise the voltage before you raise the wire. Doubling the voltage halves the percentage and doubles the maximum length: the same 20 A at 240 V allows 91 ft on 12 AWG where 120 V allows 45 ft. A 240 V feed to a sub-panel, or a 208 V three-phase run, is often cheaper than two sizes of copper.
  • On 12 V, upsize early — the percentage is brutal. The same volts lost are twelve times the percentage on 12 V that they are on 120 V. A 12 V solar run at 10 A over 20 ft loses 6.60% on 12 AWG; 10 AWG brings it to 4.13% and 8 AWG to 2.59%. Size a low-voltage run for the percentage, not for the volts.
  • Stranded or solid changes the answer by 0.20 V — say which you have. 12 AWG is 1.93 Ω/1000 ft solid and 1.98 Ω/1000 ft stranded, so the canonical run is 7.72 V solid and 7.92 V stranded. NM cable up to 10 AWG is solid; most other cable is stranded. If the answer is close to a limit, the stranding is the difference between passing and failing.
  • Check the drop at the load, not at the panel. The voltage that matters is the one at the far end — 112.10 V on the canonical run, not 120 V. A motor that starts hard, a light that dims when the load switches on, and a heater that never quite reaches temperature are all drop symptoms, and they all live at the load end.
  • Keep the 3% target for branch circuits and 5% for the total. The branch should hold 3% and the feeder plus branch together should hold 5% — so a feeder that already loses 2% leaves only 3% for the branch. Size the feeder first, then the branch, and keep the two numbers separate.
  • When the tool says 4.9% on a long feeder, upsize one more size. The calculation is resistance-only and ignores reactance (Table 9). On a feeder over about 100 ft at high current the real drop is a little higher — up to 5–10% higher on a 200 ft feeder at 100 A in steel conduit. A result just inside 5% is not inside 5% once the reactance is counted.

Common mistakes

  • Entering the round-trip length. The tool doubles the one-way length internally — the current travels out and back. Enter 200 ft for a 100 ft run and the answer doubles to 15.81 V. Measure the route from the panel to the load once, and enter that number.
  • Treating 3% as a code limit. 3% on a branch circuit and 5% total are NEC informational notes (210.19(A) IN No. 4, 215.2(A)(1) IN No. 2) — recommendations, not enforceable limits. The only enforceable drop limits are 647.4(D) (1.5% / 2.5% for sensitive electronic equipment) and 695.7 (fire pumps). A project specification can set a different limit, and an inspector cannot fail a job for 3.1% on a branch circuit.
  • Sizing for ampacity and forgetting the drop. 12 AWG carries 20 A on ampacity (60 °C column) and still loses 6.58% at 100 ft. A wire that passes the ampacity check and fails the drop check is the wrong wire — and it is the most common sizing error on long runs, because the ampacity table is the one people look at first.
  • Upsizing the phase conductors and forgetting the ground. NEC 250.122(B) requires the equipment grounding conductor to grow in the same proportion as the phase conductors. On the canonical run the phase grows 12 AWG → 8 AWG (a 2.53× ratio), so the 12 AWG ground must become 8 AWG. A 12 AWG ground on an 8 AWG circuit is a code violation an inspector will find.
  • Using the breaker size as the current. A 20 A breaker does not mean the load draws 20 A — and the drop follows the load, not the breaker. A 16 A load on a 20 A circuit drops 20% less than a full 20 A load. Enter the amps the load actually draws; the ampacity floor does the breaker math.
  • Copying a rival’s 10 AWG figure without checking it. One ranking calculator publishes “10 AWG → 3.9 V (3.3%)” for the canonical run. Neither method reproduces it: the K method gives 4.97 V (4.14%) and Table 8 stranded gives 4.96 V (4.13%). 3.9 V is the figure for 9 AWG. A calculator that does not show its work cannot be checked — and this one is wrong.
  • Mixing up solid and stranded resistance. 12 AWG is 1.93 Ω/1000 ft solid and 1.98 Ω/1000 ft stranded — a 0.20 V difference on the canonical run. Using the solid figure for a stranded cable understates the drop; using the stranded figure for NM cable overstates it. Say which you have, and use the matching column.
  • Forgetting that low voltage fails on percentage. 0.79 V lost on a 12 V circuit is 6.60%; the same 0.79 V on 120 V is 0.66%. A 12 V solar or RV run that “only” loses a volt has already failed, and the fix is wire, not a bigger battery — the battery cannot put back what the wire loses as heat.
  • Adding the feeder and branch drops as percentages of different voltages. The 5% total is 5% of the supply, and the feeder and branch drops add in volts, not in percentages of different bases. A feeder that loses 4 V on 240 V and a branch that loses 4 V on 120 V is not 1.67% + 3.33% = 5% — it is 8 V on 120 V at the load, which is 6.67%. Work in volts, then divide once.
  • Ignoring reactance on a long feeder. The resistance-only figure is exact for DC and within 1% on branch circuits under 100 ft — but on a 200 ft feeder at 100 A in steel conduit the reactance can add 5–10%. A tool that says 4.9% on that feeder is not saying the circuit passes; it is saying the resistance passes, and the reactance is still to come.

Factors that affect accuracy

  • Current — the drop is proportional to it. Double the current and the drop doubles: the canonical run is 7.90 V at 20 A and 3.95 V at 10 A on the same wire. A load that draws half the breaker rating loses half the volts — which is why the load current, not the breaker size, is the input that matters.
  • Length — the drop is proportional to it, one way. Double the one-way length and the drop doubles: 7.90 V at 100 ft, 11.85 V at 150 ft, 15.81 V at 200 ft on 12 AWG at 20 A. The length is the one-way distance from the panel to the load — the tool doubles it for the out-and-back loop.
  • Wire size — the drop is inversely proportional to the area. Each three AWG sizes doubles the area and halves the drop: 12 AWG (6,530 CM) loses 7.90 V, 9 AWG (13,090 CM) loses 3.94 V, 6 AWG (26,240 CM) loses 1.97 V at the same current and length. Two sizes up quarters the drop — which is why the fix for a failing run is usually one or two sizes, not a different wire.
  • Metal — aluminium loses about 64% more than copper. K is 21.2 for aluminium against 12.9 for copper, so the same run loses 13.00 V on 12 AWG aluminium against 7.92 V on copper. Aluminium needs a larger size to match copper — on the canonical run, 6 AWG aluminium where copper needs 8 AWG — and its ampacity is lower too (12 AWG aluminium is 15 A on the 60 °C column, against 20 A for copper).
  • Supply voltage — the volts stay, the percentage moves. The volts lost depend on the current, the length and the wire — not on the supply. The percentage is the volts divided by the supply, so the same 7.90 V is 6.58% of 120 V, 3.29% of 240 V and 65.8% of 12 V. Raising the voltage is the cheapest fix there is, and low voltage is the hardest case there is.
  • Stranding — a small difference that matters at a limit. Stranded copper has a little more resistance than solid at the same size: 12 AWG is 1.98 against 1.93 Ω/1000 ft, so the canonical run is 7.92 V stranded and 7.72 V solid. The K method does not distinguish them (7.90 V either way). At 3.0% the stranding is the difference between passing and failing.
  • Temperature — resistance rises as the wire gets hot. Table 8 is at 75 °C; a conductor running hotter has more resistance (about 0.4% per °C for copper), so a wire that is already warm from a heavy load drops a little more than the table says. The effect is small on a branch circuit and worth remembering on a feeder that runs near its ampacity.
  • Three-phase — about 13% less drop than single-phase. A balanced three-phase circuit multiplies by √3 (1.732) instead of 2, so the same run loses 6.86 V on three-phase against 7.92 V on single-phase — √3 ÷ 2 = 0.866. The drop is line-to-line, and the percentage is against the line-to-line voltage (208 V, 480 V), not the phase voltage.
  • Reactance — the part the resistance figure leaves out. Alternating current also meets inductive reactance (Table 9), which grows with the conductor size and with steel conduit. On branch circuits under 100 ft it adds under 1%; on a 200 ft feeder at 100 A it can add 5–10%. DC circuits have no reactance at all — the Table 8 figure is exact.
  • Load type — continuous loads get the 125% rule. A continuous load (three hours or more) is sized at 125% of the load current for ampacity (210.19(A)(1)), so a 16 A continuous load needs a 20 A conductor — and the drop is worked on the 16 A the load actually draws, not the 20 A the conductor is sized for. A motor’s starting current is a different problem again: the drop at starting can be five times the running drop, and 695.7 exists because of it.

Sources & assumptions

  • Method — two forms of the same formula. K method: VD = multiplier × K × I × L ÷ CM (multiplier 2 for DC and single-phase, √3 = 1.732 for balanced three-phase; K = 12.9 for copper, 21.2 for aluminium at 75 °C); Table 8 method: VD = multiplier × I × R × L ÷ 1000 (R = DC resistance in ohms per 1000 ft at 75 °C, uncoated, from NEC Chapter 9 Table 8). K ÷ CM is the resistance per foot, rounded — so the two methods agree to within the rounding. Confirmed 2026-11-23 against Mirage Metrics' voltage drop calculator (Table 8 method, K method, multiplier 2 / √3, percent vs the NEC informational note), Lelifi's voltage drop calculator (Table 8, 120 V / 20 A / 100 ft / 12 AWG → 7.72 V / 6.43%) and Wire Gauge Calculator's NEC voltage drop guide (VD = 2 × K × I × L ÷ CM, K = 12.9 / 21.2, Table 8 resistances).
  • Table 8 values — Mirage Metrics (live read 2026-11-23): the Table 8 values used here — 14 AWG solid 3.07 / stranded 3.14 · 12 AWG 1.93 / 1.98 · 10 AWG 1.21 / 1.24 · 8 AWG 0.764 / 0.778 · 6 AWG 0.491 / 0.510 · 4 AWG 0.308 / 0.321 · 3 AWG 0.245 / 0.254 · 2 AWG 0.194 / 0.201 · 1 AWG 0.154 / 0.160 · 1/0 0.122 / 0.127 · 2/0 0.0967 / 0.101 · 3/0 0.0766 / 0.0797 · 4/0 0.0608 / 0.0633 · 250 kcmil 0.0515 · 300 kcmil 0.0429 · 350 kcmil 0.0367 · 400 kcmil 0.0321 · 500 kcmil 0.0258 (copper, stranded; aluminium 14 AWG 5.06 / 5.17 · 12 AWG 3.18 / 3.25 · 10 AWG 2.00 / 2.04 · 8 AWG 1.26 / 1.28 · 6 AWG 0.808 / 0.824 · 4 AWG 0.508 / 0.524 · 3 AWG 0.403 / 0.415 · 2 AWG 0.319 / 0.329 · 1 AWG 0.253 / 0.261 · 1/0 0.201 / 0.207 · 2/0 0.159 / 0.164 · 3/0 0.126 / 0.130 · 4/0 0.100 / 0.103 · 250 kcmil 0.0847 · 300 kcmil 0.0707 · 350 kcmil 0.0605 · 400 kcmil 0.0529 · 500 kcmil 0.0424). The page states its values were transcribed from Table 8 and checked against two published reproductions, and that NFPA's panel reports for the 2023 and 2026 editions show no revision to the table. Circular mils: 14 AWG 4,110 · 12 AWG 6,530 · 10 AWG 10,380 · 8 AWG 16,510 · 6 AWG 26,240 · 4 AWG 41,740 · 3 AWG 52,620 · 2 AWG 66,360 · 1 AWG 83,690 · 1/0 105,600 · 2/0 133,100 · 3/0 167,800 · 4/0 211,600.
  • Worked examples, reproduced exactly — Lelifi (live read 2026-11-23): 120 V, 20 A, 100 ft, 12 AWG stranded copper → 2 × 20 × 1.98 × 100 ÷ 1000 = 7.92 V, 6.60% of 120 V, 112.08 V at the load; 8 AWG brings the same run to 3.06 V (2.55%) by the solid Table 8 figure (3.13 V, 2.60% by the K method). Mirage Metrics: 120 V, 16 A, 72 ft, 12 AWG stranded → 2 × 1.98 × 72 × 16 ÷ 1000 = 4.56 V (3.80%); K method 4.55 V; 10 AWG brings it to 2.86 V (2.38%). Field figures from the 2026-11-22 teardown (SERP snapshots, not GSC): voltagedropsolver 120 V / 20 A / 100 ft → 7.92 V / 6.60%; atlascalcs 7.72 V / 6.43%; calculatorx (exact-phrase #1) Table 8 + K method with metric Ω/km and an uncertainty engine (IEC 60364-5-52); voltdropcalc three solvers in one (drop / reverse wire size / maximum length, plus cost of losses).
  • The 3% / 5% figures are informational notes, not limits — Enthalpy Calculator Hub's NEC voltage drop guide (live read 2026-11-23, sourced from NFPA 70, IEEE Std 141 and IEEE Std 399): NEC 210.19(A) Informational Note No. 4 (branch circuits ≤ 3%) and 215.2(A)(1) Informational Note No. 2 (feeder ≤ 2%, total ≤ 5%); Table 8 is DC resistance at 75 °C, Table 9 is AC effective impedance (R and XL at 60 Hz, three raceway types); K = 12.9 Ω·cmil/ft copper, 21.2 aluminium at 75 °C; a balanced three-phase circuit produces about 13.4% less drop than single-phase on the same run (√3 ÷ 2 = 0.866). Wire Gauge Calculator: the same 3% / 5% figures, labelled NEC recommendations, with the worked example VD = 2 × 20 × 1.93 × 75 ÷ 1000 = 5.79 V. Enforceable exceptions (field teardown 2026-11-22, voltagelab): 647.4(D) 1.5% / 2.5% for sensitive electronic equipment and 695.7 for fire pumps.
  • Ampacity and the small-conductor caps — Appropedia's conductor ampacity guide (live read 2026-11-23): Table 310.16, 2023 edition, three temperature columns, 30 °C ambient, not more than three current-carrying conductors — 14 AWG Cu 15 / 20 / 25 A · 12 AWG 20 / 25 / 30 A · 10 AWG 30 / 35 / 40 A · 8 AWG 40 / 50 / 55 A · 6 AWG 55 / 65 / 75 A (60 / 75 / 90 °C); NEC 240.4(D) caps the overcurrent device at 15 A for 14 AWG copper, 20 A for 12 AWG and 30 A for 10 AWG. Buckworks' Table 310.16 guide: the same table, plus 110.14(C) (circuits ≤ 100 A use the 60 °C column unless terminations are listed for 75 °C) and the worked example 12 AWG Cu THHN on a 20 A breaker. Workshop Calcs and CalcSpec: the same values, including 4 AWG 70 / 85 / 95 A · 2 AWG 95 / 115 / 130 A · 1/0 125 / 150 / 170 A · 4/0 195 / 230 / 260 A · 500 kcmil 320 / 380 / 430 A, and the note that the grid is numerically identical across the 2017, 2020 and 2023 editions. Zen Calculators: NM-B (Romex) is sized from the 60 °C column, and the 90 °C column is for derating math only.
  • Equipment grounding conductor upsizing — NEC 250.122(B) (field teardown 2026-11-22, voltagelab #1 on the question variant): when the ungrounded conductors are upsized for voltage drop, the equipment grounding conductor must be upsized in the same circular-mil proportion. Table 250.122 base sizes (copper): 15 A → 14 AWG · 20 A → 12 AWG · 30–60 A → 10 AWG · 100 A → 8 AWG · 200 A → 6 AWG. Worked on the canonical run: phase 12 AWG → 8 AWG is 6,530 → 16,510 CM (2.53×), so a 12 AWG grounding conductor (6,530 CM) must grow to at least 16,510 CM — 8 AWG.
  • Rival error flagged — electriciancalc (field teardown 2026-11-22): the page publishes "10 AWG → 3.9 V (3.3%)" for the canonical 20 A, 100 ft, 120 V run. Neither method reproduces it: the K method gives 4.97 V (4.14%) and Table 8 stranded gives 4.96 V (4.13%). 3.9 V is the figure for 9 AWG (3.94 V by the K method) — the page's 10 AWG row matches a 9 AWG calculation. This page does not copy it; the Table 8 table above is the check.
  • Metric sizes — IEC 60364-5-52 Table B.52.3, method C (clipped direct / in conduit on a wall), PVC insulation, two loaded conductors: 1.5 mm² 17.5 A · 2.5 mm² 24 A · 4 mm² 32 A · 6 mm² 41 A · 10 mm² 57 A · 16 mm² 76 A · 25 mm² 101 A · 35 mm² 125 A · 50 mm² 151 A · 70 mm² 192 A · 95 mm² 232 A · 120 mm² 269 A. 1 mm² = 1,973.5 circular mils; 1 m = 3.28084 ft. mm² sizes use the K method only — there is no Table 8 resistance for metric sizes.

Figures checked on 28 November 2026 as part of the site-wide test run (3239 automated checks, all passing). See how we calculate and test.

How this calculator was checked

Figures checked 23 November 2026. Each case below was recomputed from the calculator's own formula and matched the tool's output.

Test inputsExpected result
120 V, 20 A, 100 ft, 12 AWG copper (canonical)7.90 V (K) / 7.92 V (Table 8, stranded), 6.58% / 6.60%, 112.10 V at the load, 158.0 W lost
Same run, smallest wire for 3%8 AWG — 3.13 V, 2.60%
Same run at 150 ft11.85 V, 9.88%; smallest wire 6 AWG — 2.95 V, 2.46%
Three-phase 208 V, 20 A, 100 ft, 12 AWG stranded6.86 V, 3.30%, 201.14 V at the load
DC 12 V, 10 A, 20 ft, 12 AWG stranded (solar / RV)0.79 V, 6.60%, 11.21 V at the load
Aluminium 12 AWG, 20 A, 100 ft, 120 V13.00 V, 10.83% — aluminium needs one size larger than copper on this run (6 AWG vs 8 AWG)
240 V, 30 A, 80 ft, 10 AWG stranded5.95 V, 2.48% — inside 3%
230 V, 16 A, 30 m, 2.5 mm² copper (metric)8.23 V, 3.58%; smallest wire 4 mm² — 5.15 V, 2.24%

What this check does not cover

  • Resistance-only: the tool uses NEC Table 8 DC resistance (K method) and ignores reactance (Table 9 impedance) — on long, high-current AC feeders the real drop is a little higher; the page says by how much and when it matters.
  • The K method is a rounded constant (12.9 Cu / 21.2 Al): on the canonical run it reads 7.90 V against Table 8’s 7.72 V solid and 7.92 V stranded — the page shows both, so the spread is visible.
  • Ampacity is the 60 °C column of Table 310.16 with the 240.4(D) small-conductor caps; the 75 °C column is printed in the table for equipment listed for it.
  • The 3% / 5% figures are NEC informational notes (210.19(A) IN No. 4, 215.2(A)(1) IN No. 2), not enforceable limits — the only enforceable drop limits are 647.4(D) and 695.7.
  • The voltage entered is the nominal supply, not the measured voltage at the panel, which drifts a few volts through the day.
Please note: material estimates are approximate. Always confirm product coverage with the manufacturer and buy a little extra for cuts, waste and future repairs.

What this calculator doesn't do

  • This is a planning calculation, not a code compliance check. It prices the drop from NEC Chapter 9 Table 8 DC resistance (and the K method, which is the same formula) — it does not apply the derating for more than three current-carrying conductors (310.15(C)(1)), the ambient-temperature correction (310.15(B)), or motor-starting inrush. A licensed electrician sizes the circuit; this page tells you whether the long run is the problem before you call one.
  • The calculation is resistance-only. It ignores reactance — the inductive part of the impedance in NEC Chapter 9 Table 9 — so on long, high-current AC feeders the real drop is a little higher than the figure here. On branch circuits under about 100 ft the difference is under 1%; on a 200 ft feeder at 100 A it can reach 5–10%. The page says when it matters.
  • The K method is a rounded constant. K = 12.9 for copper is a rounded resistivity, so the K result sits about 2% above the Table 8 solid-copper value and about 0.2% below the stranded value on the canonical run — 7.90 V against 7.72 V and 7.92 V. The page shows both methods, so the spread is visible instead of hidden.
  • The 3% and 5% figures are NEC informational notes (210.19(A) Informational Note No. 4 and 215.2(A)(1) Informational Note No. 2), not enforceable limits — a project specification or a local amendment can set its own limit. The only enforceable drop limits in the NEC are 1.5% / 2.5% for sensitive electronic equipment (647.4(D)) and the fire-pump rule (695.7).
  • Ampacity here is the 60 °C column of Table 310.16, with the 240.4(D) small-conductor caps — the conservative floor for NM cable and for circuits of 100 A or less, where 110.14(C) limits terminations to 60 °C unless they are listed for 75 °C. The page prints the 75 °C column too, for equipment that is listed for it.
  • The voltage you enter is the nominal supply — 120 V, 240 V, 208 V — not the voltage your utility actually delivers, which drifts a few volts either way through the day. A drop that is 2.9% of nominal can be 3.1% of what the meter reads at 7 pm. Measure the supply at the panel if the answer is close to a limit.

Voltage Drop Calculator — How Much Voltage Do You Lose on a Long Run? — frequently asked questions

How do I calculate voltage drop?

VD = 2 × K × I × L ÷ CM for DC and single-phase (1.732 instead of 2 for three-phase) — K = 12.9 for copper, 21.2 for aluminium; I is the current in amps, L is the one-way length in feet, CM is the wire area in circular mils. The same formula with Table 8 resistance is VD = 2 × I × R × L ÷ 1000. On the canonical run — 120 V, 20 A, 100 ft, 12 AWG copper — the K method gives 7.90 V (6.58%) and Table 8 gives 7.72 V solid / 7.92 V stranded. Enter your circuit above and the tool works all three figures out.

What is the 3% voltage drop rule?

It is a recommendation, not a rule. NEC 210.19(A) Informational Note No. 4 says branch-circuit conductors should be sized to prevent a drop over 3% at the farthest outlet, and 215.2(A)(1) Informational Note No. 2 says the feeder plus branch total should not exceed 5%. Both are informational notes — 90.5(C) says they are not enforceable as code. The only enforceable drop limits are 1.5% / 2.5% for sensitive electronic equipment (647.4(D)) and the fire-pump rule (695.7). Most ranking calculators print “3% maximum” as if it were law; it is a design target, and a project specification can set a different one.

What size wire do I need for a 100 ft run at 20 amps?

8 AWG copper. 12 AWG loses 7.90 V (6.58%) on a 120 V, 20 A, 100 ft run — more than double the 3% recommendation. 10 AWG loses 4.97 V (4.14%), still over. 8 AWG is the first size that holds: 3.13 V (2.60%). The ampacity floor is 12 AWG (20 A on the 60 °C column), so the drop governs, not the ampacity — and the grounding conductor grows with the phase conductors, from 12 AWG to 8 AWG (250.122(B)). At 240 V the same run is happy on 12 AWG (45 ft is the maximum at 120 V, 91 ft at 240 V).

How much voltage drop is acceptable?

3% on a branch circuit and 5% total (feeder plus branch) is the NEC’s recommendation. Inside 3% is within the branch recommendation; 3–5% is over the branch recommendation but inside the 5% total — fine for a feeder, not for a branch; over 5% is over both. Sensitive electronic equipment is stricter: 1.5% on the branch and 2.5% total (647.4(D), enforceable). In practice, motors, heaters and lights notice the drop before the code does — a motor that starts hard or a light that dims is a drop symptom at 4–5%, even though no rule is broken.

Does voltage drop depend on wire size or length?

Both — and on the current. The drop is proportional to the current and to the one-way length, and inversely proportional to the wire’s area: double the current or the length and the drop doubles; go up three AWG sizes and the area doubles, so the drop halves. On the canonical run, 12 AWG at 100 ft loses 7.90 V; at 150 ft it loses 11.85 V; at 10 A instead of 20 A it loses 3.95 V; on 8 AWG it loses 3.13 V. The supply voltage does not change the volts lost — it changes the percentage.

Is voltage drop worse on 12 V DC?

Yes — the percentage is twelve times worse than on 120 V. The volts lost depend on the current, the length and the wire, not on the supply — so the same 0.79 V is 6.60% of 12 V and 0.66% of 120 V. A 12 V solar or RV run at 10 A over 20 ft of 12 AWG loses 0.79 V (6.60%), leaving 11.21 V at the load; 10 AWG brings it to 0.50 V (4.13%) and 8 AWG to 0.31 V (2.59%). Low-voltage runs fail on percentage, which is why solar installers upsize early — and why the fix is wire, not a bigger battery.

Copper vs aluminium voltage drop — which is worse?

Aluminium loses about 64% more than copper at the same size. K is 21.2 for aluminium against 12.9 for copper, and the Table 8 resistances show it: 12 AWG is 1.98 Ω/1000 ft stranded copper against 3.25 Ω/1000 ft stranded aluminium. On the canonical run aluminium loses 13.00 V (10.83%) against copper’s 7.92 V (6.60%). Aluminium needs a larger size to match copper — on this run, 6 AWG aluminium (3.30 V, 2.75%) where copper needs 8 AWG — and its ampacity is lower too (12 AWG aluminium is 15 A on the 60 °C column, against 20 A for copper).

Why do the K method and Table 8 give different answers?

They are the same formula — the K constant is rounded. K ÷ CM is the resistance per foot, rounded to 12.9 for copper. On the canonical run the K method gives 7.90 V, Table 8 solid copper gives 7.72 V and Table 8 stranded gives 7.92 V — a 0.20 V spread. The K figure sits between the two Table 8 figures because the constant is rounded up from the solid-copper resistivity and stranded copper has a little more resistance than solid. Neither is wrong; a calculator that prints only one number hides the spread, and this page prints all three.

Do I size wire for ampacity or voltage drop?

Both — ampacity first, drop second, and take the larger wire. Ampacity (Table 310.16) is whether the wire carries the current without overheating; drop is whether it delivers the voltage. On the canonical run the ampacity floor is 12 AWG (20 A) and the drop needs 8 AWG, so the drop governs. On a short 50 A run the floor is 6 AWG (55 A) and the drop is happy on 8 AWG (1.56 V, 0.65% at 20 ft), so the ampacity governs. Size for ampacity, check the drop, take the larger — that is the order in the NEC, and the order in this tool.

What is the maximum length for 12 AWG at 20 amps?

45 ft at 120 V, 91 ft at 240 V, at the 3% target. The maximum length is L = 3.6 V × 6,530 CM ÷ (2 × 12.9 × 20 A) = 45.6 ft, rounded down to 45 ft — at 46 ft the drop is already 3.03%. Doubling the voltage doubles the length; doubling the current halves it. The full table is above: 14 AWG at 15 A allows 38 ft at 120 V, 10 AWG at 30 A allows 48 ft, 8 AWG at 40 A allows 57 ft, and 6 AWG at 55 A allows 66 ft.

How do I calculate voltage drop in mm²? (metric)

Convert the area to circular mils and use the K method: 1 mm² = 1,973.5 circular mils. A 230 V, 16 A, 30 m run on 2.5 mm² copper: 30 m is 98.43 ft and 2.5 mm² is 4,934 circular mils, so VD = 2 × 12.9 × 16 × 98.43 ÷ 4,934 = 8.23 V (3.58%), leaving 221.77 V at the load. The smallest wire for 3% is 4 mm²: 5.15 V (2.24%). There is no Table 8 resistance for metric sizes, so mm² runs use the K method only, with the IEC 60364-5-52 ampacity for reference (2.5 mm² is 24 A, 4 mm² is 32 A, method C, PVC).

What size cable do I need for a 30 m run at 16 amps? (metric)

4 mm² copper. A 230 V, 16 A, 30 m run on 2.5 mm² loses 8.23 V (3.58%) — just over the 3% target. 4 mm² brings it to 5.15 V (2.24%), and its IEC ampacity is 32 A against the 16 A load, so both checks pass. The maximum length for 3% on 2.5 mm² at 16 A is 25 m (rounded down); on 4 mm² it is 40 m. Enter the length in metres above and the tool converts — the length field takes feet or metres, and the answer prints in both.

Next step

Take the volts lost, the smallest wire and the maximum length to your electrician — and check the load behind the run first with the electricity cost calculator, the BTU calculator and the generator size calculator before you buy the wire, because the current is the input the drop follows. If the smallest wire is bigger than the wire you have, remember the grounding conductor grows with it (250.122(B)) — and if the run is 12 V, upsize early: the percentage is twelve times worse than on 120 V.

Save this estimate: use the Copy link button in the results box above to share these exact inputs, or Print results for a paper copy to take to the store.