Bathroom Fan Size Calculator
A bathroom fan is sized in CFM — cubic feet per minute, the volume of air it moves. Too small and the mirror stays fogged, the paint peels and mould grows; too big and you pay for noise and a fan that short-cycles the room. This bathroom fan size calculator works it out the way the Home Ventilating Institute (HVI) publishes it: 1 CFM per square foot of floor for bathrooms up to 100 square feet, or 50 CFM per fixture (100 for a jetted tub) for larger bathrooms — then a volume check for ceilings over 8 ft, and the code floor of 50 CFM intermittent or 20 CFM continuous from ASHRAE 62.2 and the International Residential Code. It then adjusts for your duct: every foot of duct and every elbow costs airflow, so the tool works out the equivalent duct length, derates the figure, and tells you the rating to shop for and the standard size to buy — plus the duct diameter that can actually carry it and the sones rating to look for. For the fan’s running cost, use the electricity cost calculator; for the heat the fan pulls out of the room, the heating cost calculator; and for stopping the damp at its source, the insulation calculator. If the damp is in a basement rather than a bathroom, size the drying with the dehumidifier size calculator.
Planning this project? Save to Pinterest to find this calculator again later.
How to use the Bathroom Fan Size Calculator
- Measure the room. Length × width, wall to wall, in feet or metres — the tool converts. A 10 × 8 ft bathroom is 80 sq ft. Measure the ceiling height too: at 8 ft the area method governs, above 8 ft the volume check takes over.
- Count the fixtures. Toilets, showers, standard tubs and jetted tubs. In a bathroom up to 100 sq ft the fixtures do not change the answer — HVI sizes those rooms by floor area. Above 100 sq ft the fixtures are the whole method: 50 CFM each, 100 for a jetted tub.
- Measure the duct. The straight run from the fan to the outside cap, plus the number of 90° elbows. A 10 ft run with two elbows is 20 ft of equivalent duct — and that costs 10% of the airflow. Short and straight is worth more than a bigger fan.
- Read the required CFM. The result shows all three methods side by side — area, fixture, volume check — plus the code floor, and names which one governs. That is the airflow the room needs delivered, not the number on the box.
- Shop for the adjusted rating. The duct eats airflow, so the fan you buy must be rated higher than the room needs: the tool divides by (1 − the duct loss) and rounds to the nearest 10 CFM, then names the next standard size — 50, 70, 80, 110 or 150 CFM. A 10 ft run with two elbows turns an 80 CFM need into a ~90 CFM rating, so you buy a 110 CFM fan.
- Check the duct diameter. A 4-inch duct carries up to about 100 CFM; above that you need 6 inches, above 200 CFM you need 8 inches. If the tool says your duct is too small, stepping the duct up is cheaper than buying a bigger fan that cannot breathe through it.
- Check the sones. Sones measure how loud the fan sounds: 1.0 or less is quiet, 2.0 is common, over 2.0 is loud. A quiet fan gets used; a loud one gets switched off the moment the shower ends, which is exactly when it is needed most. The code allows up to 3 sones for a switched fan and 1 sone for a continuous one.
- Check the HVI-certified CFM, not the box. The number on the box is measured at 0.1 in. of water static pressure, with almost no duct. The HVI-certified figure at 0.25 in. w.c. is the honest one for a real duct run: a Broan 110 CFM fan delivers 92 CFM at 0.25 in. w.c. Buy on the 0.25 in. figure.
- Run it for 20 minutes after the shower. HVI’s guidance is to leave the fan running for 20 minutes after you shower, so the moisture actually leaves the room instead of condensing on the walls. A timer switch or a humidity sensor does this without you having to remember.
- Use the link. The page keeps your inputs in the address bar, so the Copy link button gives you a link that reopens the same room, fixtures and duct — useful for comparing two duct routes, or for sending the numbers to your contractor.
Bathroom Fan Size Calculator formula
Floor area = length × width
HVI area method (bathrooms up to 100 sq ft): CFM = floor area in sq ft × 1 CFM per sq ft — about 8 air changes per hour at an 8 ft ceiling.
HVI fixture method (bathrooms over 100 sq ft): CFM = 50 × (toilets + showers + standard tubs) + 100 × jetted tubs
Volume check (ceilings over 8 ft): CFM = room volume in ft³ × 8 air changes per hour ÷ 60
Code floor: 50 CFM intermittent, 20 CFM continuous (ASHRAE 62.2 / IRC M1505.4.4, 2021; M1505.5, 2024)
Required CFM = the largest of the applicable figures — the page names which one governs.
Equivalent duct length = straight duct + 5 ft per 90° elbow
Duct loss: 0% at 10 ft equivalent or less · 10% at 11–25 ft · 20% at 26–50 ft · 30% above 50 ft (a typical estimate — the fan curve governs)
Shop-for rating = required CFM ÷ (1 − duct loss), rounded to the nearest 10 CFM, then up to the next standard size (50 / 70 / 80 / 110 / 150 CFM).
Litres per second = CFM × 0.472 — 80 CFM is 37.8 L/s, 150 CFM is 70.8 L/s.
The area method assumes an 8 ft ceiling, which is why 1 CFM per square foot works out to about 7.5 air changes an hour — HVI calls it “approximately eight”. The volume check is the same idea written for tall ceilings, and it only raises the figure above 8 ft.
Worked example
Worked example — 10 × 8 ft bathroom, 8 ft ceiling, one toilet and one shower, 10 ft of duct with two elbows, 4-inch duct, intermittent operation. This is the tool’s default, worked by hand so you can check it.
- Floor area: 10 × 8 = 80 sq ft (7.43 m²).
- Room volume: 80 × 8 = 640 ft³ (18.12 m³).
- HVI area method: 80 sq ft × 1 CFM per sq ft = 80 CFM. The bathroom is under 100 sq ft, so the area method applies.
- HVI fixture method: 50 (toilet) + 50 (shower) = 100 CFM — shown for comparison, but it does not govern in a bathroom under 100 sq ft.
- Volume check: 640 ft³ × 8 ÷ 60 = 85.3 CFM — shown for comparison, but the volume check only raises the figure for ceilings over 8 ft.
- Code floor: intermittent operation = 50 CFM (ASHRAE 62.2 / IRC M1505.4.4).
- Required CFM: the largest applicable figure — 80 CFM (37.8 L/s), governed by the HVI area method.
- Equivalent duct length: 10 ft straight + 2 elbows × 5 ft = 20 ft (6.10 m).
- Duct loss: 20 ft falls in the 11–25 ft band, so 10%.
- Shop-for rating: 80 ÷ (1 − 0.10) = 88.9 CFM → about 90 CFM (42.5 L/s).
- Standard size to buy: the next standard size at or above 88.9 CFM is a 110 CFM fan.
- Duct check: 80 CFM is under the 100 CFM limit for a 4-inch duct, so the 4-inch duct is fine. Aim for 1.0 sone or less.
Same room, 10 ft ceiling. The volume is 800 ft³, so the volume check is 800 × 8 ÷ 60 = 106.7 CFM — now it governs, and the required figure is 107 CFM (50.5 L/s). The shop-for rating is 107 ÷ 0.9 = 118.9 → about 120 CFM, so you buy a 150 CFM fan — and the 4-inch duct is no longer enough (107 > 100), so you step up to a 6-inch duct. Two feet of ceiling costs a whole fan size and a duct size.
Big bathroom — 12 × 12 ft, toilet, shower and standard tub. The floor area is 144 sq ft, over the 100 sq ft line, so the fixture method governs: 50 + 50 + 50 = 150 CFM (70.8 L/s). The shop-for rating is 150 ÷ 0.9 = 166.7 → about 170 CFM — above the largest single standard size, so this room needs two fans or one inline fan, on a 6-inch duct (150 CFM is inside the 100–200 CFM band).
Common bathrooms — on a short, straight duct (no duct loss). The fan to buy is the next standard size at or above the required CFM.
| Bathroom | Floor area | Required CFM | Fan to buy |
|---|---|---|---|
| 5 × 8 ft — small full bath | 40 sq ft | 50 CFM (code floor governs) | 50 CFM |
| 8 × 8 ft — hall bath | 64 sq ft | 64 CFM | 70 CFM |
| 10 × 8 ft — standard bath | 80 sq ft | 80 CFM | 80 CFM |
| 10 × 10 ft — large bath | 100 sq ft | 100 CFM | 110 CFM |
| 12 × 10 ft — toilet, shower, tub | 120 sq ft | 150 CFM (fixture method) | 150 CFM |
| 12 × 12 ft — toilet, shower, tub | 144 sq ft | 150 CFM (fixture method) | 150 CFM |
On a real duct run, add the duct loss first — a 10 ft run with two elbows adds 10%, so the 80 CFM room above needs a 110 CFM fan, not an 80 CFM one.
Bathroom fan tables: fixtures, ceilings, ducts and noise
HVI fixture method — bathrooms over 100 sq ft. Add the allowances for the fixtures in the room. An enclosed toilet compartment gets its own fan (HVI).
| Fixture | CFM allowance |
|---|---|
| Toilet / water closet | 50 CFM (23.6 L/s) |
| Shower | 50 CFM (23.6 L/s) |
| Standard bathtub | 50 CFM (23.6 L/s) |
| Jetted (whirlpool) tub | 100 CFM (47.2 L/s) |
HVI’s own example is a 20 × 12 ft bathroom with a tub, a separate shower and an enclosed toilet: 50 + 50 + 50 = 150 CFM.
Ceiling height — 10 × 8 ft room (80 sq ft). The volume check only raises the figure above an 8 ft ceiling. The second column is the alternative method (BuildSolver scales the area figure by height ÷ 8, holding 7.5 air changes an hour) — the tool uses the 8 ACH volume method, which is the plurality, and shows both so you can see the difference.
| Ceiling height | This tool (volume, 8 ACH) | BuildSolver (area × height ÷ 8) |
|---|---|---|
| 8 ft (2.44 m) | 80 CFM (area governs) | 80 CFM |
| 9 ft (2.74 m) | 96 CFM | 90 CFM |
| 10 ft (3.05 m) | 107 CFM | 100 CFM |
| 12 ft (3.66 m) | 128 CFM | 120 CFM |
Duct derating — equivalent length = straight duct + 5 ft per 90° elbow. A typical estimate (PonderLoop’s published model): other sources put one elbow at 5–15 ft of equivalent length, and flexible duct, a crushed run or a poor cap can cost more. The fan curve on the spec sheet governs.
| Equivalent duct length | Airflow lost | Example |
|---|---|---|
| 10 ft or less | 0% | 10 ft straight, no elbows |
| 11–25 ft | 10% | 10 ft + 2 elbows = 20 ft |
| 26–50 ft | 20% | 25 ft + 2 elbows = 35 ft |
| Over 50 ft | 30% | 40 ft + 4 elbows = 60 ft |
Duct size and noise — what diameter carries the air, and how loud it sounds.
| Duct diameter | Carries up to | Use for |
|---|---|---|
| 3 in (76 mm) | 50 CFM | Powder rooms, no tub or shower |
| 4 in (102 mm) | 100 CFM | Most bathrooms — the usual size |
| 6 in (152 mm) | 200 CFM | Large bathrooms, long runs |
| 8 in (203 mm) | Over 200 CFM | Two-fan or inline-fan jobs |
| Sones | How it sounds |
|---|---|
| 0.5 or less | Barely audible |
| 1.0 or less | Quiet — aim for this |
| 1.0–2.0 | Common — you hear it, it does not bother you |
| Over 2.0 | Loud — gets switched off, which defeats the fan |
| 3.0 | Code maximum for a switched (intermittent) fan; continuous fans are limited to 1.0 sone |
Why the box number lies. The CFM on the box is measured at 0.1 in. of water static pressure — almost no duct. At 0.25 in. w.c., the pressure a real duct run creates, the same fan moves less air. Broan’s own spec sheet for the AE110K (HVI-2100 certified) lists 110 CFM at 0.1 in. w.c. and 92 CFM at 0.25 in. w.c. — 16% less. Size on the 0.25 in. figure, or buy one size up.
The 50 CFM argument, settled. HVI’s chart lists 50 CFM for bathrooms under 50 sq ft, while a strict reading of the 1 CFM-per-square-foot rule gives 40 CFM for a 5 × 8 ft bathroom. The two readings disagree — but the answer never changes, because the code floor (50 CFM intermittent, ASHRAE 62.2 / IRC) lifts either figure to 50. This tool shows the area figure, the fixture figure and the code floor as separate rows, so you can see the dispute instead of having it hidden from you.
A chart to ignore. PickHVAC’s bathroom fan chart says a 12 × 12 ft bathroom needs 200 CFM. The HVI fixture method says 150 CFM (toilet + shower + tub) — and HVI’s own worked example for a 20 × 12 ft bathroom with the same three fixtures is also 150 CFM. The 200 CFM figure contradicts the method it claims to follow, so this page does not use it.
Measurement tips
- Buy quiet, or the fan never runs. A fan at 1.0 sone or less is barely noticeable; a fan over 2.0 sones gets switched off the moment the shower ends — exactly when the moisture needs removing. Quiet costs a little more and is the single best money on the page.
- Shorten the duct before you upsize the fan. A 10 ft run with two elbows costs 10% of the airflow; a 25 ft run with four elbows costs 30%. The shortest, straightest route to the outside cap — rigid duct, not sagging flex — is worth more than the next fan size.
- Use rigid duct in the attic, not flex. Flexible duct sags between supports, and every sag adds resistance a smooth rigid duct does not have. If you must use flex, pull it taut and support it every few feet. Insulate any duct run through an unconditioned attic, or condensation drips back into the fan.
- Put the fan over the shower, not the door. The fan should sit over or very near the shower or tub, where the steam is made — HVI’s guidance — not over the door where it pulls in dry hallway air and leaves the steam behind.
- Give the air a way in. An exhaust fan can only pull out the air that can get in. A bathroom door cut ¾ in short at the bottom, or a transfer grille, is the intake — without it the fan starves and the mirror stays fogged.
- Run it 20 minutes after the shower. HVI’s guidance: leave the fan on for 20 minutes after you shower. A timer switch or a humidity sensor does it automatically — a plain switch relies on memory, and memory fails.
- An enclosed toilet needs its own fan. HVI says a toilet in its own little room should have its own exhaust fan. One fan in the main room does not ventilate a closed compartment.
- Check the 0.25 in. w.c. figure before you buy. The box number is at 0.1 in. w.c.; the HVI-certified figure at 0.25 in. w.c. is what a real duct run delivers. A “110 CFM” Broan AE110K delivers 92 CFM at 0.25 in. w.c. — size on that number.
- Do not vent into the attic. The duct must discharge directly outside through a wall cap or roof cap, with a backdraft damper. Venting into the attic dumps a shower’s worth of moisture into the roof every day — the mould that follows costs far more than the duct.
- Size the duct to the fan, not the hole in the ceiling. A 150 CFM fan on a 4-inch duct is a 100 CFM system with extra noise. If the tool says 6 inches, fit 6 inches — reducing the duct to fit the hole you already have is the most common sizing mistake after buying too small.
Common mistakes
- Buying the box number. The CFM on the box is measured at 0.1 in. w.c. with almost no duct. On a real 10 ft run with two elbows it delivers about 10% less, and at 0.25 in. w.c. a 110 CFM fan delivers 92 CFM. Size on the HVI-certified 0.25 in. figure, or buy one size up.
- Forgetting the duct entirely. The most common error in bathroom fan sizing: the room needs 80 CFM, so an 80 CFM fan is bought — then a 20 ft duct with two elbows delivers about 72 CFM. The duct loss is not a footnote; it is a whole fan size.
- Using the fixture method in a small bathroom. A 10 × 8 ft bathroom with a toilet and a shower is 80 CFM by the area method, not 100 CFM by adding the fixtures — HVI uses fixtures only above 100 sq ft. Adding fixtures in a small bathroom oversizes the fan by a quarter.
- Using the area method in a big bathroom. The mirror error: a 12 × 12 ft bathroom is 144 CFM by area, but HVI sizes it by fixtures — 150 CFM for a toilet, shower and tub. The area method under-sizes large bathrooms because the moisture comes from the fixtures, not the floor.
- Ignoring the ceiling. A 10 × 8 ft bathroom at 8 ft needs 80 CFM; at 10 ft it needs 107 CFM. Two feet of ceiling is a whole fan size and a duct size — vaulted ceilings are the quiet reason a “right-sized” fan under-performs.
- Putting a big fan on a small duct. A 4-inch duct carries about 100 CFM, however big the fan. A 150 CFM fan on a 4-inch duct is a noisy 100 CFM system. Match the duct to the CFM first, then the fan to the duct.
- Buying loud to save money. A 2.5-sone fan is cheaper than a 1.0-sone fan — and it gets switched off, because nobody wants to hear it. A fan that is off moves 0 CFM, whatever the box says. Quiet is not a luxury; it is the feature that makes the fan run.
- Venting into the attic or soffit. The code requires the duct to discharge directly outside (IRC M1501.1). Into the attic, a shower’s moisture condenses on the cold roof deck every day — mould, rot and a repair bill that dwarfs the fan.
- Forgetting the 20 minutes. Switching the fan off with the light leaves the steam in the room. The moisture needs about 20 minutes of fan time after the shower to actually leave — a timer or humidity sensor, not memory.
- Trusting a chart that contradicts its own method. PickHVAC’s chart says 200 CFM for a 12 × 12 ft bathroom; the HVI fixture method it claims to follow says 150 CFM, and HVI’s own example agrees. A chart that cannot reproduce its own source’s worked example is not a source.
Factors that affect accuracy
- Floor area — the HVI area method. Up to 100 sq ft, the room needs about 1 CFM per square foot. It is the first multiplication, and the one that governs most ordinary bathrooms.
- Fixtures — the HVI fixture method. Above 100 sq ft the floor stops mattering and the fixtures take over: 50 CFM each for a toilet, shower and tub, 100 for a jetted tub. A big bathroom with three fixtures needs 150 CFM, whatever the floor area says.
- Ceiling height — the volume check. Above 8 ft the fan has to change more air: room volume × 8 air changes an hour ÷ 60. A 10 ft ceiling on a 10 × 8 ft room lifts the figure from 80 to 107 CFM. The alternative method (scale the area figure by height ÷ 8) gives 100 CFM — the page shows both.
- Duct length — equivalent length. Every foot of straight duct and every elbow adds resistance. Equivalent length is straight duct + 5 ft per 90° elbow, and the loss is 0% to 10 ft, 10% to 25 ft, 20% to 50 ft and 30% above. A long duct is a whole fan size.
- Duct diameter — the hard ceiling. A 3-inch duct carries about 50 CFM, 4-inch about 100, 6-inch about 200. No fan, however big, pushes more air through a duct than the duct can carry — and trying makes noise, not airflow.
- Duct material — rigid beats flex. Smooth rigid metal duct has the lowest friction; flexible duct, especially sagging or compressed, can lose 30–50% of its capacity. The derating bands on this page assume a decent rigid run — a bad flex run costs more.
- Operation — intermittent or continuous. The code floor is 50 CFM for a fan on a switch and 20 CFM for one that runs all the time. Continuous operation is a different compliance path, not a smaller fan doing the same job — it must actually run continuously.
- Fan curve — the 0.25 in. w.c. figure. A fan’s delivered airflow falls as the duct’s resistance rises. The HVI-certified rating at 0.25 in. w.c. is the figure that matches a real duct run; the box number at 0.1 in. w.c. is the figure that matches a laboratory.
- Sones — whether the fan gets used. 1.0 sone or less is quiet, 2.0 is common, over 2.0 is loud. The code allows up to 3 sones for a switched fan and 1 sone for a continuous one — but a loud fan gets switched off, and an off fan moves no air.
- Make-up air — the intake. An exhaust fan needs air to pull in: a door undercut of about ¾ in or a transfer grille. A sealed bathroom starves the fan, and no CFM figure survives a starved fan.
Sources & assumptions
- Method — the Home Ventilating Institute's published sizing methods (HVI, "Bathroom Ventilation"): 1 CFM per square foot of floor area for bathrooms up to 100 sq ft (about eight air changes per hour at an 8 ft ceiling); above 100 sq ft, add the fixtures instead — 50 CFM each for a toilet, shower and standard tub, 100 CFM for a jetted tub; an enclosed toilet compartment gets its own fan. Confirmed 2026-11-16 against the HVI-cited pages PonderLoop's bathroom fan size calculator, BuildSolver's bathroom exhaust fan calculator, TNAADO's bathroom exhaust fan size calculator and Clear Air Living's exhaust fan size chart, all of which state the same two methods.
- Code floor — ASHRAE Standard 62.2 and the International Residential Code (IRC M1505.4.4 in the 2021 edition, M1505.5 in 2024): a bathroom or toilet room needs 50 CFM intermittent (on demand) or 20 CFM continuous. Confirmed 2026-11-16 against PonderLoop, BuildSolver, Building Code Trainer and the ASHRAE 62.2 auditor checklist ("All bathrooms have fans rated at 50 CFM ondemand or 20 CFM continuous"). Editions and local amendments differ — Oregon, for example, requires 80 CFM where the bathroom has a bath — so the page says to check the local code.
- Ceiling height — the volume check (room volume × 8 air changes per hour ÷ 60) applies only above an 8 ft ceiling: the PonderLoop / Nova plurality ("A ceiling over 8 ft raises the figure"). The alternative method (BuildSolver) scales the area figure by height ÷ 8, holding 7.5 air changes an hour — 10 × 8 ft at 10 ft: 107 CFM by the volume method, 100 CFM by the scaling method — and the page shows both columns in its ceiling-height table.
- Duct loss — the PonderLoop model: equivalent length = straight duct + 5 ft per 90° elbow; derating 0% at 10 ft equivalent or less, 10% at 11–25 ft, 20% at 26–50 ft, 30% above 50 ft; shop-for rating = required CFM ÷ (1 − loss). Labelled a typical estimate on the page: other sources put one elbow at 5–15 ft of equivalent length (EngineerFix), and flexible duct, a crushed run or a poor wall cap can cost more — the fan curve on the spec sheet governs.
- Duct size — 4 in up to 100 CFM, 6 in 100–200 CFM, 8 in above 200 CFM (PonderLoop; The Remodelers' bathroom ventilation guide — "typically 4 inches for fans up to 100 CFM and 6 inches for larger units"; The Tibble's duct length guide).
- Standard fan sizes — 50 / 70 / 80 / 110 / 150 CFM (BuildSolver: "round up to the nearest of 50, 70, 80, 110, 150 CFM — Common HVI-listed bath fan sizes"). Above 150 CFM the tool says the room needs two fans or an inline fan.
- Box number vs delivered airflow — the CFM on the box is measured at 0.1 in. w.c. static pressure; the HVI-certified figure at 0.25 in. w.c. is the honest one for a real duct run. Broan's spec sheet for the AE110K (HVI-2100 certified) lists 110 CFM at 0.1 in. w.c. and 92 CFM at 0.25 in. w.c., 1.0 sone — confirmed 2026-11-16 against the Broan specification sheet.
- Sones — 1.0 sone or less is quiet, 1.0–2.0 is common, over 2.0 is loud (Clear Air Living, The Remodelers). Code maximums: 3 sones for a switched (intermittent) fan and 1 sone for a continuous fan (California Title 24, via GVD Renovations); the ASHRAE 62.2 auditor checklist puts local occupant-controlled fans at three sones or less.
- The 50 CFM dispute, named on the page — HVI's chart lists 50 CFM for bathrooms under 50 sq ft, while a strict reading of the 1 CFM-per-square-foot rule gives 40 CFM for a 5 × 8 ft bathroom (BuildSolver's strict reading vs PonderLoop's safe reading, per the 2026-11-15 teardown). The answer never changes either way, because the 50 CFM code floor lifts both figures to 50 — the page shows all three methods as separate rows so the dispute is visible, not hidden.
- A chart to ignore — PickHVAC's bathroom fan chart says a 12 × 12 ft bathroom needs 200 CFM. The HVI fixture method says 150 CFM (toilet + shower + tub), and HVI's own worked example for a 20 × 12 ft bathroom with the same three fixtures is also 150 CFM. The 200 CFM figure contradicts the method it claims to follow, so this page does not use it.
- Canonical examples (this tool): 10 × 8 ft, 8 ft ceiling, toilet + shower, 10 ft duct + 2 elbows, 4 in, intermittent — area 80 sq ft, volume 640 ft³; area method 80 CFM, fixture method 100 CFM (shown, does not govern under 100 sq ft), volume check 85.3 CFM (shown, not applied at an 8 ft ceiling), code floor 50 CFM → required 80 CFM (37.8 L/s); equivalent duct 20 ft → 10% loss; shop-for 80 ÷ 0.9 = 88.9 → ~90 CFM (42.5 L/s); standard pick 110 CFM; 4-in duct OK. Same room at a 10 ft ceiling: volume 800 ft³ × 8 ÷ 60 = 106.7 → required 107 CFM (volume governs); shop-for 118.9 → ~120 CFM; pick 150 CFM; 4-in duct no longer enough → 6 in. 12 × 12 ft, toilet + shower + tub: 144 sq ft → fixture method 150 CFM governs; shop-for 166.7 → ~170 CFM; no single standard size → two fans or an inline fan; duct 6 in. Metric twin: 3 × 2.4 m, 2.4 m ceiling = 7.2 m² (77.5 sq ft) → required 78 CFM (36.8 L/s); 3 m duct + 2 elbows = 19.8 ft equivalent → 10% loss; shop-for 86.7 → ~90 CFM; pick 110 CFM.
- Conversions are exact: 1 CFM = 0.471947 L/s; 1 m² = 10.7639 ft²; 1 m³ = 35.3147 ft³; 1 ft = 0.3048 m.
- Run-on time — HVI's guidance is to leave the fan running for 20 minutes after a shower, so the moisture actually leaves the room. A timer switch or a humidity sensor does this automatically.
Figures checked on 28 November 2026 as part of the site-wide test run (3239 automated checks, all passing). See how we calculate and test.
Safety note
What this calculator doesn't do
- This is a sizing estimate, not a ventilation design. It follows the Home Ventilating Institute's published sizing methods and the ASHRAE 62.2 / IRC code minimums, but it does not model your fan's actual performance curve, the static pressure of your exact duct run, or the moisture load of your household. Always check the HVI-certified CFM at 0.25 in. w.c. on the exact model's spec sheet before you buy — the box number is measured at 0.1 in. w.c. and a long duct eats into it.
- The duct-loss derating is a typical estimate, not a measurement. Equivalent length (straight duct + 5 ft per 90° elbow) and the 0 / 10 / 20 / 30% bands come from the strongest rival calculator's published model; other sources put one elbow at 5–15 ft of equivalent length, and flexible duct, a crushed run or a poor wall cap can cost far more. The fan curve on the spec sheet governs — if the model you want publishes no curve, buy the next size up.
- It sizes one fan for one bathroom. A bathroom over 150 CFM, a bathroom with an enclosed toilet compartment, or a bathroom with two wet zones (a separate shower room and a toilet room) usually needs two fans or an inline fan — the tool says so when the figure passes 150 CFM, but it does not lay out where the second fan goes.
- It does not check your wiring, your duct route or your local code. A fan over a tub or shower must be on a GFCI-protected circuit and listed for the location; the duct must discharge directly outside, never into an attic or a soffit; and your jurisdiction may have adopted a different code edition or a stricter local rule (Oregon, for example, requires 80 CFM where the bathroom has a bath). Check the local code before you buy.
- This version sizes in CFM to the HVI / ASHRAE method, which is how fans are sold in North America. A UK Part F mode (litres per second) is not built yet — the results show the L/s equivalent of every CFM figure (1 CFM = 0.472 L/s) so you can shop either way.
Bathroom Fan Size Calculator — frequently asked questions
What size bathroom fan do I need?
A 10 × 8 ft bathroom with an 8 ft ceiling needs an 80 CFM fan — 1 CFM per square foot by the HVI area method. With a 10 ft duct run and two elbows, shop for a fan rated about 90 CFM, which means a standard 110 CFM fan on a 4-inch duct. A 5 × 8 ft bathroom needs only the 50 CFM code minimum, and a 12 × 12 ft bathroom with a toilet, shower and tub needs 150 CFM by the fixture method. Use the calculator above with your room and duct for your exact figure.
How many CFM do I need for a small bathroom?
50 CFM — the code minimum. A 5 × 8 ft bathroom is 40 sq ft, so the HVI area method gives 40 CFM, but ASHRAE 62.2 and the IRC set a floor of 50 CFM for an intermittent fan (20 CFM continuous), and the floor governs. Buy a 50 CFM fan, on a short straight 4-inch duct, at 1.0 sone or less — and run it for 20 minutes after a shower.
What size fan do I need for a 10×10 bathroom?
100 CFM by the area method — so buy a 110 CFM fan. A 10 × 10 ft bathroom is exactly 100 sq ft, the top of the HVI area method, so 1 CFM per square foot gives 100 CFM. The next standard size at or above 100 CFM is 110 CFM, and a 4-inch duct carries it (up to 100 CFM is the limit — on a long duct run, step up to 6 inches). If the ceiling is over 8 ft, the volume check takes over: at 10 ft it is 107 CFM, so you buy a 150 CFM fan on a 6-inch duct.
Is 50 CFM enough for a bathroom?
Yes, for a small bathroom on a short duct — and it is the legal minimum everywhere. 50 CFM is the ASHRAE 62.2 / IRC floor for an intermittent fan, and it is enough for a bathroom up to about 50 sq ft. It is not enough for a 10 × 8 ft bathroom (80 CFM), a tall ceiling (107 CFM at 10 ft), or a long duct run (a 50 CFM fan on a 20 ft duct with two elbows delivers about 45 CFM). Size the room first; the code floor is a minimum, not a target.
How do I calculate bathroom fan CFM?
For a bathroom up to 100 sq ft: floor area in square feet × 1 CFM. A 10 × 8 ft bathroom is 80 sq ft, so 80 CFM. Above 100 sq ft: add the fixtures — 50 CFM each for a toilet, shower and standard tub, 100 CFM for a jetted tub; a 12 × 12 ft bathroom with all three is 150 CFM. Above an 8 ft ceiling: volume × 8 ÷ 60 — a 10 × 8 ft room at 10 ft is 800 ft³ × 8 ÷ 60 = 107 CFM. Then take the largest figure, and divide by (1 − the duct loss) for the rating to shop for. The calculator above does all of it.
What size duct do I need for a bathroom fan?
4 inches for most bathrooms — up to 100 CFM. A 3-inch duct carries about 50 CFM (powder rooms only); a 4-inch duct carries up to about 100 CFM; a 6-inch duct carries 100–200 CFM; an 8-inch duct carries over 200 CFM. The duct is the hard ceiling: a 150 CFM fan on a 4-inch duct is a noisy 100 CFM system. Keep the run short and straight, use rigid duct rather than sagging flex, and always discharge directly outside — never into the attic.
How loud is a bathroom fan in sones?
Aim for 1.0 sone or less — quiet. Sones measure perceived loudness: 0.5 is barely audible, 1.0 is quiet, 1.0–2.0 is common, and over 2.0 is loud enough to get switched off. The code allows up to 3 sones for a switched fan and 1 sone for a continuous fan, but those are maximums, not targets. A quiet fan gets used — and a fan that runs is the whole point.
How long should I run the bathroom fan after a shower?
20 minutes. HVI’s guidance is to leave the fan running for 20 minutes after you shower, so the moisture actually leaves the room instead of condensing on the walls and ceiling. A timer switch or a humidity-sensing fan does this automatically. Switching the fan off with the light leaves the steam in the room — the mirror clears, but the moisture stays.
How many litres per second is 80 CFM? (metric)
80 CFM is 37.8 L/s. The conversion is litres per second = CFM × 0.472, so 50 CFM is 23.6 L/s, 100 CFM is 47.2 L/s, 110 CFM is 51.9 L/s and 150 CFM is 70.8 L/s. Fans are sold in CFM in North America and in L/s in the UK and Europe, but the air is the same: a 3 × 2.4 m bathroom (7.2 m², 77.5 sq ft) needs about 78 CFM, or 36.8 L/s.
What size bathroom fan do I need for a metric room?
Work in square feet for the HVI method, then convert. A 3 × 2.4 m bathroom is 7.2 m², which is 77.5 sq ft (1 m² = 10.764 sq ft), so the area method gives 77.5 CFM — the tool rounds the requirement up to 78 CFM (36.8 L/s). With a 3 m duct and two elbows (19.8 ft equivalent) the duct loss is 10%, so shop for about 90 CFM (42.5 L/s) — a standard 110 CFM fan on a 100 mm (4-inch) duct. A 3.6 × 3.6 m bathroom is 12.96 m² (139.5 sq ft), over the 100 sq ft line, so it is sized by fixtures: toilet + shower + tub = 150 CFM (70.8 L/s).
Next step
Take the CFM, the duct size and the sones target to the store — and check the HVI-certified CFM at 0.25 in. w.c. on the exact model's spec sheet before you buy, because the box number is measured at 0.1 in. w.c. (a Broan 110 CFM fan delivers 92 CFM at 0.25 in. w.c.). Then price the fan's running cost with the electricity cost calculator, and check the room's insulation with the insulation calculator — a cold bathroom wall condenses moisture no fan can fix.
Save this estimate: use the Copy link button in the results box above to share these exact inputs, or Print results for a paper copy to take to the store.