Radiator Size Calculator

Radiator sizing is a heat-loss question before it is a shopping question: how many watts does the room lose on the coldest day, and what size of radiator replaces them at your system’s water temperature? This radiator size calculator works out the heat loss in watts and BTU/h from the room’s volume, its use (a bathroom needs more heat per cubic metre than a kitchen), the insulation, the outside walls and the windows — the CIBSE room-factor method, with the adjustments the strongest tool pages publish. It then converts the answer to the Delta-T50-rated output you actually shop for: a gas boiler at Delta-T50 needs no conversion, but a heat pump at Delta-T30 needs a radiator rated at nearly twice the heat loss, because the same radiator gives off only about half its rated output at the lower water temperature. The result is a Type 11–33 shortlist at 600 mm high, a two-radiator split when the room passes 8,000 BTU/h, and a US baseboard length for American homes. For the running cost of the heat, use the heating cost calculator; for the room’s cooling load, the BTU calculator; and for cutting the heat loss itself, the insulation calculator.

Quick answer: A typical 5 × 4 m living room with a 2.4 m ceiling needs about 2,995 W (10,220 BTU/h) of heat — with this calculator’s 10% design margin, 3,295 W (11,242 BTU/h). At Delta-T50 (a gas boiler) that is a Type 22 radiator 600 mm high × 2,000 mm long (3,500 W), or two Type 22 600×1000s for more even heat. On a heat pump at Delta-T30 the same room needs a 6,398 W Delta-T50-rated radiator — nearly twice the size. Enter your room below for your exact numbers.
The longest wall of the room, in metres or feet. Measure wall to wall — the tool works from volume, so a wrong length is a wrong answer.
The shorter wall of the room. For an L-shaped room, split it into two rectangles that do not overlap and run each one separately.
Floor to ceiling — 2.4 m (8 ft) is standard in most homes. A 3 m Victorian ceiling adds a quarter to the volume, and the heat loss with it.
Bathrooms are kept warmest (22°C) so they need the most heat per cubic metre; kitchens get free heat from cooking, so they need the least. The factors are the CIBSE room factors two published sources agree on.
The single biggest lever after room size: a poorly insulated room needs half as much heat again as a good one. If you are unsure, pick Average — it is the honest middle, and the margin covers the rest.
How many of the room’s walls face outside (0–4). Each one adds 10% — a corner room with two outside walls loses far more heat than a middle room with none.
Count each single-glazed window — each one adds 20%. Single glazing loses roughly twice the heat of double glazing per window, which is why it costs double here.
Count each double-glazed window — each one adds 10%. Triple glazing counts as double here; the difference is inside the margin.
A patio door or a large bay is a wall of glass — it adds 20%, the same as a single-glazed window, because it loses heat at roughly the same rate.
A north-facing room gets no direct sun in winter, so it adds 10%. A south-facing room gets free solar heat — this tool gives it no discount, which keeps the answer on the safe side.
Heat rises: a heated room below warms your floor from underneath, so the tool takes 5% off. A room over an unheated garage or a cold cellar gets no discount.
Delta-T is the gap between the radiator’s average water temperature and the room. Radiators are rated at ΔT50 (75°C flow / 65°C return, 20°C room); at ΔT30 a radiator gives off only 51.5% of its rating, so you need to buy nearly twice the size. If you are unsure, ΔT50 is the safe default for a boiler.
The longest clear wall run where the radiator can go, in the same units as the room. Leave blank to skip the fit check — with it, the tool tells you whether the suggested radiator fits, or whether two smaller ones (or a taller radiator) would suit the wall better.

Planning this project? Save to Pinterest to find this calculator again later.

How to use the Radiator Size Calculator

  1. Measure the room. Length, width and ceiling height, wall to wall and floor to ceiling. A 5 × 4 m room with a 2.4 m ceiling is 48 m³ — volume is what the tool works from, so measure in metres or feet and let the tool convert.
  2. Pick the room type. A living room needs 40 W/m³, a bathroom 45, a bedroom 35, a kitchen 30. The room type sets the CIBSE design temperature the room is sized to hold — 21°C for living rooms, 22°C for bathrooms, 18°C for kitchens.
  3. Be honest about insulation. Poor means draughty with single glazing and little insulation (×1.5); Average means some insulation and double glazing (×1.2); Good is a modern well-insulated home (×1.0). If you are between two, take the worse one — an undersized radiator is a cold room, an oversized one just costs a little more and a thermostatic valve trims it.
  4. Count the heat leaks. Outside walls (+10% each), single-glazed windows (+20% each), double-glazed windows (+10% each), a patio door or large bay (+20%), a north-facing main window (+10%). Take 5% off for a heated room below. These adjustments are the difference between a rule-of-thumb guess and a room-factor calculation.
  5. Pick your system’s Delta-T. ΔT50 for a gas or oil boiler — that is the rating on the box. ΔT40 or ΔT35 for a low-temperature condensing boiler. ΔT30 for a heat pump, ΔT25 for a very low flow temperature. The tool divides your heat loss by the Stelrad operating factor for that Delta-T, so the size you shop for is the Delta-T50-rated size.
  6. Read the heat loss first. The result shows the room’s heat loss in watts and BTU/h, then the Delta-T50-rated output to shop for. At ΔT50 they are the same number; at ΔT30 the shop-for figure is nearly double the heat loss — that is the radiator doing the same job with cooler water.
  7. Pick a radiator from the shortlist. The tool lists the shortest Type 11, 21, 22 and 33 radiators at 600 mm high that meet the shop-for output. Type 22 (double panel, double convector) is the usual choice for a living room; Type 11 is slimmer and suits a hallway; Type 33 is the heavy lifter for a big room on a heat pump.
  8. Split big rooms in two. Over 8,000 BTU/h, two radiators heat a room more evenly than one — the tool shows the split size. Two Type 22 600×1000s (1,750 W each) beat one Type 22 600×2000 on opposite walls, and they keep working if one valve sticks.
  9. Check the wall space. If you entered the available wall run, the tool tells you whether the suggested radiator fits. If it does not, two smaller radiators on different walls — or a taller radiator, or a vertical designer radiator — usually solve it without losing output.
  10. Buy on the Delta-T50 rating, and check the brand. Compare radiators on their ΔT50 output only — a quote at ΔT60 flatters the radiator by about 27%. Then check the output on the exact model you buy: one maker’s Type 22 600×1000 is 1,830 W and another’s is 1,750 W, and the page’s tables are the published figures, not your radiator’s datasheet.

Radiator Size Calculator formula

Heat loss (W) = room volume (m³) × room factor (W/m³) × insulation multiplier × (1 + feature adjustments) × 1.10 design margin

BTU/h = watts × 3.412

Output to shop for (ΔT50-rated, W) = heat loss ÷ Stelrad operating factor (ΔT60 1.267, ΔT50 1.000, ΔT45 0.872, ΔT40 0.748, ΔT35 0.629, ΔT30 0.515, ΔT25 0.406)

Room factors (W/m³): living/dining 40 · bathroom 45 · bedroom/study 35 · kitchen 30 · hallway 35 · conservatory 60–80 (tool uses 70). Insulation: poor ×1.5 · average ×1.2 · good ×1.0 · excellent ×0.85. Feature adjustments: +10% per outside wall · +20% per single-glazed window · +10% per double-glazed window · +20% patio door or large bay · +10% north-facing · −5% heated room below.

US mode: baseboard length (ft) = BTU/h ÷ 550. EDR: steam = BTU/h ÷ 240, hot water = BTU/h ÷ 150–170 (tool uses 160). The BTU/ft³ figures behind the US output are the CIBSE factors converted (living 3.87, bathroom 4.35, bedroom 3.38, kitchen 2.90 BTU/ft³) — not the hotter Turnbull figures (5/6/4/3), which run about 29% high against CIBSE for a living room.

The Stelrad factors follow the (50 ÷ ΔT)1.3 law: a radiator’s output falls with the temperature gap to the power 1.3, which is why the drop is not linear — ΔT40 is not 20% below ΔT50, it is 25% below, and ΔT30 is not 30% below, it is 48.5% below. One popular site’s “derate ~17% for ΔT40 / ~30% for ΔT30” line is wrong on both counts and should not be used.

Worked example

Worked example — 5 × 4 m living room, 2.4 m ceiling, average insulation, 2 outside walls, 1 double-glazed window, gas boiler (ΔT50). This reproduces the published worked example step by step, with the tool’s design margin shown as its own step at the end.

  1. Volume: 5 × 4 × 2.4 = 48 m³ (1,695 ft³).
  2. Base heat loss: 48 m³ × 40 W/m³ (living room) = 1,920 W.
  3. Insulation: 1,920 × 1.2 (average) = 2,304 W.
  4. Features: 2 outside walls (+20%) + 1 double-glazed window (+10%) → 2,304 × 1.30 = 2,995 W.
  5. BTU: 2,995 × 3.412 = 10,220 BTU/h. This is the published figure, reproduced exactly.
  6. Design margin: the tool adds 10% (one published guide uses 15%; the worked example above carries no separate margin, so the margin is shown here, not hidden in the steps): 2,995 × 1.10 = 3,295 W (11,242 BTU/h).
  7. Shop for: at ΔT50 the factor is 1.000, so shop for 3,295 W. Shortest Type 22 at 600 mm high: 600×2000 (3,500 W). Type 33 600×1400 (3,430 W) also meets it. Type 11 and Type 21 would need more than 2.4 m of wall, so they are not offered as a single radiator.
  8. Or split it: 11,242 BTU/h is over the 8,000 BTU/h split point, so two radiators heat the room more evenly — two Type 22 600×1000 (1,750 W each, 3,500 W total) on opposite walls.
  9. Heat pump (ΔT30): shop for 3,295 ÷ 0.515 = 6,398 W ΔT50-rated (21,828 BTU/h) — nearly twice the size. Split: two Type 22 600×2000 (3,500 W each). Without the margin the same step is 2,995 × 1.94 = 5,811 W, about 5,800 W.
  10. US baseboard: 11,242 ÷ 550 = 20.4 ft of baseboard (about 20 ft 6 in). EDR: 46.8 sq ft steam (÷ 240) or 70.3 sq ft hot water (÷ 160).

Cross-checks the tool reproduces. A 2.5 × 2 m bathroom, 2.4 m ceiling, average insulation, no outside walls or windows: 12 m³ × 45 = 540 × 1.2 = 648 W (2,211 BTU/h) — the published figure, exactly. A 4.5 × 3.6 m living room, 2.4 m ceiling, average insulation, 2 outside walls, 1 double-glazed window: 38.88 m³ × 40 × 1.2 × 1.30 = 2,426 W before the margin — the figure this method gives for the room the method-comparison table below is built on.

Why do radiator calculators disagree? They do not all measure the same thing. For the same 4.5 × 3.6 × 2.4 m living room (2 outside walls, filled cavity, 1.92 m² of double glazing, heated above, suspended timber floor), the published methods give:

MethodHeat lossWhat it counts
U-value surface method (moretips)1,223 W (4,170 BTU/h)Each surface’s U-value and area, plus ventilation — the most accurate, and the only one a heat-pump survey uses.
W/m³, qssupplies convention1,788 W (6,100 BTU/h)Room volume × 40 W/m³ with its own adjustment set and a 15% margin.
W/m³, this tool’s convention (buildcalcu)2,426 W (8,277 BTU/h)Room volume × 40 W/m³, ×1.2 average insulation, ×1.30 features — before this tool’s 10% margin (2,669 W with it).
BTU/ft³, Turnbull (business-opt)2,615 W (8,925 BTU/h)5 BTU/ft³ for a living room — 51.8 W/m³, about 29% hotter than the CIBSE 40 W/m³ before any adjustments.

That is a 2.1× spread for the same room, and it is the honest truth about radiator sizing: room-factor methods are quick estimates that oversize against a full survey, and one guide warns that rules of thumb are “often wrong by 50% or more”. This tool uses the CIBSE room-factor convention because it is the one the strongest tool pages publish, it shows every step, and it adds a 10% margin rather than hiding the uncertainty. If the room matters — a heat pump, a big open-plan space, a listed building — get a room-by-room BS EN 12831 survey and use its figure instead.

BTU by room size — published ranges. These are the ranges the guides publish, not this tool’s outputs, and they assume a well-insulated room with the usual walls and windows already counted. A draughty room with three outside walls and single glazing will need more than the top of the range; the calculator prices each of those features separately, which is why its figure for the same room runs higher.

RoomPublished BTU/h rangeSources
Small bedroom (up to 10 m²)2,500–4,000fantasticservices; traderadiators 4,000–7,000 for a bedroom generally
Medium bedroom4,000–5,500fantasticservices
Living room (15–25 m²)5,500–8,500fantasticservices; traderadiators 5,000–9,000
Kitchen5,000–8,000traderadiators
Bathroom2,000–4,000traderadiators; a 2.5 × 2 m bathroom works out at 2,211 BTU/h by the formula
Hallway3,000–6,000traderadiators
Open-plan living (25 m²+)8,500–12,000+fantasticservices; qssupplies gives 8,500 BTU/h for a 5 × 6 m open-plan room
Conservatory6,000–10,000+traderadiators

Radiator outputs, Delta-T factors and costs

Room factors (W/m³) and design temperatures. The CIBSE room factors two published sources agree on. The design temperature is the room temperature the radiator is sized to hold on the coldest day.

RoomW/m³Design tempBTU/ft³ equivalent
Living / dining room4021°C3.87
Bathroom4522°C4.35
Bedroom / study3518–19°C3.38
Kitchen3018°C2.90
Hallway3518°C3.38
Conservatory60–80 (tool uses 70)21°C5.81–7.74

Stelrad operating factors (Delta-T). Divide your heat loss by the factor to get the Delta-T50-rated output to shop for. The “size multiplier” column is the same step the other way round: at ΔT30 you buy a radiator 1.94× the heat loss. Verified against Stelrad’s own published table and the (50 ÷ ΔT)1.3 formula, which agree to three decimal places at every point.

Delta-TTypical systemOperating factorSize multiplierDerate vs ΔT50
ΔT60Old high-temperature system1.267×0.79— (radiator gives 27% more)
ΔT50Gas / oil boiler — the standard rating1.000×1.000%
ΔT45Modern condensing boiler0.872×1.1513%
ΔT40Low-temperature boiler0.748×1.3425%
ΔT35Condensing boiler, low flow0.629×1.5937%
ΔT30Heat pump (air / ground source)0.515×1.9448.5%
ΔT25Heat pump, very low flow0.406×2.4659%

Radiator outputs at ΔT50, 600 mm high. Outputs scale linearly with length, so a 600×2000 Type 22 gives twice a 600×1000 (3,500 W). The 600×1000 figures are the ones two published sources agree on; the 600×600 figures are from materialcalculator. Always check the datasheet of the radiator you buy — one maker’s Type 22 600×1000 is 1,830 W, about 5% above the published figure.

TypePanels / convectors600×600600×1000Per metre (600 high)
Type 11Single panel, single convector1,860 BTU/h (545 W)3,400 BTU/h (1,000 W)1,000 W
Type 21Double panel, single convector2,700 BTU/h (791 W)4,600 BTU/h (1,350 W)1,350 W
Type 22Double panel, double convector3,500 BTU/h (1,026 W)6,000 BTU/h (1,750 W)1,750 W
Type 33Triple panel, triple convector4,800 BTU/h (1,407 W)8,400 BTU/h (2,450 W)2,450 W

UK costs (2026 reference ranges, moretips). These are UK prices for the radiator and the fitting — US prices differ, and the tool does not price radiators.

ItemTypical UK cost
Type 22 radiator, 600×1000£60–150
Thermostatic valve (TRV) pair£20–60
Designer / column radiator£200–800+
Plumber — like-for-like swap£150–300
Plumber — new position (new pipework)£250–500

Measurement tips

  • Size up, not down. An oversized radiator costs a little more and a thermostatic valve trims it; an undersized one leaves a cold room that no valve can fix. If you sit between two sizes, take the bigger one — the 10% design margin is there for the same reason.
  • Put the radiator under the window. It is the coldest surface in the room, and the rising warm air counters the cold draught falling off the glass. A radiator on an inside wall heats the room less evenly for the same output.
  • Two radiators beat one big one over 8,000 BTU/h. Opposite walls, roughly half the output each. The room heats evenly, there is no cold corner, and one valve sticking does not leave you with no heat at all.
  • Fit thermostatic radiator valves (TRVs). They let each room hold its own temperature — a bedroom at 18°C, a living room at 21°C — and they trim an oversized radiator instead of overheating the room. A TRV pair costs £20–60 and pays for itself in a heating season.
  • Do not box a radiator in. A cover, a shelf above it or a sofa pressed against it cuts the output by 10–20% — the warm air has nowhere to go. Leave at least 10 cm clear above and in front of a radiator.
  • Compare radiators on ΔT50 only. A quote at ΔT60 flatters the radiator by about 27% — a 2,000 W radiator at ΔT60 is only about 1,580 W at ΔT50. If a listing does not say which Delta-T its output is at, ask, and walk away if the seller cannot tell you.
  • Bleed a new radiator after the first week. Air trapped at the top leaves the top cold and the bottom hot, which looks exactly like an undersized radiator. A radiator key and two minutes fix it — and top the system pressure up afterwards.
  • For a heat pump, plan the radiators before the heat pump. At ΔT30 you need nearly twice the Delta-T50-rated output, which usually means bigger radiators, more radiators, or underfloor heating — and a BS EN 12831 room-by-room survey under MIS 3005-D, which is a condition of MCS certification.
  • Chrome towel rails give less heat than they look. A heated towel rail needs 20–25% more output than a plain radiator of the same size, and a chrome one gives off less heat than a white one of the same dimensions — size it up, and do not count on it to heat a cold bathroom on its own.
  • Insulate before you upsize. Draught-proofing, loft insulation and cavity-wall insulation cut the heat loss the radiator has to replace — a room that goes from Average to Good insulation needs a radiator a sixth smaller. The insulation calculator shows what the upgrade is worth.

Common mistakes

  • Buying on BTU without checking the Delta-T. The most expensive mistake in radiator shopping: a radiator quoted at ΔT60 gives 27% less heat at ΔT50, and half its rating at ΔT30. Always ask which Delta-T the output is rated at, and convert with the Stelrad factors on this page.
  • Using the ‘derate ~17% for ΔT40 / ~30% for ΔT30’ line. It is wrong on both counts — the true derates are 25% and 48.5% (Stelrad’s own table: 0.748 and 0.515). A heat-pump radiator sized on the wrong line comes out a third too small.
  • Trusting one calculator’s number as the truth. For the same room, published methods range from 1,223 W (U-value) to 2,615 W (Turnbull BTU/ft³) — a 2.1× spread. A single number without its method is a guess with a decimal point; read the method comparison on this page before you buy.
  • Forgetting the ceiling height. Heat loss follows volume, not floor area. A 3 m Victorian ceiling adds a quarter to the volume over a 2.4 m ceiling — a calculator that only asks for floor area will undersize every tall room in the house.
  • Counting the room but not the walls and windows. Two outside walls and a single-glazed window add 40% to the base figure. A room-factor table that ignores them is a table for a middle room with no windows — most rooms are not that room.
  • Sizing a heat pump from a rule of thumb. Heat pumps run at ΔT30 or lower, where a small error in the heat loss becomes a large error in the radiator size, and an undersized radiator means a cold house at the design temperature. Heat pumps need a room-by-room BS EN 12831 survey — it is a condition of MCS certification under MIS 3005-D.
  • Putting one huge radiator in a big room. Over 8,000 BTU/h, one radiator leaves a cold end. Two radiators on opposite walls heat the same room evenly for roughly the same money — and if one is off, the other still takes the edge off.
  • Covering the radiator. A decorative cover, a shelf hard above it or a sofa pushed against it cuts the output by 10–20%. A radiator that was sized right becomes a radiator that is a fifth too small, and the room never quite warms up.
  • Ignoring the towel rail. A bathroom heated only by a chrome towel rail is usually a cold bathroom: towel rails need 20–25% more output than a plain radiator of the same size, and chrome gives off less heat than white. Size the rail up, or add a small radiator as well.
  • Forgetting to bleed and balance. A new radiator full of air, or a system where the nearest radiator hogs the flow, looks exactly like undersizing — cold top, cold far rooms. Bleed the radiators and balance the lockshield valves before you blame the size.

Factors that affect accuracy

  • Room volume. The base of the calculation: length × width × height. Every cubic metre of a living room needs 40 W, so a 48 m³ room starts at 1,920 W before anything else is counted. Floor area alone tells you nothing — ceiling height is a third of the volume.
  • Room type and design temperature. Bathrooms are sized to 22°C and need 45 W/m³; kitchens to 18°C and 30 W/m³, because cooking adds free heat. The same 12 m³ room needs 540 W as a bathroom and 360 W as a kitchen — a 50% difference from the room’s use alone.
  • Insulation — the biggest lever. Poor insulation multiplies the base figure by 1.5, Average by 1.2, Good by 1.0, Excellent by 0.85. Going from Poor to Good nearly halves the radiator you need, which is why insulating first is usually cheaper than buying bigger radiators.
  • Outside walls. Each outside wall adds 10%. A corner room with two outside walls needs 20% more heat than a middle room of the same size, and a detached room with three or four outside walls needs 30–40% more.
  • Windows. Single glazing adds 20% per window, double glazing 10% — glass loses heat far faster than a wall. A room with three single-glazed windows needs 60% more heat than the same room with none, which is why glazing upgrades and radiator sizing go together.
  • Patio doors and bay windows. A wall of glass counts like a single-glazed window: +20%. A conservatory-style bay or a full-width patio door can dominate a room’s heat loss on its own.
  • Aspect. A north-facing room gets no direct sun in winter, so it adds 10%. A south-facing room gets free solar heat — this tool gives it no discount, which keeps the answer on the safe side for the coldest, dullest week of the year.
  • What is below. A heated room below warms the floor from underneath, so the tool takes 5% off. A room over an unheated garage, a cold cellar or open ground gets no discount — and a suspended timber floor over a ventilated void can lose more heat than the walls.
  • Delta-T — the system’s water temperature. The factor that turns a heat loss into a radiator size. At ΔT50 the shop-for figure equals the heat loss; at ΔT30 it is 1.94× the heat loss; at ΔT25 it is 2.46×. A heat pump does not change how much heat the room loses — it changes how much radiator you need to deliver it.
  • Radiator type and height. At 600 mm high, a metre of Type 11 gives 1,000 W, Type 21 gives 1,350 W, Type 22 gives 1,750 W and Type 33 gives 2,450 W. Taller radiators give more per metre of wall, which is why a 700 mm radiator can replace a longer 600 mm one when the wall is short — and why a vertical radiator suits a narrow wall.

Sources & assumptions

  • Method — CIBSE W/m³ room-factor with buildcalcu's adjustment set: heat loss (W) = room volume (m³) × room factor (W/m³) × insulation multiplier × (1 + feature adjustments) × 1.10 design margin; BTU/h = watts × 3.412. BuildCalcu's radiator BTU calculator (updated October 2026) publishes the same method, the same room-factor table and the same worked example this page reproduces; QS Supplies' BTU guide publishes the same formula and the same room factors, with a 15% margin instead of 10%.
  • Room factors and design temperatures — living/dining 40 W/m³ at 21°C, bathroom 45 at 22°C, bedroom/study 35 at 18–19°C, kitchen 30 at 18°C, hallway 35 at 18°C, conservatory 60–80 at 21°C (tool uses 70, the midpoint, and says so). BuildCalcu and QS Supplies agree on the factors; the CIBSE design temperatures (21°C living, 22°C bathroom, 18°C bedroom/kitchen/hall) are reproduced in the MCS Heat Load Calculator's design conditions per Business-Opt's BTU calculator.
  • Insulation and feature adjustments — poor ×1.5, average ×1.2, good ×1.0, excellent ×0.85; +10% per outside wall, +20% per single-glazed window, +10% per double-glazed window, +20% patio door or large bay, +10% north-facing, −5% heated room below (BuildCalcu). Design margin 10%: MaterialCalculator ('Radiator output should exceed calculated room heat loss by 10% as the minimum design margin — standard UK heating engineering practice') and MoreTips ('Choose a radiator whose output at ΔT50 is at least that figure plus about 10%'). QS Supplies uses 15% — the page says so.
  • Delta-T factors — Stelrad operating factors: ΔT60 1.267, ΔT50 1.000, ΔT45 0.872, ΔT40 0.748, ΔT35 0.629, ΔT30 0.515, ΔT25 0.406. Verified against Stelrad's own published operating-factor table (ΔT25 0.406, ΔT30 0.515, ΔT35 0.629, ΔT40 0.748, ΔT45 0.872; 'Output at Δt30 = 2000 × 0.515 = 1030'; 'divide the heat output required by the relevant operating factor') and against the (50 ÷ ΔT)^1.3 formula, which agrees to 3 decimal places at every point. QS Supplies' older correction table agrees to 2 decimal places (ΔT60 1.27, ΔT40 0.75, ΔT30 0.51, ΔT25 0.41). BS EN 442 ΔT50 = 75°C flow / 65°C return (70°C mean water) minus a 20°C room (Stelrad; QS Supplies and MoreTips agree).
  • The derate line this page flags as wrong — one popular site's 'derate ~17% for ΔT40 / ~30% for ΔT30' contradicts Stelrad's own table: the true derates are 25% (1 − 0.748) and 48.5% (1 − 0.515). A heat-pump radiator sized on the wrong line comes out about a third too small.
  • Radiator outputs — 600 mm high at ΔT50: Type 11 1,000 W / 3,400 BTU/h, Type 21 1,350 W / 4,600, Type 22 1,750 W / 6,000, Type 33 2,450 W / 8,400 (BuildCalcu = MoreTips, identical; outputs scale linearly with length). 600 × 600 mm: 1,860 / 2,700 / 3,500 / 4,800 BTU/h (MaterialCalculator). Brand variance about 10% (MoreTips); one maker's Type 22 600×1000 is 1,830 W, about 5% above the published figure.
  • Worked example, reproduced exactly — 5 × 4 × 2.4 m living room, average insulation, 2 outside walls, 1 double-glazed window: 48 m³ × 40 = 1,920 W × 1.2 = 2,304 W × 1.30 = 2,995 W = 10,220 BTU/h (BuildCalcu). The tool then adds its 10% margin (3,295 W = 11,242 BTU/h) as a separate, labelled step. Bathroom cross-check: 2.5 × 2 × 2.4 m, average, no adjustments — 12 m³ × 45 = 540 × 1.2 = 648 W = 2,211 BTU/h (BuildCalcu).
  • Method spread, same published room (4.5 × 3.6 × 2.4 m living, 2 walls, filled cavity, 1.92 m² double glazing, heated above, suspended timber floor) — U-value surface method 1,223 W (4,170 BTU/h) per MoreTips ('Adding 10% gives about 1,223 W'); QS Supplies W/m³ 1,788 W (6,100 BTU/h); this tool's convention 2,426 W (8,277 BTU/h) before its margin; Turnbull BTU/ft³ 2,615 W (8,925 BTU/h) — the Turnbull method from Business-Opt (5 BTU/ft³ living = 51.8 W/m³, about 29% hotter than the CIBSE 40 W/m³) applied to the same room's inputs. A 2.1× spread, named on the page.
  • Room-size BTU ranges — QS Supplies' table (3 × 3 m bedroom 2,000 BTU; 4 × 5 m living 5,200; 5 × 6 m open-plan 8,500; 'when the total BTU requirement exceeds 8,000 BTU, it is usually more practical to use two smaller radiators'); Fantastic Services (small bedroom 2,500–4,000; living 15–25 m² 5,500–8,500; open-plan 25 m²+ 8,500–12,000+); Trade Radiators (living 5,000–9,000; bedroom 4,000–7,000; kitchen 5,000–8,000; bathroom 2,000–4,000; hallway 3,000–6,000; conservatory 6,000–10,000+). The page labels these as published ranges and explains why the calculator's figure runs higher.
  • US mode — baseboard 550 BTU/h per foot (BuildCalcu: 'divides the room's BTU requirement by 550 BTU per foot'; standard residential baseboard 500–600 BTU/h per foot at 180°F average water temperature). EDR: 240 BTU/h per sq ft steam, 150–170 hot water (tool uses 160). US BTU/ft³ figures are the CIBSE factors converted (living 3.87, bathroom 4.35, bedroom 3.38, kitchen 2.90), not Turnbull's 5/6/4/3.
  • Costs and practice — UK 2026 reference ranges from MoreTips: Type 22 600×1000 £60–150, TRV pair £20–60, designer/column £200–800+, plumber swap £150–300, new position £250–500. Two radiators over 8,000 BTU/h (QS Supplies). Towel rails need 20–25% more output than a plain radiator of the same size, and chrome rails give off less heat than white (BuildCalcu). Covers, shelves and furniture against a radiator cut output 10–20% (BuildCalcu). Heat-pump sizing needs a room-by-room BS EN 12831 survey under MIS 3005-D — an MCS requirement (Business-Opt, MaterialCalculator, BuildCalcu all state it).
  • Conversions — 1 W = 3.412 BTU/h; 1 m³ = 35.3147 ft³; 1 m = 3.28084 ft; ΔT60 quotes flatter a radiator by 26.7% against ΔT50 (1.267 factor; multiply a ΔT60 figure by 0.789 to get ΔT50).

Figures checked on 28 November 2026 as part of the site-wide test run (3239 automated checks, all passing). See how we calculate and test.

Safety note

Radiators run hot enough to burn — keep small children away from bare radiators and never drape clothes or towels over one to dry them: it is a fire risk as well as cutting the output by 10–20%. Gas work must be done by a Gas Safe registered engineer in the UK (a licensed HVAC contractor in the US); never break into a gas pipe or move a boiler yourself. Bleeding a radiator releases hot water under pressure — use a radiator key, keep your hand clear, and top the system pressure up afterwards. A heat-pump install needs a room-by-room heat-loss survey by a qualified installer — never size one from a rule of thumb.
Please note: material estimates are approximate. Always confirm product coverage with the manufacturer and buy a little extra for cuts, waste and future repairs.

What this calculator doesn't do

  • This is a quick estimate, not a BS EN 12831 heat-loss survey. Room-factor methods oversize against a full surface-by-surface survey — for one published room the U-value method gives 1,223 W where this tool's convention gives 2,426 W before its margin (see the method comparison below). For a heat pump, a room-by-room BS EN 12831 survey under MIS 3005-D is not optional — never size a heat-pump system from this tool alone.
  • It sizes one rectangular room at a time. L-shaped rooms, open-plan spaces and rooms with a vaulted or sloping ceiling need splitting into rectangles (or a surveyor's calculation) — the tool cannot see your room shape, and a conservatory with a glass roof loses heat faster than any room-factor table captures.
  • The conservatory factor is a midpoint, not a measurement. Published guidance gives 60–80 W/m³ for conservatories and the tool uses 70 — a glass-roofed conservatory in an exposed spot can need the top of the range or more, and a well-insulated garden room can need far less.
  • Radiator outputs vary by brand by about 10%. The Type 11–33 outputs on this page (1,000 / 1,350 / 1,750 / 2,450 W per metre at 600 mm high) are the published figures two sources agree on, but one maker's Type 22 600×1000 is 1,830 W and another's is 1,750 W — always check the output on the radiator you actually buy before ordering.
  • It does not size the boiler, the pipework or the pump, and it does not price the job. The UK cost table below is a 2026 reference range from one guide — get a quote from your installer, and price the running cost of the heat with the heating cost calculator.

Radiator Size Calculator — frequently asked questions

What size radiator do I need?

A typical 5 × 4 m living room with a 2.4 m ceiling needs a Type 22 radiator 600 mm high × 2,000 mm long (3,500 W). The room loses about 2,995 W (10,220 BTU/h); with this calculator’s 10% design margin that is 3,295 W (11,242 BTU/h), and the shortest Type 22 meeting it at 600 mm high is 2,000 mm long. For your own room, enter its size, room type, insulation and windows above — the tool gives you the heat loss, the size to shop for at your system’s Delta-T, and the shortest Type 11, 21, 22 and 33 that meet it. On a heat pump at ΔT30 the same room needs a 6,398 W Delta-T50-rated radiator, nearly twice the size.

How many BTU do I need for a 12×12 room?

About 7,640 BTU/h (2,239 W) for a 12 × 12 ft living room with an 8 ft ceiling, average insulation, 2 outside walls and 1 double-glazed window. The volume is 1,152 ft³ (32.6 m³); × 40 W/m³ = 1,305 W; × 1.2 (average insulation) = 1,566 W; × 1.30 (2 walls + 1 double-glazed window) = 2,036 W; + 10% design margin = 2,239 W = 7,640 BTU/h. A Type 22 radiator 600 mm high × 1,400 mm long (2,450 W) covers it. A bedroom the same size needs less — about 6,680 BTU/h — because bedrooms are sized to 18–19°C instead of 21°C.

What is Delta-T, and why does it change the radiator size?

Delta-T (ΔT) is the gap between the radiator’s average water temperature and the room temperature. Radiators are rated at ΔT50: 75°C flow and 65°C return (70°C mean water) minus a 20°C room. A gas boiler runs close to ΔT50, so the rating on the box is the output you get. A heat pump runs at ΔT30 — cooler water, a smaller gap — and the same radiator gives off only 51.5% of its rated output (Stelrad’s operating factor for ΔT30 is 0.515). So you divide the heat loss by 0.515 to get the Delta-T50-rated size to buy: a room losing 3,295 W needs a 6,398 W radiator at ΔT30. The full factor table is above — ΔT60 1.267, ΔT50 1.000, ΔT45 0.872, ΔT40 0.748, ΔT35 0.629, ΔT30 0.515, ΔT25 0.406.

How much bigger a radiator do I need for a heat pump?

Nearly twice as big — 1.94× the heat loss at ΔT30. A 5 × 4 m living room losing 2,995 W needs a 5,811 W Delta-T50-rated radiator at ΔT30 (2,995 × 1.94); with this calculator’s 10% margin that is 6,398 W. At ΔT25 the multiplier is 2.46×. That usually means bigger radiators, more radiators, or underfloor heating — and a room-by-room BS EN 12831 survey under MIS 3005-D, which is a condition of MCS certification. Never size a heat-pump system from a rule of thumb: at ΔT30 a small error in the heat loss becomes a large error in the radiator size.

How do I calculate radiator BTU in metric?

Work in watts, then multiply by 3.412. Measure the room in metres and multiply length × width × height for the volume in cubic metres; multiply by the room factor (living room 40 W/m³, bathroom 45, bedroom 35, kitchen 30); multiply by the insulation factor (poor 1.5, average 1.2, good 1.0, excellent 0.85); add the feature adjustments (+10% per outside wall, +20% per single-glazed window, +10% per double-glazed window); add the 10% design margin; then convert watts to BTU/h by multiplying by 3.412. Example: a 5 × 4 × 2.4 m living room is 48 m³ × 40 = 1,920 W × 1.2 = 2,304 W × 1.30 = 2,995 W × 1.10 = 3,295 W × 3.412 = 11,242 BTU/h. One cubic metre is 35.3147 cubic feet if you are converting from feet.

What size radiator for a 20 m² living room?

A Type 22 radiator 600 mm high × 2,000 mm long (3,500 W) for a 20 m² living room with a 2.4 m ceiling, average insulation, 2 outside walls and 1 double-glazed window. The volume is 48 m³ (20 m² × 2.4 m), so the heat loss is 48 × 40 = 1,920 W × 1.2 = 2,304 W × 1.30 = 2,995 W (10,220 BTU/h), or 3,295 W (11,242 BTU/h) with the 10% design margin. A well-insulated 20 m² room with one outside wall and no windows needs less — about 2,323 W (7,927 BTU/h), a Type 22 600×1400. The calculator prices each wall and window separately, which is why its figure runs higher than the published room-size BTU tables that assume a well-insulated room.

Type 11 vs Type 22 — which radiator should I buy?

Type 22 for most living rooms; Type 11 where the wall is tight or the room is small. At 600 mm high, a metre of Type 11 (single panel, single convector) gives 1,000 W and a metre of Type 22 (double panel, double convector) gives 1,750 W — 75% more heat from the same length of wall, at the cost of about twice the depth (roughly 100 mm vs 60 mm). Type 21 (1,350 W/m) sits between them; Type 33 (2,450 W/m) is the heavy lifter for a big room or a heat pump. The tool lists the shortest length of each type that meets your heat loss, so you can see the trade-off: a Type 11 that needs 2.4 m of wall vs a Type 22 that needs 1.4 m.

Do I need one big radiator or two smaller ones?

Two, once the room passes 8,000 BTU/h. One big radiator heats the end of the room it sits in and leaves the far end cold; two radiators on opposite walls heat the room evenly for roughly the same money. The tool shows the split size whenever the shop-for output passes 8,000 BTU/h — for the 5 × 4 m worked example that is two Type 22 600×1000s (1,750 W each) instead of one Type 22 600×2000. Two radiators also keep some heat going if one valve sticks, and they suit rooms where no single wall is long enough for the big radiator.

Why do radiator calculators disagree with each other?

Because they do not all measure the same thing. For the same 4.5 × 3.6 × 2.4 m living room, the U-value surface method gives 1,223 W, one W/m³ guide gives 1,788 W, this tool’s convention gives 2,426 W (2,669 W with its margin), and the Turnbull BTU/ft³ method gives 2,615 W — a 2.1× spread. Room-factor methods are quick estimates that oversize against a full survey, and one guide warns that rules of thumb are “often wrong by 50% or more”. The Turnbull figures run about 29% hotter than the CIBSE factors before any adjustments (5 BTU/ft³ = 51.8 W/m³ vs 40 W/m³ for a living room), and one popular site’s Delta-T derate line is wrong on both counts (it says ~17% for ΔT40 and ~30% for ΔT30; the true figures are 25% and 48.5%). Use a calculator that shows its method, and for a heat pump or a big room get a BS EN 12831 survey.

Can I use this calculator for a heat pump or baseboard heaters?

For baseboard heaters, yes — the tool gives the US baseboard length (BTU/h ÷ 550 per foot) and the EDR figures (steam ÷ 240, hot water ÷ 160) with every result. For a heat pump, the tool’s ΔT30 and ΔT25 settings show the Delta-T50-rated size you would need, but that is a starting point, not a design: heat-pump sizing needs a room-by-room BS EN 12831 heat-loss survey under MIS 3005-D, and MCS certification requires it. A heat pump also changes the system design — flow temperatures, pipe sizes and controls — which no radiator calculator can do. Use the tool to understand the scale of the radiators (nearly twice the size at ΔT30), then get the survey.

Next step

Take the Type, height and length from the shortlist — plus the BTU/h figure — to the merchant or your installer, and check the output on the exact model's datasheet before ordering, since brands vary by about 10%. Then price the running cost of the heat with the heating cost calculator, and see what insulation would save with the insulation calculator before you buy bigger radiators. If the room is on a heat pump, get a room-by-room BS EN 12831 survey — this tool is a starting point, not a design.