Generator Size Calculator

A generator that is too small stalls the moment the biggest motor starts; a generator that is too big costs more, burns more fuel and runs inefficiently. Sizing one comes down to three numbers. First, the running watts — what everything you want on at the same time draws while it runs. Second, the starting surge — the brief extra burst the single largest motor needs to spin up (a refrigerator that runs at 700 W needs 2,200 W for a fraction of a second). Third, headroom — about 20% so the generator is not pinned at full output. This generator size calculator does that arithmetic from an appliance library: set a quantity for each thing you want to run, add a custom appliance or two if yours is not listed, enter your altitude (generators lose about 3.5% of their power per 1,000 ft above sea level) and pick a safety margin. It returns the running total, the peak, the recommended watts with headroom, the next common generator size, the size in kVA and the current in amps — and it names the appliance that sets the surge, so you can see what is driving the size. For the heating load behind a winter outage, pair it with the BTU calculator; for a wood-heated backup, the firewood calculator works out the cords for the season.

Quick answer: With the defaults — one refrigerator, one furnace blower and the house lights, at sea level with 20% headroom: running load 2,100 W, largest extra surge 1,550 W (the furnace blower), peak 3,650 W, recommended 4,380 W — so the next common size is a 4,500 W generator (5.48 kVA, 36.5 A at 120 V). Add your own appliances and your altitude to get your number.
Anything not in the library — a 1 HP well pump, an electric range, a second refrigerator. Enter its running watts here and its starting watts below; leave both blank to ignore it.
The brief total draw when its motor starts. Leave blank if it has no motor (starting = running).
Generators lose about 3.5% of their rated power per 1,000 ft above sea level (Generac, Honda and Westinghouse manuals). Denver at about 5,280 ft loses about 18%.
Headroom keeps the generator off full output, covers nameplate figures that run high, and leaves room for one more load later. 20% is the field default.

Planning this project? Save to Pinterest to find this calculator again later.

How to use the Generator Size Calculator

  1. Start with the defaults: one refrigerator, one furnace blower and the house lights — the classic winter-outage essentials. Press Calculate to see the baseline, then adjust it to your house.
  2. Set a quantity for everything you want running AT THE SAME TIME. A second refrigerator counts; a microwave you will only use while the space heater is off does not — size for the worst moment, not for every appliance you own.
  3. Read the running watts in each label as typical figures, not measurements of your appliances. A modern ENERGY STAR refrigerator can run at 150–400 W, not 700 W; an old one can run higher. The nameplate on your appliance (or its manual) beats any table — use the custom-appliance rows for anything whose label you have checked.
  4. Watch which appliance sets the surge. The results name it: it is usually the furnace blower, the central air conditioner or a pump, not the biggest running load. If the surge-setter is something you can stagger — start the well pump before the air conditioner, for example — the size comes down.
  5. Enter your altitude. At sea level the derating is zero; at 5,000 ft the tool divides the requirement by 0.825, which is why the same essentials need a 6,500 W generator at sea level and a 7,500 W one in Denver. If you only ever run the generator at home, enter your home altitude, not the altitude of the store.
  6. Keep the safety margin at 20% unless you have a reason to change it. 0% means the generator runs flat out at your peak; 30% is for loads you have not measured. The margin applies to the peak (running + largest surge), which is the method the field's calculators use.
  7. Use the custom-appliance rows for anything not listed: a 1 HP well pump (about 2,000 W running, 4,000 W starting), an electric range, a second air conditioner. Enter running watts and, for a motor, starting watts; for a heater or any load with no motor, leave starting watts blank and it counts as running watts only.
  8. Read the results top to bottom: total running watts, the largest extra surge and which appliance sets it, the peak, the altitude derating, then the recommended size with headroom, the next common size, the type (portable or standby), the size in kVA and the current at 120 V and 240 V.
  9. Shop by RUNNING watts, not by the big number on the box. Generator boxes shout the starting (peak) watts; the running watts are the smaller number in the spec sheet, and that is the number the recommended size must meet or beat. A "7,500 W" generator is usually a 6,000 W running machine.
  10. If the recommended size lands just above a common size — 5,900 W against a 5,500 W model — take the next size up. Generators do not like running at 100% for hours, and the next size up is cheaper than the one that stalls on the coldest night of the outage.

Generator Size Calculator formula

Running watts = the sum of (quantity x running watts) for every appliance you want on at the same time. Starting watts are the total draw of a motor appliance in the fraction of a second it starts; the EXTRA surge is starting watts minus running watts (a refrigerator: 2,200 - 700 = 1,500 W extra). Peak watts = total running watts + the SINGLE largest extra surge — the Generac wattage worksheet method, which assumes one motor starts at a time. Recommended watts = peak watts x (1 + margin) / altitude factor, where the margin defaults to 20% and the altitude factor = 1 - 0.035 x altitude in feet / 1,000 (Generac, Honda and Westinghouse manuals: about 3.5% of rated power lost per 1,000 ft above sea level). Next common size = the smallest size in the ladder [1,000, 2,000, 2,500, 3,000, 3,500, 4,000, 4,500, 5,000, 5,500, 6,500, 7,500, 8,000, 9,000, 9,500, 10,000, 12,000, 12,500, 14,000, 15,000, 17,500, 18,000, 20,000, 22,000, 24,000, 26,000] that is at least the recommended watts. kVA = recommended kW / 0.8 (generators are conventionally rated at 0.8 power factor). Amps = recommended watts / volts (120 V and 240 V shown; 240 V is about 230 V outside North America). A portable generator's starting (peak) rating is typically about 25% above its running rating, so a generator whose running rating covers the recommended watts also covers the peak.Example (a) — defaults: refrigerator 1, furnace blower 1, house lights 1, sea level, 20% margin. Running = 700 + 800 + 600 = 2,100 W. Extra surges: refrigerator 2,200 - 700 = 1,500 W; furnace blower 2,350 - 800 = 1,550 W; lights 0. Largest = furnace blower 1,550 W. Peak = 2,100 + 1,550 = 3,650 W. Recommended = 3,650 x 1.20 / 1.00 = 4,380 W. Next common size = 4,500 W. kVA = 4.38 / 0.8 = 5.48 kVA. Amps = 4,380 / 120 = 36.5 A at 120 V; 4,380 / 240 = 18.25 A at 240 V. Type: portable generator.Example (b) — essentials: refrigerator 1, furnace blower 1, sump pump (1/2 HP) 1, house lights 1, LED TV 1, laptop 1, sea level, 20% margin. Running = 700 + 800 + 1,050 + 600 + 120 + 75 = 3,345 W. Extra surges: refrigerator 1,500 W; furnace blower 1,550 W; sump pump 2,150 - 1,050 = 1,100 W; the rest 0. Largest = furnace blower 1,550 W. Peak = 3,345 + 1,550 = 4,895 W. Recommended = 4,895 x 1.20 = 5,874 W. Next common size = 6,500 W. kVA = 5.874 / 0.8 = 7.34 kVA. Amps = 48.95 A at 120 V, 24.48 A at 240 V.Example (c) — central air: refrigerator 1, central AC (3 ton) 1, house lights 1, LED TV 1, sea level, 20% margin. Running = 700 + 3,500 + 600 + 120 = 4,920 W. Extra surges: refrigerator 1,500 W; central AC 7,000 - 3,500 = 3,500 W. Largest = central AC 3,500 W. Peak = 4,920 + 3,500 = 8,420 W. Recommended = 8,420 x 1.20 = 10,104 W. Next common size = 12,000 W. kVA = 10.104 / 0.8 = 12.63 kVA. Amps = 84.2 A at 120 V, 42.1 A at 240 V. Type: large portable or standby.Example (d) — altitude: the same essentials as (b) at 5,000 ft. Altitude factor = 1 - 0.035 x 5 = 0.825. Recommended = 5,874 / 0.825 = 7,120 W. Next common size = 7,500 W. kVA = 7.12 / 0.8 = 8.90 kVA. The same load needs one size up at 5,000 ft — the generator loses 17.5% of its rated power up there.Example (e, metric altitude): the same essentials as (b) at 1,524 m (5,000 ft). Altitude factor = 1 - 0.035 x 5,000 / 1,000 = 0.825, so the recommended size is again 7,120 W and the next common size 7,500 W. Enter metres directly — the tool converts.

Worked example

Essentials for a winter outage: one refrigerator, one furnace blower, one 1/2 HP sump pump, the house lights, one LED TV and one laptop, at sea level, 20% headroom. Step one — running watts: 700 + 800 + 1,050 + 600 + 120 + 75 = 3,345 W. Step two — extra surges: refrigerator 2,200 - 700 = 1,500 W; furnace blower 2,350 - 800 = 1,550 W; sump pump 2,150 - 1,050 = 1,100 W; lights, TV and laptop have no motors, so 0. Step three — largest surge: the furnace blower at 1,550 W. Step four — peak: 3,345 + 1,550 = 4,895 W. Step five — headroom: 4,895 x 1.20 = 5,874 W recommended. Step six — next common size: 6,500 W running. Step seven — kVA: 5.874 / 0.8 = 7.34 kVA. Step eight — current: 5,874 / 120 = 48.95 A at 120 V, 5,874 / 240 = 24.48 A at 240 V. A 6,500 W portable (about 8,125 W starting) covers the 4,895 W peak with room to spare. At 5,000 ft the same list needs 7,120 W recommended and a 7,500 W generator — altitude costs a whole size.

Appliance wattages — running watts / starting watts (total draw at startup). Typical figures; your nameplate is the final word.

ApplianceRunning wattsStarting wattsExtra surge
Refrigerator / freezer7002,2001,500
Chest freezer5001,5001,000
Furnace blower, gas or oil (1/2 HP)8002,3501,550
Central air conditioner, 3 ton3,5007,0003,500
Window air conditioner, 10,000–12,000 BTU1,2003,6002,400
Well pump, 1/2 HP1,0002,1001,100
Sump pump, 1/3 HP8001,300500
Sump pump, 1/2 HP1,0502,1501,100
Electric water heater4,5004,5000
Microwave, 1,000 W output1,5001,5000
Coffee maker1,2001,2000
Toaster1,2001,2000
Hair dryer1,5001,5000
Space heater1,5001,5000
House lights6006000
LED / LCD TV1201200
Desktop computer4004000
Laptop computer75750
Air compressor, 1 HP1,6004,5002,900
Circular saw1,4002,8001,400
Table saw1,8003,6001,800
RV air conditioner, 15,000 BTU1,8003,6001,800
Running watts: Generac wattage worksheet (2018) unless noted. Starting watts: EWEB generator sizing guide, miniwebtool and Generac-dealer charts (see Sources). A 1,000 W-output microwave draws about 1,500 W from the wall. Central AC starting watts vary by unit — 2x to 3x running (7,000–10,500 W for a 3-ton); the tool uses 7,000 W and says so. Resistive loads (heaters, toasters, microwaves, lights, electronics) have no surge: starting watts equal running watts.

Altitude derating — power lost per 1,000 ft above sea level: 3.5% (Generac, Honda, Westinghouse manuals):
AltitudePower lostPower leftWhat it means
Sea level0%100%No derating
1,000 ft (305 m)3.5%96.5%A 5,000 W generator delivers 4,825 W
2,000 ft (610 m)7%93%A 5,000 W generator delivers 4,650 W
3,000 ft (914 m)10.5%89.5%A 5,000 W generator delivers 4,475 W
5,000 ft (1,524 m)17.5%82.5%A 5,000 W generator delivers 4,125 W
5,280 ft (1,609 m) — Denver18.5%81.5%A 5,000 W generator delivers 4,075 W
8,000 ft (2,438 m)28%72%A 5,000 W generator delivers 3,600 W
10,000 ft (3,048 m)35%65%A 5,000 W generator delivers 3,250 W
Without the high-altitude carburetor jet kit the loss is worse; a hot day costs about another 1% per 10°F above 85°F. Fuel-injected (EFI) generators adjust the mixture automatically but still lose the same power to thin air.

Common generator sizes (running watts) and what they typically run:
Running wattsTypeTypically runs
1,000–2,000Small inverterPhone charging, laptop, a few lights, a small refrigerator (one at a time)
2,500–3,500Inverter / small portableRefrigerator, lights, TV, laptop — a 30-amp RV
4,500–5,500PortableEssentials: refrigerator, furnace blower, sump pump, lights, electronics
6,500–7,500PortableEssentials plus a well pump or a window AC
9,500–10,000Large portableEssentials plus a window AC and an electric water heater (staggered)
12,000–15,000Large portableMost of the house, including one central air conditioner
20,000–26,000StandbyWhole house, including central air and electric water heating
Sizes are the running-watts ratings of common Generac, Champion and Honda models; standby units (Generac Guardian 10–26 kW) are permanently installed and start automatically.

Measurement tips

  • Check the nameplate before you trust the table. Every appliance has a label (usually on the back or inside the door) giving volts and amps — watts = volts x amps. A refrigerator nameplate reading 120 V and 6 A is 720 W running, close to the table's 700 W; one reading 3 A is 360 W, and the table would oversize your generator by a whole step.
  • Size for the worst moment, not for the whole house. The generator only needs to cover what runs at the same instant. A microwave you use while the space heater is off, and a toaster you use while the hair dryer is off, do not all add up — but the refrigerator, the furnace blower and the lights do, because they run together all night.
  • Stagger the big motors. Start the well pump, let it finish, then start the air conditioner. Two motors starting in the same second is the one case where the single-surge rule breaks — and it is also the easiest to avoid by waiting ten seconds between switches.
  • Buy by running watts, not the box number. The big number on the box is the starting (peak) watts; the running watts are in the small print of the spec sheet. A "7,500 W" portable is usually a 6,000 W running machine — if the tool recommends 6,500 W, that box is too small.
  • Add the altitude before you buy, not after. A generator bought at a sea-level store and run at 5,000 ft delivers 17.5% less than its label — that is a full size step. Enter your home altitude in the tool, and if you camp or work higher, size for the highest altitude you will use it at.
  • Keep 20% headroom even if the arithmetic looks exact. Published wattages are averages, motors draw more as they age, and a generator run at 100% for hours runs hot, loud and short-lived. The 20% is also your allowance for the one load you forgot — there is always one.
  • For central air, check the compressor, not the air handler. The nameplate locked-rotor amps (LRA) give the true starting draw: starting watts = LRA x volts. A soft-start kit (about $300–$400 installed) can cut a 3-ton unit's starting surge roughly in half and drop you a whole generator size — ask your HVAC technician before buying a bigger generator.
  • Mind the fuel derate. The same generator makes less power on propane or natural gas than on gasoline — typically 10–20% less. If you plan to run on propane, size the generator on its propane rating, not its gasoline rating, or the tool's recommended size will be short by that same 10–20%.
  • Count the 240 V loads separately. A well pump, an electric water heater and a central air conditioner are usually 240 V loads; the rest are 120 V. The tool totals watts either way, but your transfer switch and inlet must be wired for the 240 V loads — a 120 V-only setup cannot run them at any wattage.
  • Test the size before the storm. Once the generator is home, run your actual load list on it for an hour: fridge, furnace, sump pump, lights. If it stumbles when the furnace kicks in, you have found the surge-setter in real life — and you still have time to exchange the unit or add a soft-start kit.

Common mistakes

  • Adding up every starting surge. The single most common sizing error: totalling the starting watts of the refrigerator, the furnace, the sump pump and the air conditioner together. Motors do not all start in the same second, so that number oversizes the generator by two or three times — and oversizing costs money, fuel and efficiency. Only the largest surge counts.
  • Buying by the peak number on the box. A generator advertised as "9,500 W" usually delivers 7,500 W running. If your load needs 8,000 W running, that box is too small even though the headline number is bigger than your load. Always read the running (rated) watts on the spec sheet.
  • Forgetting altitude. A 5,000 W generator at 5,000 ft is a 4,125 W generator. Buyers at altitude who size at sea level end up a full size short — and discover it on the first cold night, when the furnace and the refrigerator start together.
  • Forgetting the furnace blower. People size for the refrigerator and the lights and forget that a gas furnace still needs 800 W for its blower (2,350 W to start) — and without the blower there is no heat at all. The blower is the surge-setter in most winter-outage lists.
  • Sizing for everything you own instead of everything that runs at once. The toaster, the hair dryer, the microwave and the coffee maker are almost never on together. Adding all four adds 5,400 W to the answer for a moment that never happens — and pushes you from a 6,500 W portable to a standby unit.
  • Using the microwave's output watts. A "1,000 W microwave" draws about 1,500 W from the wall — the 1,000 W is the cooking power, not the electrical draw. The same trap applies to any appliance whose headline number is its output, not its input.
  • Running a generator indoors or in the garage. Carbon monoxide kills in minutes and you cannot smell it. A generator belongs at least 20 ft from the house, exhaust pointing away, with working CO alarms inside — never in a garage, even with the door open.
  • Backfeeding through a wall outlet. Plugging a generator into a household outlet energises the house wiring backwards and can kill a line worker restoring power — and it is illegal in most places. Hardwired loads need a transfer switch or an interlock installed by a licensed electrician.

Factors that affect accuracy

  • Running watts of the load list: every appliance that runs at the same time adds its running watts. The essentials list in the worked example is 3,345 W; adding a 4,500 W electric water heater more than doubles it to 7,845 W — one resistive load can dominate the whole answer.
  • Largest starting surge: the peak is set by one motor, and which one matters. In the essentials example the furnace blower's 1,550 W extra surge sets the peak; add a 3-ton central air conditioner and its 3,500 W surge takes over, pushing the peak from 4,895 W to 8,420 W.
  • Central air conditioner size: a 3-ton unit runs at about 3,500 W and surges to 7,000–10,500 W. It is the single biggest step-change in generator sizing — with central air you are usually in 12,000 W portable or standby territory, without it you are usually in a 5,000–7,500 W portable.
  • Altitude: 3.5% of rated power lost per 1,000 ft. The same essentials need 5,874 W recommended at sea level and 7,120 W at 5,000 ft — one whole generator size. At 10,000 ft the loss is 35% and the same load needs a 9,000 W machine.
  • Temperature: about 1% per 10°F above 85°F, on top of altitude. A hot afternoon at 5,000 ft costs roughly another 5–10% — the tool does not model it, so leave extra headroom if you will run the generator on hot days at altitude.
  • Safety margin: 20% is the default and the field standard. Dropping it to 0% saves one generator size on paper and costs reliability in practice — the generator runs flat out, and any nameplate figure that runs high pushes it over. Raising it to 30% buys room for a future load.
  • Fuel type: the same generator makes less power on propane or natural gas than on gasoline, typically 10–20% less. Size on the fuel you will actually burn, or the recommended watts will be short by that margin when it matters.
  • Motor age and condition: an old refrigerator compressor or a worn well pump can draw 10–20% more on startup than a new one. If your appliances are old, the nameplate figures are minimums, not maximums — and the 20% headroom is doing real work.
  • Simultaneous starts: the tool assumes one motor starts at a time. Two big motors on one thermostat, or a pump and a compressor that cycle together, break that assumption and need both surges added — use a custom-appliance row to carry the second surge.
  • Inverter vs conventional: an inverter generator of the same running watts delivers cleaner power for electronics and runs quieter, but costs more per watt and tops out around 7,000–9,500 W running. Above that, conventional portables and standby units are the options — the watts are the same either way.

Sources & assumptions

  • Method — the Generac portable generator wattage worksheet (2018): total the running watts of everything that runs at the same time, then add the single highest starting-watts requirement — "Total wattage requirements assumes starting one product at a time" — and "Starting watts are typically 2X running watts". The same formula is used by miniwebtool's generator size calculator ((sum of running watts + largest single surge) x (1 + margin)) and moneydeck's generator size calculator ("Required W = sum of running W + max(starting W - running W)"). This tool adds only the EXTRA surge (starting minus running) of the largest motor on top of the running total — the physically exact version of the worksheet method; the worksheet itself adds the full starting figure, which double-counts that motor's running watts and is the more conservative of the two. The page states which convention it uses.
  • Running watts are the Generac wattage worksheet: refrigerator/freezer 700, house lights 600, LED/LCD TV 120, coffee maker 1,200, desktop computer 400, laptop computer 75, microwave 1,500, hair dryer 1,500, toaster 1,200, air compressor 1,000, circular saw 1,400, table saw 1,800, RV air conditioner (15,000 BTU) 1,800, slow cooker 250, blender 1,000. Starting watts (total draw at startup) are the EWEB generator sizing guide + miniwebtool + Generac-dealer consensus: refrigerator/freezer 2,200, chest freezer 1,500, furnace blower (gas/oil, 1/2 HP) 2,350, well pump (1/2 HP) 2,100, sump pump (1/3 HP) 1,300 and (1/2 HP) 2,150, electric water heater 4,500, window AC (10,000-12,000 BTU) 3,600, air compressor (1 HP) 4,500, space heater 1,500. Central AC (3 ton) 3,500 running / 7,000 starting follows Generac's 2x rule and the Generac-dealer chart; the 2-3x spread (7,000-10,500 W) is stated on the page. Circular saw 2,800, table saw 3,600 and RV AC 3,600 starting watts come from Generac's 2x rule. A 1,000 W-output microwave draws about 1,500 W from the wall, so the tool uses 1,500 / 1,500.
  • Window AC note: the 2018 Generac worksheet lists a 12,000 BTU window AC at 3,250 running watts — an old low-efficiency unit. The current consensus across miniwebtool, jamieservices and Homeowner Basics for a modern 10,000-12,000 BTU unit is about 1,200 W running / 3,600 W starting, and the tool uses that figure; the worksheet's 3,250 W figure is flagged here for older units. Check your own nameplate either way.
  • Headroom — 20% is the field default (miniwebtool: "20% (recommended)"; moneydeck; Homeowner Basics: "add about 20%"); the tool offers 0/10/20/25/30% and applies the margin to (running watts + largest extra surge).
  • Altitude derating — 3.5% of rated power lost per 1,000 ft above sea level: Generac support ("Maximum power decreases approximately 3.5% for each 1,000 ft above sea level"), the Honda EB3000c and EU2000i manuals and the Westinghouse iGen1500 manual all give the same figure. (The ranking board's refined spec said 3%/1,000 ft; the manufacturer figure is 3.5% and the tool uses 3.5%.) Temperature derating is about 1% per 10°F above 85°F (Powerhouse PH2200i manual) — stated on the page, not modelled. A generator rated at sea level delivers (1 - 0.035 x ft/1,000) of its rating at altitude, so the required sea-level rating is the peak with headroom divided by that factor.
  • kVA is computed at the conventional 0.8 power factor (kVA = kW / 0.8); amps = watts / volts (120 V and 240 V shown; 240 V is about 230 V outside North America). A portable generator's starting (peak) rating is typically about 25% above its running rating (for example Generac GP3600: 3,600 running / 4,500 starting), so a generator whose running rating covers the recommended watts also covers the peak.
  • Common sizes (running watts) are the Generac / Champion / Honda model lineups: 1,000 / 2,000 / 2,500 / 3,000 / 3,500 / 4,000 / 4,500 / 5,000 / 5,500 / 6,500 / 7,500 / 8,000 / 9,000 / 9,500 / 10,000 / 12,000 / 12,500 / 14,000 / 15,000 / 17,500 / 18,000 / 20,000 / 22,000 / 24,000 / 26,000 (portable to 20,000 W; Generac Guardian standby 10-26 kW above that). Above 26,000 W the tool says so and points at a standby sizing by an electrician.
  • Canonical examples (this tool): defaults (refrigerator 1, furnace blower 1, house lights 1, sea level, 20% margin) — running 2,100 W, largest extra surge 1,550 W (furnace blower), peak 3,650 W, recommended 4,380 W, next size 4,500 W, 5.475 kVA, 36.5 A at 120 V, 18.25 A at 240 V. Essentials (refrigerator 1, furnace blower 1, sump pump 1/2 HP 1, lights 1, TV 1, laptop 1) — running 3,345 W, peak 4,895 W, recommended 5,874 W, next size 6,500 W, 7.3425 kVA. Same essentials at 5,000 ft (1,524 m): derating factor 0.825, recommended 7,120 W, next size 7,500 W. Central AC example (refrigerator 1, central AC 3 ton 1, lights 1, TV 1) — running 4,920 W, peak 8,420 W, recommended 10,104 W, next size 12,000 W, 12.63 kVA.
  • Carbon-monoxide safety: run a generator at least 20 ft from the house with the exhaust pointing away, and keep working CO alarms inside (CDC guidance). Never run a generator indoors or in a garage, and never plug one into a wall outlet (backfeeding) — hardwired loads need a transfer switch or interlock installed by a licensed electrician (NEC Article 702).

Figures checked on 28 November 2026 as part of the site-wide test run (3239 automated checks, all passing). See how we calculate and test.

Safety note

Carbon monoxide kills in minutes and you cannot smell it: never run a generator indoors, in a garage, or on a porch — keep it at least 20 ft from the house with the exhaust pointing away, and keep working CO alarms inside. Never plug a generator into a wall outlet: backfeeding energises the house wiring backwards and can kill a line worker restoring power. Hardwired loads (furnace, well pump, water heater) need a transfer switch or interlock installed by a licensed electrician. Let the engine cool before refuelling, and keep fuel in approved containers away from the generator.
Please note: material estimates are approximate. Always confirm product coverage with the manufacturer and buy a little extra for cuts, waste and future repairs.

What this calculator doesn't do

  • This tool gives a planning estimate, not an electrical load calculation. A licensed electrician sizes a real standby installation and the transfer switch from a load calculation (NEC Article 220 / Article 702), and the final generator choice must match the nameplate watts of your own appliances — published wattage tables are typical figures, and your models can draw 5–15% more. If the number this tool gives is close to a size boundary, buy the larger size or get a load review before you spend.
  • Only ONE motor surge is added — the largest. That is the Generac worksheet method and the field standard: motors start one at a time, so the worst real instant is everything running plus the single biggest motor starting. If two big motors share one thermostat or timer and genuinely start together (two central AC units on one call, a well pump and a sump pump on the same float switch), add the second surge yourself or use the custom-appliance rows to carry it.
  • Starting watts are the least certain number in generator sizing. The same 3-ton central air conditioner is listed at 7,000 starting watts by the Generac 2x rule and at 10,500 by sources using 3x — the difference is the compressor, its age and whether it has a soft-start kit. The tool uses the 2x figure and flags the spread; if your compressor's nameplate locked-rotor amps (LRA) say otherwise, trust the nameplate: starting watts = LRA x volts.
  • Altitude derating uses the manufacturer figure of 3.5% per 1,000 ft above sea level (Generac, Honda, Westinghouse manuals). It assumes a naturally aspirated engine with the right high-altitude jetting or EFI. Without the jet kit, the loss at altitude is worse; with a turbocharged diesel standby unit it is smaller. The tool also ignores temperature derating (about 1% per 10°F above 85°F) — on a hot day at altitude, both apply.
  • The recommended size is a RUNNING-watts rating. A generator also has a starting (peak) rating, typically about 25% above its running rating, and the tool's recommendation is set so that rating covers the peak too — but always check both numbers on the spec sheet before buying: a model whose running watts match but whose starting watts fall short will trip or stall when the biggest motor kicks in.
  • kVA is computed at the conventional 0.8 power factor (kVA = kW / 0.8). Some inverter generators and most standby units are rated at 1.0 power factor for resistive loads, in which case kVA equals kW. The watts figure is the one to size by; kVA is shown because standby generators are often sold by kVA.
  • Fuel type, runtime and fuel consumption are not part of this tool. A 5,000 W portable on gasoline, propane and natural gas does not deliver the same watts on each fuel (propane and natural gas typically derate 10–20% below gasoline), and runtime depends on the tank and the load. Size by watts here, then check the fuel and runtime figures on the model you buy.
  • This tool does not size the transfer switch, the inlet, the cord or the panel. A portable generator powering hardwired loads (furnace, well pump, water heater) needs a transfer switch or interlock installed by a licensed electrician — never plug a generator into a wall outlet. Backfeeding kills line workers and is illegal in most places.

Generator Size Calculator — frequently asked questions

How many watts of generator do I need?

For the essentials — one refrigerator, one furnace blower, one 1/2 HP sump pump, the house lights, a TV and a laptop — 5,874 W recommended, so a 6,500 W generator (7.34 kVA). That is 3,345 W running plus the furnace blower's 1,550 W starting surge, with 20% headroom. A smaller list (refrigerator, furnace blower and lights only) needs 4,380 W recommended — a 4,500 W generator. Add central air conditioning and the answer jumps to 10,104 W recommended, a 12,000 W generator. Enter your own appliances and altitude in the tool for your number.

What size generator do I need?

Most homes need a 5,000–7,500 W portable generator for the essentials (refrigerator, furnace blower, sump or well pump, lights and electronics). Add a window air conditioner and you are usually at 7,500 W; add central air conditioning, an electric water heater or electric heat and you are usually at 10,000–12,000 W or a standby generator. The exact size depends on your load list — add the running watts, add the single largest starting surge, add 20% headroom, and round up to the next common size.

How many watts does a refrigerator need to start?

About 700 W running and 2,200 W starting (Generac worksheet and EWEB sizing guide) — the extra surge is 1,500 W for a fraction of a second as the compressor spins up. A modern ENERGY STAR refrigerator can run much lower, 150–400 W, so check the nameplate: watts = volts x amps. A chest freezer is smaller, about 500 W running and 1,500 W starting.

How many watts does a 3-ton central air conditioner need?

About 3,500 W running and 7,000 W starting by the Generac 2x rule — but central AC starting watts vary by unit, from 2x to 3x running (7,000–10,500 W for a 3-ton), so check the compressor nameplate locked-rotor amps (LRA): starting watts = LRA x volts. A soft-start kit can cut the surge roughly in half. With a 3-ton unit in the load list, most homes need a 12,000 W portable or a standby generator.

How does altitude affect generator size?

A generator loses about 3.5% of its rated power per 1,000 ft above sea level (Generac, Honda and Westinghouse manuals). At 5,000 ft it delivers 82.5% of its label rating, so a 5,000 W generator is really a 4,125 W machine up there — and the same essentials that need a 6,500 W generator at sea level need a 7,500 W one at 5,000 ft. Enter your altitude in the tool; it divides the requirement by the derating factor. Without the high-altitude jet kit the loss is worse, and a hot day costs about another 1% per 10°F above 85°F.

How many kVA is a 5,000 watt generator?

6.25 kVA at the conventional 0.8 power factor (kVA = kW / 0.8). A 6,500 W generator is 8.13 kVA, a 7,500 W generator is 9.38 kVA, and a 10,000 W generator is 12.5 kVA. Standby generators are often sold by kVA, so the tool shows both — but size by watts, since watts are what your appliances draw. Some inverter generators are rated at 1.0 power factor, in which case kVA equals kW.

How many amps does a 5,000 watt generator produce?

41.7 A at 120 V and 20.8 A at 240 V (amps = watts / volts). A 6,500 W generator gives 54.2 A at 120 V and 27.1 A at 240 V. Outside North America the mains voltage is about 230 V, so a 5,000 W generator gives about 21.7 A at 230 V — close to the 240 V figure the tool shows. Check the generator's outlet ratings too: a 30 A outlet cannot deliver 40 A no matter what the generator is rated for.

What size generator do I need at 1,500 metres altitude?

About one size larger than at sea level. 1,500 m is about 4,921 ft, so the derating is about 17% (power factor 0.83). The essentials list (refrigerator, furnace blower, sump pump, lights, TV, laptop) needs 5,874 W at sea level and about 7,080 W at 1,500 m — a 7,500 W generator instead of a 6,500 W one. Enter metres directly in the altitude field; the tool converts to feet and applies the 3.5%-per-1,000-ft derating.

How do I convert generator watts to kVA?

Divide the watts by 1,000 to get kilowatts, then divide by 0.8 (the conventional power factor for generators): kVA = kW / 0.8. So 5,000 W = 5 kW = 6.25 kVA, and 7,500 W = 7.5 kW = 9.38 kVA. To go the other way, kW = kVA x 0.8. The tool shows kVA next to the recommended watts so you can compare a standby generator sold in kVA with a portable sold in watts.

Can a generator run a well pump and a refrigerator at the same time?

Yes, if it is sized for both — and the well pump is usually the harder load. A 1/2 HP well pump runs at 1,000 W and starts at 2,100 W; with a refrigerator (700 W running, 2,200 W starting), lights and a furnace blower, the running total is about 3,100 W and the peak about 4,650 W, so a 5,500 W generator covers it with 20% headroom. The catch is the start: stagger them — let the pump finish starting before the refrigerator compressor kicks in — and never assume a 1 HP well pump (about 2,000 W running, 4,000 W starting) fits the same size. Enter it as a custom appliance if yours is 1 HP.

Next step

Take the recommended size and kVA to the store and check them against the RUNNING watts on the generator's spec sheet — not the big peak number on the box. Then check the nameplate watts of your own biggest appliances (the furnace blower and any air conditioner first) and get a transfer-switch quote from a licensed electrician before the next outage. For the heating load behind a winter outage, run the BTU calculator on the rooms the generator must heat.

Save this estimate: use the Copy link button in the results box above to share these exact inputs, or Print results for a paper copy to take to the store.