Heat Pump Size Calculator — What Size Heat Pump Do I Need? Tons, BTU & kW

A heat pump is two machines in one box: an air conditioner in summer and a heater in winter — and the two jobs rarely need the same size. In a mild climate the cooling load sets the size; in a cold one the heating load can be nearly three times the cooling load, and a unit sized on cooling alone leaves the house cold in January. This heat pump size calculator works out both loads separately, from your floor area and your IECC climate zone, with the insulation, ceiling height, windows, sun and occupants that move the answer — then sizes the unit in tons from the cooling load (1 ton = 12,000 BTU/h), gives you the heat-to-cool ratio with a green/amber/red verdict, and checks the heating output you need at your winter design temperature against what a cold-climate model and a standard model actually deliver there. For the cooling load on its own, use the BTU calculator; for what the heat will cost to run, the heating cost calculator and the electricity cost calculator; for the radiators on a low-temperature system, the radiator size calculator; for cutting the load itself, the insulation calculator; for backup power on the coldest nights, the generator size calculator; and for the wood that heats the house when the power is out, the firewood calculator.

Quick answer: A 2,000 sq ft home in climate zone 4 with average insulation and 8 ft ceilings needs 40,000 BTU/h of cooling (11.7 kW) and 56,000 BTU/h of heating (16.4 kW) — a 3.5-ton heat pump. The heat-to-cool ratio is 1.40, so check the cold-weather capacity: a cold-climate 3.5-ton delivers about 37,400 BTU/h at the 14°F design temperature (67% of the heating load), and the balance point is about 29°F — plan on 10 kW of backup strip heat, or step up to 4 tons. Enter your home below for your exact loads.
Heated floor area of the whole home — all floors together. A 2,000 sq ft house is the worked example below; a 1,500 sq ft one is a row in the size table.
Your IECC climate zone sets both factors: cooling falls as you go north, heating rises steeply. Pick the nearest city if you do not know your zone number.
Poor insulation adds 20% to both loads; good insulation takes 15% off. The multiplier is this page’s labelled planning factor — a blower-door test gives the real figure.
Average ceiling height. Above 8 ft the loads scale by height ÷ 8 — a 10 ft ceiling adds 25%. At 8 ft or below there is no adjustment.
Glass loses heat in winter and gains it in summer, so windows move both loads the same way. Count the glass, not the window frames.
Sun moves the cooling load only — it does not change the heating load. A house shaded by trees or a north-facing slope takes the shaded figure.
People in the home. Each person above 2 adds 600 BTU/h to the cooling load (body heat); the heating load is unchanged — people warm a house, they do not cool it.
A ducted system has one outdoor unit and ducts; a mini-split has one outdoor unit and a head in each room. Mini-split mode adds the head sizes to the result.
How many indoor heads the mini-split has. Only used in mini-split mode — the cooling load is divided by the heads and each head is rounded up to the next standard size (6,000–36,000 BTU/h).
What covers the coldest hours if the heat pump falls short. Strips are sized in kW below; a dual-fuel furnace takes over below the balance point instead.

Planning this project? Save to Pinterest to find this calculator again later.

How to use the Heat Pump Size Calculator — What Size Heat Pump Do I Need? Tons, BTU & kW

  1. Enter the heated floor area. All floors together, in square feet or square metres — the area the heat pump actually heats and cools, not the footprint. A two-storey 1,000 sq ft footprint is 2,000 sq ft of floor area. Garages and unheated basements do not count.
  2. Pick your climate zone. Zones 1–2 are hot (Miami, Houston, Phoenix), zone 3 is warm (Atlanta, Dallas), zone 4 is mixed (Washington DC, St. Louis, Seattle), zone 5 is cold (Chicago, Denver, Boston, Columbus) and zones 6–7 are very cold (Minneapolis, Duluth). The zone sets both factors: cooling falls as you go north, heating rises steeply — from 15 BTU/h per sq ft in zones 1–2 to 45 in zones 6–7.
  3. Set the insulation. Poor (old or uninsulated) adds 20% to both loads; good (well insulated, new build) takes 15% off; average is the middle. If you have had a blower-door test, use the result to pick — air leakage is the load the insulation selector cannot see.
  4. Enter the ceiling height and the glass. Above 8 ft the loads scale by height ÷ 8. Windows move both loads (glass loses heat in winter and gains it in summer); sun moves the cooling load only. A shaded house with few windows can be a quarter smaller than the same house sunny with glass everywhere.
  5. Count the occupants. Each person above two adds 600 BTU/h to the cooling load. It is a small number on a whole house — 1,200 BTU/h for a family of four — but it is the difference between a 3-ton and a 3.5-ton unit on a small home.
  6. Read the two loads separately. The result shows the cooling load and the heating load in BTU/h and in kW, side by side. They are different numbers for a reason: the cooling load sizes the unit, the heating load decides whether that unit can heat the house — and in zones 4 and above, the heating load is the bigger number.
  7. Read the tons. Nominal tons come from the cooling load divided by 12,000 BTU/h, rounded up to the next half ton — 40,000 BTU/h is 3.5 tons. Tons are a cooling rating: a 3.5-ton unit is rated 42,000 BTU/h of cooling at 47°F, and its heating output at 5°F is a different, smaller number.
  8. Read the heat-to-cool ratio. Heating divided by cooling: 1.40 on the worked example. At 1.25 or below the ratio is green — cooling sets the size and a standard model covers the heat. From 1.25 to 2.0 it is amber — check the cold-weather capacity. Above 2.0 it is red — heating dominates, and the page says so plainly: cold-climate model plus backup, and a Manual J before you buy.
  9. Read the output you need at your design temperature. The result gives two bands from NEEP: 100–115% of the heating load with no backup heat, 75–85% with backup covering the rest. Those are the outputs the heat pump must deliver at the design temperature — not at 47°F, where every unit looks strong.
  10. Compare cold-climate with standard. The result shows what each type delivers at 47°F, 17°F and 5°F, and at your design temperature. A cold-climate 3.5-ton gives about 37,400 BTU/h at a 14°F design temperature; a standard one gives about 24,400. In zones 1–3 the standard model is usually fine; in zones 4 and above the cold-climate model is the one that keeps the house warm.
  11. Read the balance point and the backup. The balance point is the outdoor temperature where the heat pump’s falling capacity meets the house’s rising heat loss — about 29°F for the cold-climate model on the worked example, 33°F for the standard one. Below it, backup heat fills the gap: the result sizes it in kW and rounds up to the next standard strip kit (5, 10, 15 or 20 kW). With a dual-fuel system the furnace takes over at the balance point instead.
  12. If it is a mini-split, read the head sizes. Switch the system type to mini-split and enter the number of heads: the cooling load is divided by the heads and each head is rounded up to the next standard size — 6,000, 9,000, 12,000, 15,000, 18,000, 24,000 or 36,000 BTU/h. The outdoor unit stays the tonnage above; the heads are a shortlist, not a per-room design.

Heat Pump Size Calculator — What Size Heat Pump Do I Need? Tons, BTU & kW formula

Cooling load (BTU/h) = floor area (sq ft) × zone cooling factor × insulation × ceiling factor × windows factor × sun factor + 600 × (occupants − 2) — the 600 BTU/h per extra person is the cooling load of body heat; the heating load has no occupant term

Heating load (BTU/h) = floor area (sq ft) × zone heating factor × insulation × ceiling factor × windows factor

Zone factors (BTU/h per sq ft) — cooling / heating: zones 1–2: 24 / 15 · zone 3: 22 / 22 · zone 4: 20 / 28 · zone 5: 18 / 35 · zones 6–7: 16 / 45

Insulation: poor × 1.20 · average × 1.00 · good × 0.85 — ceiling factor: height ÷ 8 above 8 ft, 1.00 at 8 ft or below — windows: few × 0.95 · average × 1.00 · many × 1.10 — sun (cooling only): shaded × 0.95 · average × 1.00 · sunny × 1.10

Nominal tons = cooling load ÷ 12,000, rounded UP to the next half ton (minimum 1.5 tons; above 6 tons the house needs two systems or a zoned design) — 1 ton = 12,000 BTU/h = 3.517 kW · kW = BTU/h × 0.000293071

Heat-to-cool ratio = heating load ÷ cooling load — ≤ 1.25 green (cooling sets the size) · 1.25–2.0 amber (check cold-weather capacity) · > 2.0 red (heating dominates — cold-climate model plus backup, Manual J required)

Heating output needed at the design temperature (NEEP): no backup heat 100–115% of the heating load · with backup heat 75–85% of the heating load

Capacity at temperature T (this page’s labelled linear model): rated capacity at 47°F minus the fall to the 5°F median, spread evenly — capacity(T) = tons × 12,000 − (tons × 12,000 − median 5°F capacity) × (47 − T) ÷ 42 · median 5°F capacity per ton: cold-climate 10,333 BTU/h (31,000 for a 3-ton) · standard 5,600 BTU/h (16,800 for a 3-ton) · below 5°F the same line is extrapolated, and the page says so

Balance point: the outdoor temperature where heat-pump capacity equals house heat loss — heat loss(T) = heating load × (65 − T) ÷ (65 − design temp) · capacity(T) from the line above · solved for T; below the design temperature the heat pump alone covers the design load

Backup heat (kW) = (heating load − cold-climate capacity at the design temperature) × 0.000293071, rounded up to the next 5 kW strip kit (5 / 10 / 15 / 20 kW) — 0 kW if the model covers the load

Mini-split head = cooling load ÷ heads, rounded up to the next standard size (6,000 / 9,000 / 12,000 / 15,000 / 18,000 / 24,000 / 36,000 BTU/h) · airflow = 400–500 CFM per ton for a ducted system

1 sq ft = 0.092903 m² · 1 m² = 10.7639 sq ft · 1 BTU/h = 0.293071 W · design temperatures (representative 99% values): zones 1–2 32°F · zone 3 22°F · zone 4 14°F · zone 5 3°F · zones 6–7 −10°F — your county’s figure governs.

Worked example

Worked example — 2,000 sq ft, climate zone 4, average insulation, 8 ft ceilings, average windows and sun, 2 occupants, ducted, no backup. This is the tool’s default, worked by hand so you can check it. It reproduces the field benchmark’s canonical example exactly.

  1. Cooling load: 2,000 × 20 (zone 4) × 1.00 × 1.00 × 1.00 × 1.00 = 40,000 BTU/h (11.7 kW). The three 1.00s are average insulation, an 8 ft ceiling and average windows; with few windows it would be 40,000 × 0.95 = 38,000 BTU/h.
  2. Heating load: 2,000 × 28 (zone 4) × 1.00 × 1.00 × 1.00 = 56,000 BTU/h (16.4 kW). Sun and occupants do not touch the heating load.
  3. Nominal tons: 40,000 ÷ 12,000 = 3.33 → rounded up to the next half ton = 3.5 tons (42,000 BTU/h rated at 47°F).
  4. Heat-to-cool ratio: 56,000 ÷ 40,000 = 1.40 — amber. Cooling sets the size, but heating needs more than cooling, so the cold-weather capacity decides the model.
  5. Output needed at the 14°F design temperature (NEEP): no backup 56,000–64,400 BTU/h (100–115% of 56,000); with backup 42,000–47,600 BTU/h (75–85%).
  6. What the models deliver at 14°F: the cold-climate 3.5-ton gives about 37,400 BTU/h (67% of the heating load); the standard 3.5-ton gives about 24,400 BTU/h (44%). Neither covers the 56,000 BTU/h load alone — the cold-climate one is closer, and it is the one to buy in zone 4.
  7. At 5°F: cold-climate 36,167 BTU/h vs standard 19,600 BTU/h — the medians of the ENERGY STAR certified-models list. At 17°F: cold-climate 37,833 vs standard 26,000.
  8. Balance point: about 29°F for the cold-climate model and 33°F for the standard one — below 29°F the cold-climate unit needs help, below 33°F the standard one does.
  9. Backup heat: the gap at the design temperature is 56,000 − 37,417 = 18,583 BTU/h = 5.4 kW → the next standard strip kit is 10 kW. Or step up to a 4-ton cold-climate model and re-check.
  10. Airflow: 3.5 tons × 400–500 CFM/ton = 1,400–1,750 CFM for the ducted system. Mini-split: 40,000 ÷ 4 heads = 10,000 BTU/h each → the next standard size is 12,000 BTU/h heads.

Same house, mild climate — 2,000 sq ft, zones 1–2. Cooling 2,000 × 24 = 48,000 BTU/h (14.1 kW); heating 2,000 × 15 = 30,000 BTU/h (8.8 kW); 4 tons; ratio 0.63 — green. A standard 4-ton delivers about 38,857 BTU/h at the 32°F design temperature — 130% of the heating load — so no backup heat is needed, and the balance point (~26°F) sits below the design temperature: the heat pump alone covers the design load.

Same house, very cold climate — 2,000 sq ft, zones 6–7 (Minneapolis). Cooling 2,000 × 16 = 32,000 BTU/h (9.4 kW); heating 2,000 × 45 = 90,000 BTU/h (26.4 kW); 3 tons by cooling; ratio 2.81 — red. The cold-climate 3-ton delivers about 29,214 BTU/h at the −10°F design temperature — 32% of the heating load — and the balance point is about 36°F. This is a heating job, not a cooling job: the page’s verdict is a cold-climate model plus backup heat and a Manual J before you buy. Note the city table below sizes the same Minneapolis house at 4 tons — the design-temperature capacity method, not the zone-factor method — and the difference is the 2–5 ton spread the page names, not a mistake.

Metric twin — 186 m², zone 4, average insulation, 2.4 m ceilings. 186 m² is 2,002 sq ft, so the loads are the same house in metric: cooling 11.7 kW, heating 16.4 kW, 3.5 tons, ratio 1.40. A 150 m² modern, well-insulated house needs about 4.5–7.5 kW of heating (30–50 W/m²); the same floor unrenovated needs 12–18 kW (80–120 W/m²) — the EN 12831 bands in the table below.

High ceilings — the same 2,000 sq ft zone 4 house with 10 ft ceilings. The ceiling factor is 10 ÷ 8 = 1.25, so cooling is 40,000 × 1.25 = 50,000 BTU/h and heating is 56,000 × 1.25 = 70,000 BTU/h — 4.5 tons instead of 3.5. Two extra feet of ceiling is a full half ton.

Heat pump size tables: factors by zone, size by area, capacity at design temperature, and SEER2 / HSPF2

Why the same house sizes 2 to 5 tons. The field’s calculator pages agree on the arithmetic — 1 ton is 12,000 BTU/h, tons come from the cooling load rounded up to the next half ton — and still disagree on the answer by a factor of two and a half, because they answer three different questions. A cooling-driven page sizes the same 2,000 sq ft average home at 3.5 tons in zone 4. A heating-driven page sizes it at 5 tons. A design-temperature page sizes it by what a real model delivers at the county’s design temperature — 2 tons in Seattle, 4 tons in Minneapolis. This page shows all three numbers separately — the cooling tons, the heating load, and the capacity at the design temperature — so you can see which question each number answers instead of picking one silently.

The heating-factor disagreement, named. The zone-4 heating factor is the one number the field cannot agree on: localfixerpro uses 28 BTU/h per sq ft, everydaytools uses about 19.25, and greencalcs folds heating into a single 20 BTU/h rate for both loads. On a 2,000 sq ft house that is 56,000 vs 38,500 vs 40,000 BTU/h — a 45% spread before any other factor is applied. This page uses localfixerpro’s fully open split-factor table as its labelled planning basis, because it is the only one that publishes separate cooling and heating factors per zone — and it names the disagreement here so you know the heating load is the soft number and the cooling load is the firm one. The cooling factors are tighter: 20 BTU/h per sq ft in zone 4 on localfixerpro, greencalcs and everydaytools alike, against thebuildingcode’s wider 12–25 range.

Tons are a cooling rating. A “3-ton” heat pump is rated 36,000 BTU/h of cooling at 47°F. Its heating output at 5°F is a different number — about 31,000 BTU/h for a median cold-climate model and about 16,800 for a median standard one — and the rating on the box does not tell you either figure. Sizing by tons alone is sizing by the summer number; in zones 4 and above, the winter number is the one that decides whether the house stays warm. Check the model’s capacity at your design temperature, not its tonnage.

Do not size to the old furnace. The furnace or boiler being replaced was almost certainly oversized — old boilers are routinely oversized by 50–100% — and copying its rating onto a heat pump buys a unit that short-cycles in summer, costs more than it should, and still leaves the house cold on the design day, because a heat pump’s capacity falls as it gets colder while a furnace’s does not. Size from the loads on this page, then confirm with a Manual J.

NEEP’s no-padding rule, and the variable-speed nuance. NEEP’s cold-climate sizing guide warns against padding the loads — load calculations already carry safety factors, and grossly oversized equipment cycles too often, dehumidifies poorly and costs more to run. That is why the heating targets are 100–115% with no backup and 75–85% with backup, not 120% or 130%. A variable-speed (inverter) unit softens the rule: it can slow down in mild weather, so a little oversizing on the heating side costs less comfort than it would on a single-stage unit — but it does not make a 5-ton unit right for a 3-ton house.

The federal credit is gone — check the state and utility rebates instead. The 25C Energy Efficient Home Improvement Credit (30%, up to $2,000 a year for a heat pump) and the 25D Residential Clean Energy Credit were terminated by the One Big Beautiful Bill Act (P.L. 119-21, signed 4 July 2025) for property placed in service after 31 December 2025 — per IRS Fact Sheet FS-2025-05. A heat pump installed in 2026 gets no federal tax credit. Systems placed in service on or before 31 December 2025 are still claimed on IRS Form 5695 with the 2025 return. What replaces the credit is state and utility rebates — check the DSIRE database for your state before you sign a quote, and do not let a contractor price a credit that no longer exists into the job.

Factors by climate zone (the planning basis of this page). Cooling and heating factors are BTU/h per sq ft of floor area, from localfixerpro’s published table; design temperatures are representative 99% values — your county’s figure governs.

IECC zoneCooling factorHeating factorDesign tempExample cities
Zones 1–2 — hot241532°FMiami, Houston, Phoenix
Zone 3 — warm222222°FAtlanta, Dallas, Los Angeles
Zone 4 — mixed202814°FWashington DC, St. Louis, Seattle
Zone 5 — cold18353°FChicago, Denver, Boston, Columbus
Zones 6–7 — very cold1645−10°FMinneapolis, Duluth, Fairbanks

Size by floor area and zone (nominal tons, cooling-driven). Tons = area × cooling factor ÷ 12,000, rounded up to the next half ton. The heating load for the same house is in the worked example and the factors table — in zones 5–7 it, not the tons, is the number that matters.

Floor areaZones 1–2Zone 3Zone 4Zone 5Zones 6–7
1,000 sq ft2 t2 t2 t1.5 t1.5 t
1,500 sq ft3 t3 t2.5 t2.5 t2 t
2,000 sq ft4 t4 t3.5 t3 t3 t
2,500 sq ft5 t5 t4.5 t4 t3.5 t
3,000 sq ft6 t5.5 t5 t4.5 t4 t

Size by city (design-temperature method, greencalculus). A 2,000 sq ft two-storey house with average insulation, sized by the smallest ENERGY STAR cold-climate model that reaches 100% of the heat loss at the county’s design temperature. Compare with the zone-factor table above — Seattle sizes 2 tons here and 3.5 tons there, because the factor table assumes the cold end of zone 4 and Seattle’s design temperature is mild.

CitySizeWhy
Seattle2 tMild design temperature — heating load is small
Dallas2 tWarm zone 3 — cooling sets the size
Columbus3 tZone 5 — heating starts to matter
Boston3 tZone 5 — same as Columbus
Chicago3.5 tZone 5 — cold design temperature
Denver3.5 tZone 5 — high altitude, cold nights
Minneapolis4 tZone 6 — heating dominates

Nominal sizes. 1 ton = 12,000 BTU/h = 3.517 kW. Units are sold in half-ton steps from 1.5 to 6 tons; above 6 tons the house needs two systems or a zoned design.

Nominal sizeCooling capacitykW
1.5 t18,000 BTU/h5.3 kW
2 t24,000 BTU/h7.0 kW
2.5 t30,000 BTU/h8.8 kW
3 t36,000 BTU/h10.6 kW
3.5 t42,000 BTU/h12.3 kW
4 t48,000 BTU/h14.1 kW
4.5 t54,000 BTU/h15.8 kW
5 t60,000 BTU/h17.6 kW
5.5 t66,000 BTU/h19.3 kW
6 t72,000 BTU/h21.1 kW

Heating capacity at the rating temperatures (BTU/h). The 47°F figure is the nominal rating; the 5°F figures are the medians of the ENERGY STAR certified-models list (29 October 2026); the 17°F figures are this page’s linear model between the two, and the standard 3-ton’s 22,300 BTU/h at 17°F sits inside tradecalc’s published 22,000–28,000 band. Check the exact model’s extended-performance table — these are medians, not datasheets.

SizeAt 47°F (both)At 17°F — cold-climateAt 17°F — standardAt 5°F — cold-climateAt 5°F — standard
2 t24,00021,60014,90020,70011,200
3 t36,00032,40022,30031,00016,800
4 t48,00043,20029,70041,30022,400
5 t60,00054,00037,10051,70028,000

Metric — heating load per square metre (EN 12831). Specific heat load for a fast first estimate before the formal room-by-room calculation. The middle band is this page’s interpolation between the two published bands.

BuildingW/m²150 m² house
Well-insulated, modern30–504.5–7.5 kW
Average insulation50–807.5–12 kW
Unrenovated, pre-198080–12012–18 kW

SEER2 / HSPF2 — what to buy. SEER2 is seasonal cooling efficiency, HSPF2 is seasonal heating efficiency, both under the DOE test procedure in force since 1 January 2023. A higher number is a more efficient unit, not a bigger one.

LevelSEER2HSPF2Note
Federal minimum — split system14.37.5Nationwide, since 1 Jan 2023 (10 CFR 430.32)
Federal minimum — single-package13.46.7Everything in one outdoor cabinet
ENERGY STAR — split system (v6.2)15.27.8Plus 11.0 EER2
ENERGY STAR — cold-climate—≥ 8.1Plus COP ≥ 1.75 at 5°F and ≥ 70% of rated capacity at 5°F

Airflow and backup kits. A ducted system needs 400–500 CFM per ton of airflow — 1,400–1,750 CFM for a 3.5-ton unit — and undersized ducts are the commonest reason a right-sized heat pump underperforms. Electric strip backup comes in 5, 10, 15 and 20 kW kits; the result rounds the gap up to the next kit. The balance point for a standard system in a zone-5 home sits in the high 20s °F, and a cold-climate model drops it into the low teens — cutting backup runtime by 60–80% across the heating season.

Measurement tips

  • Size from the loads, not from the old equipment. The furnace or boiler being replaced was almost certainly oversized by 50–100%, and a heat pump sized to its rating short-cycles in summer and still falls short on the design day. The loads on this page — area times the zone factors, corrected for insulation and ceiling — are the starting point; a Manual J is the confirmation.
  • Check the capacity at your design temperature, not at 47°F. Every heat pump looks strong at 47°F, where the rating is taken. The number that matters is the capacity at your winter design temperature — 14°F in zone 4, 3°F in zone 5 — and the gap between a cold-climate model and a standard one there is the difference between a warm house and a cold one.
  • Use the ratio before the tons. A heat-to-cool ratio under 1.25 means cooling sets the size and the choice is easy. From 1.25 to 2.0 the model choice matters — buy the cold-climate unit. Above 2.0 the house is a heating job wearing a cooling size, and the honest answer is a cold-climate model, backup heat, and a Manual J before any money moves.
  • Buy the cold-climate model in zones 4 and above. The price gap is real — typically $2,000–$5,000 more than a standard unit at the same tonnage — but a standard 3.5-ton delivers about 24,400 BTU/h at a 14°F design temperature against a cold-climate model’s 37,400. The cheaper unit is the one that needs 10 kW of strip heat all winter.
  • Count the windows before you argue about the tons. Glass moves both loads, and a house with a wall of south-facing glass can be a full half ton bigger than the same floor plan with small windows. If two quotes disagree by a ton, the difference is usually the glass, the ceiling height, or the insulation assumption — ask which one each quote used.
  • Check the ducts before you blame the unit. A ducted heat pump needs 400–500 CFM per ton, and undersized or leaky ducts are the commonest reason a right-sized unit underperforms — the house stays cold, the strips run, and the bill blames the heat pump. A duct check costs less than a ton of capacity.
  • For a mini-split, size the heads room by room. The head figures on this page divide the whole-house load by the number of heads, which is a shortlist, not a design. A sunny south room takes a bigger head than a shaded north room of the same size, and the sum of the heads can exceed the outdoor unit — the outdoor unit is sized to the whole house, the heads to the rooms.
  • Ask for the extended-performance table. The tonnage on the box is a cooling rating at 47°F. The table that matters is the manufacturer’s extended-performance data: capacity and COP at 17°F and at 5°F for the exact model. If the installer cannot produce it, the quote is a guess, not a size.
  • Check rebates before you sign — the federal credit is gone. The 25C credit ended on 31 December 2025, so no 2026 install gets a federal tax credit. State and utility rebates still exist and can be worth thousands — check the DSIRE database for your state, and get the rebate in writing before the install, not after.
  • Keep the balance point in mind when you pick the backup. Below the balance point the backup does the heating: with electric strips that heat costs two to three times what heat-pump heat costs, so a lower balance point (cold-climate model) is worth real money every winter. With a dual-fuel system the furnace takes over instead — cheaper per BTU than strips, but it needs a gas line and a furnace to maintain.

Common mistakes

  • Sizing to the old furnace. The classic mistake: the old furnace was 100,000 BTU/h, so the heat pump must be 100,000 BTU/h. Old boilers are routinely oversized by 50–100%, and a heat pump does not hold its rating as it gets colder — a furnace does. Size from the loads, not from the label on the dead equipment.
  • Sizing on cooling alone in a cold climate. A 3.5-ton unit cools the zone-4 worked example perfectly and heats only two-thirds of it at the design temperature. In zones 4 and above, a cooling-only size is a January complaint — the heating load and the capacity at the design temperature are the numbers that decide the model.
  • Reading tons as heating capacity. A 3-ton heat pump is 36,000 BTU/h of cooling at 47°F — and about 16,800 BTU/h of heating at 5°F if it is a standard model. The tonnage says nothing about the winter output. Two 3-ton units can differ by nearly two to one at 5°F.
  • Padding the loads “to be safe”. NEEP warns against it explicitly: load calculations already carry safety factors, and a padded size cycles too often, dehumidifies poorly in summer, and costs more to buy and to run. The NEEP bands are 100–115% with no backup and 75–85% with backup — not 120% or 130%.
  • Using one BTU-per-square-foot rule for both loads. The single-rate pages fold heating into the cooling rate (20 BTU/h per sq ft for everything), which undersizes the heating side by 40% in zone 4 — 40,000 BTU/h of “heating” where the split-factor method gives 56,000. Cooling and heating need separate factors; that is the whole point of this page.
  • Trusting a phone or web estimate as a design. A rule-of-thumb calculator — including this one — is a planning estimate. The final size comes from a Manual J load calculation, room by room, with your actual walls, windows and air leakage. Skipping it to save a few hundred dollars is how a $15,000 system ends up a ton wrong.
  • Forgetting the ceiling. Two extra feet of ceiling is 25% more load — the zone-4 worked example goes from 3.5 tons to 4.5 tons at 10 ft ceilings. A vaulted great room sized as an 8 ft room is the commonest reason a new system cannot hold temperature on the coldest day.
  • Buying the standard model for a cold climate to save money. The standard unit is cheaper at the counter and more expensive every winter after: at a 14°F design temperature it delivers about a third less heat than the cold-climate model at the same tonnage, and the strips make up the difference at two to three times the cost per BTU.
  • Counting on a federal tax credit that ended. The 25C credit — 30%, up to $2,000 a year — ended for property placed in service after 31 December 2025. A quote that still prices it in is either stale or wrong; check the DSIRE database for the state and utility rebates that actually exist in 2026.
  • Ignoring the ducts on a ducted install. A heat pump moves 400–500 CFM per ton, and ducts sized for a furnace — or installed for a smaller system — choke it. The unit is blamed for a duct problem, the strips run all winter, and the fix (bigger ducts, sealed joints) costs more after the install than before it.

Factors that affect accuracy

  • Climate zone — the biggest factor. The heating factor triples from zones 1–2 (15 BTU/h per sq ft) to zones 6–7 (45), while the cooling factor falls from 24 to 16. The same 2,000 sq ft house is 4 tons in Miami and 3 tons in Minneapolis by cooling — and 30,000 vs 90,000 BTU/h of heating. The zone is the first input because it moves the answer most.
  • Floor area — the load scales with it. Every factor is per square foot, so the loads are linear in area: double the house, double the load. Measure the heated area — all floors, no garage, no unheated basement — because a 200 sq ft error is a 4,000 BTU/h error in zone 4, and a half ton on a small house.
  • Insulation — ±20% either way. Poor insulation multiplies both loads by 1.20; good insulation by 0.85. On the worked example that is the difference between 47,600 and 67,200 BTU/h of heating — a full ton and a half. Insulation is the cheapest tonnage on this page: the insulation calculator shows what a top-up saves.
  • Ceiling height — volume, not area. Above 8 ft the loads scale by height ÷ 8: a 10 ft ceiling adds 25%, a 12 ft ceiling adds 50%. Below 8 ft there is no reduction — the design load is set by heat loss through the envelope, not by the volume alone, and a low ceiling does not make the walls leak less.
  • Windows — glass loses and gains. Windows move both loads: average glass is the baseline, a glass-heavy house adds 10%, and few windows take 5% off. A single large south-facing window can add more cooling load than a whole small room, and the same window is a heat loss at night in January. Count the glass area, not the window count.
  • Sun exposure — cooling only. A sunny house takes 10% more cooling than the same house shaded; a shaded house takes 5% less. Sun does not change the heating load — the January sun is weak and the design temperature is set for the coldest hours, which are dark. Do not let a summer factor size a winter decision.
  • Occupants — small but real. Each person above two adds 600 BTU/h of cooling. On a 2,000 sq ft house that is 3% of the cooling load; on a 900 sq ft flat with four people it is 7% — enough to tip the rounding from 2 tons to 2.5. People warm a house, so the heating load is untouched.
  • System type — ducts vs heads. A ducted system loses capacity to the ducts (and needs 400–500 CFM per ton of airflow); a mini-split puts the head in the room and loses nothing to ducts, but its heads are sized room by room and the outdoor unit is sized to the whole house. The loads are the same either way — the delivery is not.
  • Backup heat — what the coldest hours cost. With no backup the heat pump must deliver 100–115% of the heating load at the design temperature; with backup it needs only 75–85%, and the strips or the furnace cover the rest. The backup choice changes the size of the unit you buy, not just the bill you pay.
  • Design temperature — the county beats the zone. The zone values are representative 99% temperatures; your county can sit a few degrees either side. A 5°F difference in design temperature moves the heating load by about 8% — and the capacity at that temperature by more. Get the county figure from your installer and re-check the numbers.

Sources & assumptions

  • Method — cooling load and heating load computed separately from floor area × zone factor × insulation × ceiling × windows (sun and occupants touch cooling only), nominal tons = cooling load ÷ 12,000 rounded UP to the next half ton, heat-to-cool ratio = heating ÷ cooling. Zone factors are localfixerpro's published split-factor table (cooling 24/22/20/18/16 + heating 15/22/28/35/45 BTU/h per sq ft for zones 1-2/3/4/5/6-7), used as the labelled planning basis — the heating-factor disagreement (localfixerpro 28 vs everydaytools ~19.25 vs greencalcs' single-rate 20 in zone 4) is named on the page. Confirmed 2026-11-19 against LocalFixerPro's heat pump size calculator (separate loads, heat-to-cool gauge, NEEP bands) and GreenCalculus' heat pump size calculator (design-temperature capacity method, NEEP + DOE sizing rules). Insulation poor ×1.20 / average ×1.00 / good ×0.85 and ceiling above 8 ft ×(height÷8) are this page's labelled planning factors, consistent with the site's dehumidifier page.
  • NEEP heating-output bands — 100-115% of the heating load at the design temperature with no backup heat, 75-85% with backup, from NEEP's Guide to Sizing & Selecting Air-Source Heat Pumps in Cold Climates (revised 8 April 2020). Confirmed 2026-11-19 against greencalculus and LocalFixerPro, both citing the same NEEP guide. ACCA Manual S cooling limit, as given by the DOE sizing notes quoted on greencalculus: cooling capacity 90-115% of the cooling load. The page does not pad loads — NEEP warns against it, and the bands above are the unpadded targets.
  • Capacity at temperature — this page's labelled linear model between the 47°F rating (tons × 12,000 BTU/h) and the median 5°F capacity: cold-climate 31,000 BTU/h and standard 16,800 for a 3-ton, the medians of the ENERGY STAR certified-models list (29 October 2026), per greencalculus. The standard 3-ton's 17°F figure from the same model (~22,300 BTU/h) sits inside tradecalc's published 22,000-28,000 BTU/h band for a 3-ton at 17°F. Balance point by the hvacbase load-line method: heat loss from zero at 65°F to the full load at the design temperature, met against the capacity line. ENERGY STAR cold-climate criteria (COP ≥1.75 at 5°F, ≥70% of rated capacity at 5°F, ≥8.1 HSPF2) per hvacbase's summary of the ENERGY STAR specification.
  • Size by city (design-temperature method, greencalculus, 30 October 2026) — a 2,000 sq ft two-storey house with average insulation: 2 tons in Seattle or Dallas, 3 tons in Columbus or Boston, 3.5 tons in Chicago or Denver, 4 tons in Minneapolis. The page presents this as greencalculus' published table, not as this tool's output — the zone-factor method sizes the same Seattle house at 3.5 tons, and the difference is named as the field's 2-5 ton spread.
  • SEER2 / HSPF2 minimums — split-system heat pump 14.3 SEER2 / 7.5 HSPF2 nationwide since 1 January 2023 (10 CFR 430.32(c)); single-package 13.4 / 6.7; ENERGY STAR v6.2 split 15.2 SEER2 / 7.8 HSPF2 (+11.0 EER2). Confirmed 2026-11-19 against HVACBase's SEER2 minimums and GreenCalculus' SEER2 calculator (both citing 10 CFR 430.32 and DOE 82 FR 1786).
  • 25C / 25D terminated — the One Big Beautiful Bill Act (P.L. 119-21, signed 4 July 2025) terminated the 25C Energy Efficient Home Improvement Credit for property placed in service after 31 December 2025 and the 25D Residential Clean Energy Credit for expenditures made after 31 December 2025, per IRS Fact Sheet FS-2025-05 (August 2025). Confirmed 2026-11-19 against the IRS fact sheet via Retrofit Relay's heat pump tax credit guide (verified against IRS guidance 15 July 2026, re-checked 12 October 2026) and HVACFixPro's 2026 credit guide. Systems placed in service on or before 31 December 2025 are claimed on IRS Form 5695 with the 2025 return; state/utility rebates (DSIRE database) replace the credit.
  • Metric loads (EN 12831) — 30-50 W/m² for well-insulated homes, 80-120 W/m² for unrenovated pre-1980 buildings; a modern 150 m² house needs about 4.5-7.5 kW, a poorly insulated one 12-18 kW. Confirmed 2026-11-19 against Solimpeks' heat pump sizing guide. The page's 50-80 W/m² middle band is labelled as its interpolation between the two published bands. Old boilers routinely oversized by 50-100% — same source.
  • Design temperatures are representative 99% values per zone (zones 1-2 32°F, zone 3 22°F, zone 4 14°F, zone 5 3°F, zones 6-7 −10°F); the county's figure governs and a ZIP/county lookup is a planned mode, not part of this version. Heat-to-cool ratio bands (green ≤1.25, amber 1.25-2.0, red >2.0) are LocalFixerPro's published bands. Airflow 400-500 CFM/ton and electric strip kits in 5/10/15/20 kW are field standards, stated as such on the page.
  • Canonical example (this tool): 2,000 sq ft, zone 4, average insulation, 8 ft ceilings, average windows and sun, 2 occupants, ducted, no backup — cooling 2,000 × 20 = 40,000 BTU/h (11.72 kW), heating 2,000 × 28 = 56,000 BTU/h (16.41 kW), 3.5 tons, ratio 1.40 (amber), no-backup output 56,000-64,400 BTU/h, with-backup 42,000-47,600, cold-climate 3.5 t at the 14°F design temp 37,417 BTU/h (67%), standard 24,400 (44%), at 5°F cold 36,167 vs standard 19,600, at 17°F cold 37,833 vs standard 26,000, balance point cold ~29.0°F vs standard ~33.4°F, backup gap 5.45 kW → 10 kW kit, airflow 1,400-1,750 CFM, mini-split 4 heads → 12,000 BTU/h each. Metric twin: 186 m² → 11.74 kW cooling / 16.43 kW heating, 3.5 t. Mild: 2,000 sq ft zones 1-2 → 48,000 / 30,000, 4 t, ratio 0.63 (green), standard 4 t at 32°F 38,857 (130%), balance point ~26.2°F (below the design temp), no backup. Minneapolis: 2,000 sq ft zones 6-7 → 32,000 / 90,000, 3 t, ratio 2.81 (red), no-backup 90,000-103,500, cold-climate at −10°F 29,214 (32%), balance point ~36.1°F. 10 ft ceiling: 50,000 / 70,000, 4.5 t.

Figures checked on 28 November 2026 as part of the site-wide test run (3239 automated checks, all passing). See how we calculate and test.

Please note: material estimates are approximate. Always confirm product coverage with the manufacturer and buy a little extra for cuts, waste and future repairs.

What this calculator doesn't do

  • This is a planning estimate, not a Manual J load calculation. It sizes from floor area and climate-zone factors — the method the field's calculator pages use — not from a room-by-room survey of your walls, windows, air leakage and ductwork. ACCA Manual J governs the final size: get one from your installer before you buy, especially above a 1.40 heat-to-cool ratio or below zone 4.
  • The zone factors are rules of thumb for average homes. A tight new build with good insulation and air sealing needs less than the factor table says, and a leaky pre-1980 house with single glazing needs more. The insulation selector moves the answer by ±20%, but it cannot see your actual walls — a blower-door test can.
  • The design temperatures are representative 99% values for the zone — the temperature your area stays above 99% of winter hours. Your county's figure governs, and it can sit a few degrees either side of the zone value: a ZIP/county lookup is a planned mode for this page, not part of this version.
  • The capacity figures are medians of the ENERGY STAR certified-models list (29 October 2026), not any one model's datasheet — a real cold-climate 3-ton can deliver anywhere from about 28,000 to about 36,000 BTU/h at 5°F, and a real standard 3-ton from about 14,000 to about 20,000. Check the exact model's extended-performance table before you order.
  • Mini-split head sizes come from the whole-house cooling load divided by the number of heads. Real heads are sized room by room — a sunny south room takes a bigger head than a shaded north one of the same size — so treat the head figures as a shortlist, not a per-room design.
  • This page sizes the equipment; it does not price it. There is no cost, savings or payback figure here — and no federal tax credit for a 2026 install (see the FAQ). Price the running cost with the heating cost calculator once you have the tons.

Heat Pump Size Calculator — What Size Heat Pump Do I Need? Tons, BTU & kW — frequently asked questions

What size heat pump do I need?

A 2,000 sq ft home in climate zone 4 with average insulation needs a 3.5-ton heat pump — 40,000 BTU/h of cooling (11.7 kW) and 56,000 BTU/h of heating (16.4 kW), with a heat-to-cool ratio of 1.40. The same house is 4 tons in zones 1–2 and 3 tons in zones 6–7 by cooling — but the heating load is what decides the model: 30,000 BTU/h in the mild zones, 90,000 in the very cold ones. Enter your area, zone and insulation above for your exact loads and tons.

How many tons is a 2,000 sq ft house?

2 to 4 tons, depending on the climate — that is the honest answer. By the cooling load: 4 tons in zones 1–2, 4 tons in zone 3, 3.5 tons in zone 4, 3 tons in zone 5 and 3 tons in zones 6–7. By the design-temperature capacity method the same house is 2 tons in Seattle or Dallas, 3 tons in Columbus or Boston, 3.5 tons in Chicago or Denver and 4 tons in Minneapolis. The spread is the field’s, not a mistake — it is why this page shows the cooling tons, the heating load and the capacity at your design temperature separately, and why a Manual J governs the purchase.

What is a good heat-to-cool ratio?

1.25 or below is green, 1.25 to 2.0 is amber, above 2.0 is red. The ratio is the heating load divided by the cooling load: 1.40 on the worked example (56,000 ÷ 40,000). Green means cooling sets the size and a standard model covers the heat. Amber means heating needs more than cooling — check the cold-weather capacity and buy the cold-climate model. Red means heating dominates: a cold-climate model plus backup heat, and a Manual J before you buy. A mild-climate house sits around 0.63; a Minneapolis house around 2.81.

Do I need a cold-climate heat pump?

In zones 4 and above, yes — in zones 1–3, usually not. The difference is the heating output at 5°F: a median cold-climate 3-ton delivers about 31,000 BTU/h and a median standard 3-ton about 16,800 BTU/h (ENERGY STAR certified-models list, 29 October 2026). An ENERGY STAR cold-climate model must hold at least 70% of its rated capacity at 5°F with a COP of at least 1.75, and reach 8.1 HSPF2. At a 14°F design temperature the cold-climate 3.5-ton gives about 37,400 BTU/h against the standard model’s 24,400 — the cheaper unit at the counter is the expensive one all winter.

What is the balance point of a heat pump?

The outdoor temperature where the heat pump’s falling capacity meets the house’s rising heat loss — typically about 25–30°F. On the worked example it is about 29°F for the cold-climate model and 33°F for the standard one. Above the balance point the heat pump heats the house alone; below it, backup heat fills the gap. A lower balance point means fewer backup hours and a lower bill — it is the single number that captures why a cold-climate model pays in a cold climate.

How much backup heat do I need?

The gap between the heating load and what the heat pump delivers at the design temperature, rounded up to the next 5 kW strip kit. On the worked example the gap is 56,000 − 37,417 = 18,583 BTU/h = 5.4 kW, so the next kit is 10 kW. Strip kits come in 5, 10, 15 and 20 kW. With a dual-fuel system the furnace covers the gap instead, and the heat pump shuts off below the balance point — cheaper per BTU than strips, but it needs a gas line and a furnace to maintain.

Can I size a heat pump from my old furnace?

No — the old furnace was almost certainly oversized, and copying its rating buys the wrong heat pump. Old boilers are routinely oversized by 50–100%, and a heat pump’s capacity falls as it gets colder while a furnace’s does not, so a 100,000 BTU/h furnace does not imply a 100,000 BTU/h heat pump. Size from the loads on this page — area times the zone factors, corrected for insulation and ceiling — then confirm with a Manual J load calculation before you buy.

What SEER2 and HSPF2 should I buy?

At least the federal minimums — 14.3 SEER2 and 7.5 HSPF2 for a split-system heat pump (since 1 January 2023) — and higher in a cold climate. ENERGY STAR asks 15.2 SEER2 and 7.8 HSPF2 for a split system, and its cold-climate tier asks 8.1 HSPF2 with a COP of at least 1.75 at 5°F. In a warm climate SEER2 matters more; in a cold one HSPF2 does. A higher rating is a more efficient unit, not a bigger one — the size comes from the loads above, the rating from the label.

Is there still a federal tax credit for heat pumps?

No — for a heat pump installed in 2026 there is no federal residential tax credit at all. The 25C Energy Efficient Home Improvement Credit (30%, up to $2,000 a year for a heat pump) was terminated for property placed in service after 31 December 2025 by the One Big Beautiful Bill Act (P.L. 119-21), per IRS Fact Sheet FS-2025-05; 25D ended on the same date. A system placed in service on or before 31 December 2025 is still claimed on IRS Form 5695 with the 2025 return. What replaces the credit is state and utility rebates — check the DSIRE database for your state before you sign a quote.

What size heat pump for 186 m²? (metric)

11.7 kW of cooling and 16.4 kW of heating — a 3.5-ton unit. 186 m² is 2,002 sq ft, so it is the worked example in metric: zone 4, average insulation, 2.4 m ceilings. In EN 12831 terms, a modern well-insulated 150 m² house needs about 4.5–7.5 kW of heating (30–50 W/m²) and the same floor unrenovated needs 12–18 kW (80–120 W/m²). Enter the area in square metres above and the tool gives you both loads in kW and in BTU/h.

How many kW per m² does a heat pump need? (metric)

30–50 W/m² for a well-insulated home and 80–120 W/m² for an unrenovated one (EN 12831). A modern 150 m² house needs about 4.5–7.5 kW of heating; the same floor unrenovated needs 12–18 kW. Average insulation sits between the two bands, at roughly 50–80 W/m². Those are heating figures — the cooling load in kW is a separate number, and in a warm climate it is the bigger one. Use the tool above with your area in square metres for both loads together.

Next step

Take the tons, the heating load and the cold-climate capacity figures to your installer — and ask for the Manual J and the exact model's extended-performance table (capacity at 17°F and 5°F) before you order, since the medians on this page are not a datasheet. Then price the running cost with the heating cost calculator, and see what insulation would save with the insulation calculator before you buy a bigger unit.

Save this estimate: use the Copy link button in the results box above to share these exact inputs, or Print results for a paper copy to take to the store.